Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 15 1 3 I NCO031836 111 12 I 19/02/08 I17 18 I S I 19 I G I 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70 71 [.. I 72 73 L_LJ74 751 I I I I I I I80
u u
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
09:15AM 19/02/08
12/08/01
Fourth Creek WWTP
693 Bell Farm Rd
Exit Time/Date
Permit Expiration Date
Statesville NC 28687
12:10PM 19/02/08
14/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Kenneth Andrew Galloway/ORC//
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Todd A Smith,PO Box 1111 Statesville INC 28687/Operations Manager/704-878-3438/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Wes Bell uSigned by:
MRO WQ//704-663-1699 Ext.2192/ 2/18/2019
e
E�:96D90CC3437...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger Division of Water Quality//704-2;
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
eyj � 2/18/2019
AtaccsatAFvazs... Page#
NPDES yr/mo/day Inspection Type
NCO031836 I11 12, 19/02/08 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO031836 Owner - Facility: Fourth Creek WWTP
Inspection Date: 02/08/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The permit renewal package was received by the Division on 6/20/12. The Division reissued
the permit on 2/11/19 with an effective date of 3/1/19 and expiration date of 3/31/23.
The City of Statesville implements an approved Industrial Pretreatment Program.
The last compliance evaluation inspection was performed by DWR staff on 10/26/17.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Page# 3
Permit: NCO031836
Inspection Date: 02/08/2019
Record Keeping
Owner - Facility: Fourth Creek WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: The records reviewed durina the inspection were oraanized and well maintained. Discharae
Monitoring Reports (eDMRs) were reviewed for the period January 2018 through December
2018. All monitoring frequencies were correct. A monthly average flow violation was
reported in December 2018. The Division will separately address this limit violation through
the issuance of a Notice of Deficiency (NOD).
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ❑
Comment: Influent and effluent analyses are performed by the City of Statesville's 4th Creek WWTP
Laboratory (Certification #181). Meritech, Inc. (low level mercury and toxicity) has also been
contracted to provide analytical support. The laboratory instrumentation used for field
analyses appeared to be properly calibrated/verified.
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment: The subject permit requires influent BOD and TSS composite samples. The composite
sampler was collecting 350 ml. aliquots and the internal sampler temperature was less than
two degrees Celsius at the time of the inspection. The facility staff perform daily
temperature checks and monthly aliquot calibrations (at a minimum) on the sampler.
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
Page# 4
Permit: NCO031836 Owner - Facility: Fourth Creek WWTP
Inspection Date: 02/08/2019 Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑
representative)?
Comment: The subiect Dermit reauires comDosite and arab effluent samples. The comDosite samDler
was collecting greater than 100 ml. aliquots (at a minimum) and the internal sampler
temperature was less than four Celsius at the time of the inspection. The facility staff
Perform daily temperature checks and monthly aliquot calibrations (at a minimum) on the
sampler.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and ❑ ❑ 0 ❑
sampling location)?
Comment: The Division has conditionally waived the instream monitoring requirements due to the City's
participation in the Yadkin -Pee Dee River Basin Association.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facility appeared to be properly operated and well maintained.
The ORC and staff implement a comprehensive process control program with all
measurements being properly documented and maintained on -site.
The facility is equipped with a SCADA system to assist the wastewater staff with the
facility's operations.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: Both mechanical bar screens were operational and in service.
Screenings are disposed at the County Landfill.
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 5
Permit: NCO031836
Owner - Facility: Fourth Creek WWTP
Inspection Date: 02/08/2019
Inspection Type: Compliance Evaluation
Pump Station - Influent
Yes No NA NE
Is the wet well free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
❑
❑
0
❑
Comment:
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Surface
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
E ❑
❑
❑
Are the diffusers operational?
❑ ❑
0
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
0 ❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑ ❑
0
❑
Comment: Both aeration basin trains were operational and in service. Each aeration basin train is
equipped with six platform aerators.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
■
❑
❑
Page# 6
Permit: NCO031836
Inspection Date: 02/08/2019
Secondary Clarifier
Owner - Facility: Fourth Creek WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: All three secondary clarifiers were oDerational and in service. The sludae blanket levels
were measured at approximately nine feet at the time of the inspection. The periodic wet
weather events and water saturated fields caused the facility to maintain a higher than
normal solids inventory due to the inability to distribute and/or land apply bio-solids. The
facility staff were in the process of lowering the solids inventory due to improved weather
conditions and the ability to land apply bio-solids.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: The total residual chlorine levels in the chlorine contact basin are checked on a daily basis.
One of the three chlorine contact chamber trains was in the process of being drained and
cleaned.
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Comment: Aqueous sodium bisulfite is used for dechlorination.
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Yes No NA NE
Liquid
❑
❑
■
❑
❑
❑
■
❑
■
❑
❑
❑
❑
❑
■
❑
❑
❑
■
❑
Page# 7
Permit: NCO031836 Owner - Facility:
Inspection Date: 02/08/2019 Inspection Type:
Fourth Creek WWTP
Compliance Evaluation
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The flow meter is calibrated twice Der vear and was last calibrated on 9/6/18 by Carolina
Technical Services, Inc.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: The effluent appeared slightly turbid with no foam.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment: The digester is equipped with surface aeration (platform aerators).
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ❑ ■
❑ ❑ ❑ ■
■ ❑ ❑ ❑
Comment: The facility is equipped with a belt press (operational); however, the treatment unit was not in
service at the time of the inspection. Dewatered bio-solids are distributed (Sta-Lime
Process) under the authority of Permit No. WQ0006245. The City also has a Land
Application Permit (WQ0014543) as a back-up disposal option.
Standby Power
Yes No NA NE
Page# 8
Permit: NC0031836
Inspection Date: 02/08/2019
Owner - Facility: Fourth Creek WWTP
Inspection Type: Compliance Evaluation
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
■
■
❑
❑
❑
❑
❑
❑
■
❑
❑
❑
Comment: The generator is put under load once every ten days (at a minimum) and serviced quarterly
by a contracted company (Carolina Power Systems/CAT)
Page# 9
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Mr. Andy Smith
Operations Manager/Water Resources
City of Statesville
Post Office Box 1111
Statesville, North Carolina 28687
Dear Mr. Smith:
NORTH CAROLINA
Environmental Quality
19 February 2019
Subject: Compliance Evaluation Inspection
City of Statesville/Fourth Creek WWTP
NPDES Permit No. NCO031836
Iredell County
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on
February 8, 2019, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible Charge (ORC) of our
findings by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning this report, please do
not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bell(cr�,ncdenr.gov.
Sincerely,
DocuSigned by:
A14CC681 AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure:
Inspection Report
D Q
� North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
NORTH CAROLINA