Loading...
HomeMy WebLinkAboutNC0066397_Inspection_20190215ROY COOPER Governor MICHAEL S. REGAN Secretary LINDA CULPEPPER Director Mr. Steve Boheler, Superintendent Cleveland County Schools 866 Poplar Springs Church Road Shelby, NC 28152 Dear Mr. Boheler: NORTH CAROLINA EnW&onmrrstgf Qegorrty February 15, 2019 Subject: Compliance Evaluation Inspection Casar Elementary School WWTP NPDES Permit No. NCO066397 Cleveland County Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at the subject facility on February 14, 2019, by Ori Tuvia. Timothy Lancaster's cooperation during the site visit was much appreciated. Please advise the staff involved with this NPDES Permit by forwarding a copy of the enclosed report. The report should be self-explanatory; however, should you have any questions concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia@ncdenr.gov. Sincerely, DocuSigned by: A�w H P;z,c.ti. for F161FB69A2D84A3... W. Corey Basinger Regional Supervisor Mooresville Regional Office Division of Water Resources Cc: NPDES, MRO Files (Laserfiche) State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations Mooresville Regional Office 1 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115 704 663 1699 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 IF I 3 I NCO066397 111 12 I 19/02/14 I17 18 I S i 19 i G i 201 I 211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA ---------------------- Reserved ------------------- 67 I 72 I r, I 73I I I74 751 I I I I I I I80 1.0 70Id I 71 tyI I I —I � I I i Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 12:OOPM 19/02/14 18/09/01 Casar Elementary School WWTP 436 School House Rd Exit Time/Date Permit Expiration Date Casar NC 28020 01:00PM 19/02/14 23/08/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Timothy Reid Lancaster/ORC/704-487-9087/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Steve Boheler,866 Poplar Springs Church Rd Shelby INC 28152//704-487-9087/7044878943 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date DocuSigned by: Ori A Tuvia 7JI— MRO WQ//704-663-1699/ 2/15/2019 EBB057A2DE017498... DocuSigned by: Signature of Management Q A Reviewer Agency/Office/Phone and ax Numbers Date s-� H M4-t4 2 .15.19 Andrew Pitner MRO WQ//704-663-1699 Ext.21 !F161FB69A2D84A3.. . EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type NCO066397 I11 121 19/02/14 117 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# Permit: NCO066397 Owner - Facility: Casar Elementary School WWTP Inspection Date: 02/14/2019 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ 0 ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: Subject permit expires on 8/31/2023. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported CM Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: Records reviewed during the inspection were well organized and maintained. DMR's, COC, ORC logs and calibration logs were reviewed for the months June 2017 - October 2018. Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Page# 3 Permit: NCO066397 Owner - Facility: Casar Elementary School WWTP Inspection Date: 02/14/2019 Inspection Type: Compliance Evaluation Laboratory Yes No NA NE Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees 0 ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: PH is measured in house. Pace Labs performs and analyzes all other sampling required by the subject permit Effluent Sampling Is composite sampling flow proportional? Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: The permit requires effluent -grab samples. Operations & Maintenance Yes No NA NE ❑ ❑ M ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ■ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The facility appeared well maintained and operated at the time of the inspection. At the time of the inspection the visual alarm for the holding tank prior to disinfection was not working. Septic Tank (If pumps are used) Is an audible and visual alarm operational? Is septic tank pumped on a schedule? Are pumps or syphons operating properly? Are high and low water alarms operating properly? Comment: Septic tank was last pumped on 7/23/2018 by Wesson Septic Tank Service Inc. Sand Filters (Low rate) (If pumps are used) Is an audible and visible alarm Present and operational? Yes No NA NE ❑ ❑ ❑ ■ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE ■ ❑ ❑ ❑ Page# 4 Permit: NCO066397 Owner - Facility: Casar Elementary School WWTP Inspection Date: 02/14/2019 Inspection Type: Compliance Evaluation Sand Filters (Low rate) Yes No NA NE Is the distribution box level and watertight? 0 ❑ ❑ ❑ Is sand filter free of ponding? 0 ❑ ❑ ❑ Is the sand filter effluent re -circulated at a valid ratio? 0 ❑ ❑ ❑ # Is the sand filter surface free of algae or excessive vegetation? 0 ❑ ❑ ❑ # Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1) 0 ❑ ❑ ❑ Comment: Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? 0 ❑ ❑ ❑ Are UV bulbs clean? 0 ❑ ❑ ❑ Is UV intensity adequate? 0 ❑ ❑ ❑ Is transmittance at or above designed level? ❑ ❑ ❑ Is there a backup system on site? ❑ ❑ ❑ Is effluent clear and free of solids? 0 ❑ ❑ ❑ Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0 ❑ ❑ ❑ Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: Flow meter was calibrated on 11/7/2018 by Fortech Labs. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, and ❑ ❑ 0 ❑ sampling location)? Comment: Discharges into a dry ditch, No upstream or downstream flow. Page# 5 Permit: NC0066397 Inspection Date: 02/14/2019 Owner - Facility: Casar Elementary School WWTP Inspection Type: Compliance Evaluation Page#