HomeMy WebLinkAboutNC0066397_Inspection_20190215ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Mr. Steve Boheler, Superintendent
Cleveland County Schools
866 Poplar Springs Church Road
Shelby, NC 28152
Dear Mr. Boheler:
NORTH CAROLINA
EnW&onmrrstgf Qegorrty
February 15, 2019
Subject: Compliance Evaluation Inspection
Casar Elementary School WWTP
NPDES Permit No. NCO066397
Cleveland County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on February 14, 2019, by Ori Tuvia. Timothy Lancaster's cooperation
during the site visit was much appreciated. Please advise the staff involved with this NPDES
Permit by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr.gov.
Sincerely,
DocuSigned by:
A�w H P;z,c.ti.
for
F161FB69A2D84A3...
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
Cc: NPDES, MRO Files (Laserfiche)
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office 1 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115
704 663 1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NCO066397 111 12 I 19/02/14 I17 18 I S i 19 i G i 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved -------------------
67
I 72 I r, I 73I I I74 751 I I I I I I I80
1.0 70Id I 71 tyI I
I —I � I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
12:OOPM 19/02/14
18/09/01
Casar Elementary School WWTP
436 School House Rd
Exit Time/Date
Permit Expiration Date
Casar NC 28020
01:00PM 19/02/14
23/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Timothy Reid Lancaster/ORC/704-487-9087/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Steve Boheler,866 Poplar Springs Church Rd Shelby INC
28152//704-487-9087/7044878943 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Ori A Tuvia 7JI— MRO WQ//704-663-1699/ 2/15/2019
EBB057A2DE017498...
DocuSigned by:
Signature of Management Q A Reviewer Agency/Office/Phone and ax Numbers Date
s-� H M4-t4
2 .15.19
Andrew Pitner MRO WQ//704-663-1699 Ext.21 !F161FB69A2D84A3..
.
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO066397 I11 121 19/02/14 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO066397 Owner - Facility: Casar Elementary School WWTP
Inspection Date: 02/14/2019 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: Subject permit expires on 8/31/2023.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: Records reviewed during the inspection were well organized and maintained. DMR's, COC,
ORC logs and calibration logs were reviewed for the months June 2017 - October 2018.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑
Page# 3
Permit: NCO066397 Owner - Facility: Casar Elementary School WWTP
Inspection Date: 02/14/2019 Inspection Type: Compliance Evaluation
Laboratory
Yes No NA NE
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: PH is measured in house. Pace Labs performs and analyzes all other sampling required by
the subject permit
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: The permit requires effluent -grab samples.
Operations & Maintenance
Yes No NA NE
❑ ❑ M ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility appeared well maintained and operated at the time of the inspection. At the time
of the inspection the visual alarm for the holding tank prior to disinfection was not working.
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment: Septic tank was last pumped on 7/23/2018 by Wesson Septic Tank Service Inc.
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Yes No NA NE
❑ ❑ ❑ ■
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
■ ❑ ❑ ❑
Page# 4
Permit: NCO066397 Owner - Facility:
Casar Elementary School WWTP
Inspection Date: 02/14/2019 Inspection Type:
Compliance Evaluation
Sand Filters (Low rate)
Yes No NA NE
Is the distribution box level and watertight?
0
❑
❑
❑
Is sand filter free of ponding?
0
❑
❑
❑
Is the sand filter effluent re -circulated at a valid ratio?
0
❑
❑
❑
# Is the sand filter surface free of algae or excessive vegetation?
0
❑
❑
❑
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
0
❑
❑
❑
Comment:
Disinfection - UV
Yes No NA NE
Are extra UV bulbs available on site?
0
❑
❑
❑
Are UV bulbs clean?
0
❑
❑
❑
Is UV intensity adequate?
0
❑
❑
❑
Is transmittance at or above designed level?
❑
❑
❑
Is there a backup system on site?
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: Flow meter was calibrated on 11/7/2018 by Fortech Labs.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and ❑ ❑ 0 ❑
sampling location)?
Comment: Discharges into a dry ditch, No upstream or downstream flow.
Page# 5
Permit: NC0066397
Inspection Date: 02/14/2019
Owner - Facility: Casar Elementary School WWTP
Inspection Type: Compliance Evaluation
Page#