Loading...
HomeMy WebLinkAboutWQ0013027_Inspection_20190108 DocuSign Envelope ID:7426267C-4BB7-4F8A-BE52-7EBF2A4D51 FO ROY COOPED , A ICHAEL S.REGAN .� . Secretary max` LINDA CULPEPPER NORTH CARODNA O+A-tOr Environmental Quality January 28, 2019 Grady W Fulcher The Sea Isle Plantation North Homeowners Association PO Box 989 Atlantic Beach, NC 28512-0989 SUBJECT: Compliance Inspection Report Sea Isle Plantation North WWTP Non-discharge Permit No. WQ0013027 Carteret County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Sea Isle Plantation North WWTP on 1/08/2019. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in Non-discharge Permit No. WQ0013027. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. NorthCaroLngDepsrt rim ntofEnvironmeatalQua?rtp I Diuisionof Water Resources Wilmington Reg•3rLa-Dffioe 1 127 CardirreiDrive Exten son I 1451nr:ngton, NorthCaro-ms28405 "•• 910-796-7215 DocuSign Envelope ID:7426267C-4BB7-4F8A-BE52-7EBF2A4D51 FO If you should have any questions, please do not hesitate to contact Helen Perez with the Water Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at helen.perez@ncdenr.gov. Sincerely, DocuSigned by: E3ABA14AC7DC434... Morella Sanchez-King, Regional Supervisor Water Quality Regional Operations Section Wilmington Regional Office Division of Water Resources, NCDEQ ATTACHMENTS Cc: Uploaded to Laserfiche Dan Fortin - electronic copy NorthCafo Una DepartrnentoffnvironmeatadQualitw I Diuisianof Water Resources Z��p Wilmington Rego noIOffice 1 127 Cardinr lDrivefxtenson I WiHmington. North Caro ina23405 - 910-796-7215 Compliance Inspection Report Permit: WQ0013027 Effective: 04/10/17 Expiration: 03/31/22 Owner: The Sea Isle Plantation North Homeowners Association SOC: Effective: Expiration: Facility: Sea Isle Plantation North WWTP County: Carteret Sea Isle N Dr Region: Wilmington Indian Beach NC 28512 Contact Person: Grady W Fulcher Title: Phone: 252-247-4017 Directions to Facility: Take NC 58 East/North about one mile past Indian Beach. Facility is on the left,prior to Pine Knoll Shores. System Classifications: WW3., Primary ORC: Robert C Howard Certification: 996013 Phone: 252-241-5460 Secondary ORC(s): Daniel Edward Fortin 7180 252-393-8720 On-Site Representative(s): On-site representative Daniel Edward Fortin 252-393-8720 Related Permits: Inspection Date: 01/08/2019 Entry Time: 10:OOAM Exit Time: 11:15AM Primary Inspector: Helen I Perez Phone: 910-796-7387 Secondary Inspector(s): Tom Tharrington Phone Reason for Inspection: Routine Inspection Type: Compliance Evaluation Permit Inspection Type: High Rate Infiltration Facility Status: Compliant ❑ Not Compliant Question Areas: Treatment Flow Measurement-Effluent Treatment Flow Measurement-Influent Miscellaneous Questions Treatment Flow Measurement-Water Treatment Treatment Filters Use Records Record Keeping Treatment Activated Sludge Treatment Sludge Storage/Treatment Treatment Clarifiers Treatment Disinfection End Use-Infiltration Treatment Flow Measurement Treatment Return pumps Standby Power Coastal Requirements (See attachment summary) Page: 1 Permit: WQ0013027 Owner-Facility:The Sea Isle Plantation North Homeowners Association Inspection Date: 01/08/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Inspection Summary: A compliance inspection of the Sea Isle Plantation WWTF was conducted on 01-08-2019. The ORC, RC Howard, Dan Fortin and several other staff members of Fortin Contract Service were present during the inspection.This was a routine inspection and a technical assistance visit by Tom Tharrington. This facility treats wastewater from a STEP collection system.The influent is not a typical waste stream due to the septic tanks and the seasonal residential occupancy. Sporatic violations and three civil penalties have been issued for exceedances of monthly total nitrogen limits since 2016, mostly due to high TKN. Staff have been in contact with the Wilmington Regional Office(WIRO)and has had some technical assistance from Tom Tharrington, but the cause for the high TKN has not been found. During the inspection, samples were collected at various locations of treatment for a nutrient mass balance.Additional sampling will be conducted in the near future and Tom will communicate with ORC with findings. The facility and the high-rate infiltration fields were well maintained. Only one train was in operation due to seasonal low flows.The generator was not powering the plant when in operation,and a call for repair was made the day of the inspection. Please inform WIRO when service is performed and the unit is operational. The effluent composite sample is collected based on time instead of flow proportional due to low flow volumes.After a discussion within the WIRO staff,time based collection for the composite sample will be allowed at this time. Page: 2 Permit: WQ0013027 Owner-Facility:The Sea Isle Plantation North Homeowners Association Inspection Date: 01/08/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Lagoon Spray, LR ❑ Activated Sludge Drip,LR ❑ Single Family Spray, LR ❑ Activated Sludge Spray, LR ❑ Recycle/Reuse ❑ Single Family Drip ❑ Reuse(Quality) ❑ Activated Sludge Spray, HR ❑ Infiltration System Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑ Do all treatment units appear to be operational?(if no,note below.) 0 ❑ ❑ ❑ Comment: No comment. Treatment Flow Measurement-Influent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement-Water Use Records Yes No NA NE Is water use metered? ❑ ❑ ❑ Are the daily average values properly calculated? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement-Effluent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: The flowmeter was calibrated on 4-4-2018 by Delta Systems Environmental. Standby Power Yes No NA NE Is automatically activated standby power available? 0 ❑ ❑ ❑ Page: 3 Permit: WQ0013027 Owner-Facility:The Sea Isle Plantation North Homeowners Association Inspection Date: 01/08/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑ Is generator operable? ❑ ❑ ❑ Does generator have adequate fuel? ❑ ❑ ❑ Comment: Generator starts and operats when power is interupted, but does not power the plant due to a possible control circulatory issue. Company, to repair the generator, was called earlier that morning of inspection. Treatment Activated Sludqe Yes No NA NE Is the aeration mechanism operable? ❑ ❑ ❑ Is the aeration basin thoroughly mixed? ❑ ❑ ❑ Is the aeration equipment easily accessed? ❑ ❑ ❑ Is Dissolved Oxygen adequate? ❑ ❑ ❑ Are Settleometer results acceptable? ❑ ❑ ❑ Is activated sludge an acceptable color? 0 ❑ ❑ ❑ Comment: Process control testing includes settleometer, Nitrate and Ammonia strips. There is an ORP sensor located in each anoxic tank and a DO sensor in each aeration basin. Treatment Clarifiers Yes No NA NE Are the weirs level? ❑ ❑ ❑ Are the weirs free of solids and algae? ❑ ❑ ❑ Is the scum removal system operational? ❑ ❑ ❑ Is the scum removal system accessible? ❑ ❑ ❑ Is the sludge blanket at an acceptable level? ❑ ❑ ❑ Is the effluent from the clarifier free of excessive solids? 0 ❑ ❑ ❑ Comment: No comment. Treatment Return pumps Yes No NA NE Are they in place? 0 ❑ ❑ ❑ Are they operational? 0 ❑ ❑ ❑ Comment: Staff uses 4 telescoping valves located at a common tank to adjust the flow of RAS and nitrate recycle back to the anoxic tanks. Treatment Filters Yes No NA NE Is the filter media present? ❑ ❑ ❑ Is the filter media the correct size and type? ❑ ❑ ❑ Is the air scour operational? ❑ ❑ ❑ Is the scouring acceptable? ❑ ❑ ❑ Is the clear well free of excessive solids? ❑ ❑ ❑ Is the mud well free of excessive solids and filter media? ❑ ❑ ❑ Does backwashing frequency appear adequate? M ❑ ❑ ❑ Page: 4 Permit: WQ0013027 Owner-Facility:The Sea Isle Plantation North Homeowners Association Inspection Date: 01/08/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Comment: No comment. Treatment Sludge Storage/Treatment Yes No NA NE Is the aeration operational? 0 ❑ ❑ ❑ Is the aeration pattern even? 0 ❑ ❑ ❑ If required,are Sanitary"Ts"present in tankage? ❑ ❑ 0 ❑ Comment: Solids from digester are pumped and hauled by Barnes Environmental. Records for 2018 were sent to the Wilmington Regional Office after the inspection. Treatment Disinfection Yes No NA NE Is the system working? ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time(-30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas,does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ Is the chlorinator accessible? ❑ ❑ ❑ If tablets,are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge,solids,and growth? ❑ ❑ ❑ If UV,are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ #Is it a dual feed system? ❑ ❑ ❑ Does the Stationary Source have more than 2500 Ibs of Chlorine(CAS No.7782-50-5)? ❑ ❑ ❑ If yes,then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes,then what is the EPA twelve digit ID Number?(1000- ) If yes,then when was the RMP last updated? Comment: No comment. Record Keeping Yes No NA NE Is a copy of current permit available? ❑ ❑ ❑ Are monitoring reports present: NDMR? ❑ ❑ ❑ NDAR? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are application rates adhered to? ❑ ❑ ❑ Is GW monitoring being conducted,if required(GW-59s submitted)? ❑ ❑ ❑ Are all samples analyzed for all required parameters? ❑ ❑ ❑ Are there any 2L GW quality violations? ❑ 0 ❑ ❑ Page: 5 Permit: WQ0013027 Owner-Facility:The Sea Isle Plantation North Homeowners Association Inspection Date: 01/08/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine Is GW-59A certification form completed for facility? ❑ ❑ ❑ Is effluent sampled for same parameters as GW? ❑ ❑ ❑ Do effluent concentrations exceed GW standards? ❑ ❑ ❑ Are annual soil reports available? ❑ ❑ ❑ #Are PAN records required? ❑ ❑ ❑ #Did last soil report indicate a need for lime? ❑ ❑ ❑ If so,has it been applied? ❑ ❑ ❑ Are operational logs present? ❑ ❑ ❑ Are lab sheets available for review? ❑ ❑ ❑ Do lab sheets support data reported on NDMR? ❑ ❑ ❑ Do lab sheets support data reported on GW-59s? ❑ ❑ ❑ Are Operational and Maintenance records present? ❑ ❑ ❑ Were Operational and Maintenance records complete? ❑ ❑ ❑ Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑ Is a copy of the SOC readily available? ❑ ❑ ❑ No treatment units bypassed since last inspection? 0 ❑ ❑ ❑ Comment: Operational and maintenance logs were present. Reminder to document all activites performed on the facility, including the infiltration field maintenance and residual removal records. A review of groundwater monitoring reports showed no violations since 2014. End Use-Infiltration Yes No NA NE #Is the application High Rate or Low Rate? High Rate Are buffers maintained? ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ Is municipal water available in the area? ❑ ❑ ❑ Are GW monitoring wells required? ❑ ❑ ❑ Are GW monitoring wells located properly w/respect to RIB and CB? ❑ ❑ ❑ Are GW monitoring wells properly constructed,including screened interval? ❑ ❑ ❑ Is a usable green area maintained? 0 ❑ ❑ ❑ Is the disposal site acceptable? ❑ ❑ ❑ Is the distribution equipment acceptable? ❑ ❑ ❑ Is the disposal site free of ponding? ❑ ❑ ❑ Is the disposal site free of breakout? ❑ ❑ ❑ Are the disposal sites free of solids,algae,etc.? ❑ ❑ ❑ Do the records show that the fields are properly maintained? ❑ ❑ ❑ Are the disposal sites free of vegetation? ❑ ❑ ❑ Do any surface water features appear to be adversely impacted by GW discharge? ❑ ❑ ❑ Page: 6 Permit: WQ0013027 Owner-Facility:The Sea Isle Plantation North Homeowners Association Inspection Date: 01/08/2019 Inspection Type:Compliance Evaluation Reason for Visit: Routine No chemicals or rototiller used to eliminate vegetation,solids,algae,etc.? 0 ❑ ❑ ❑ Comment: Fields were well maintained. Please remember to document any maintenance performed on the infiltration fields. Coastal Requirements Yes No NA NE Are essential treatment units provided in duplicate? 0 ❑ ❑ ❑ Is an adequately sized aerated equalization basin present? ❑ ❑ ❑ If so, is it operable? ❑ ❑ ❑ If present,are diffusers cleaned regularly? ❑ ❑ ❑ Is the equalization capacity adequate? 0 ❑ ❑ ❑ Comment: Visual and audio alarms were operational when high water float was pulled at equalization basin. The alarm is connected to a telemetry system which called Dan Fortin during inspection. Page: 7