HomeMy WebLinkAboutNC0071943_Inspection_20190122ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Mike Gibert, Public Works Director
Town of Boiling Springs
2556 Rockyford Road
Boiling Springs, NC 28017
Dear Mr. Gibert:
NORTH CAR-OLINA
Ert0ronmerttal griorlly
January 28, 2019
Subject: Compliance Sampling Inspection
Town of Boiling Springs WWTP
NPDES Permit No. NCO071943
Cleveland County
Enclosed is a copy of the Compliance Sampling Inspection for the inspection conducted at the
subject facility on January 22, 2019 by Ori Tuvia. The cooperation of Todd Humphries and Terry Price
during the site visit was much appreciated. Please advise the staff involved with this NPDES Permit by
forwarding a copy of the enclosed report.
At the time of the inspection, split samples were collected. The results will be forwarded at a later
date.
The report should be self-explanatory; however, should you have any questions concerning this
report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuviakncdenr. _og_v.
Sincerely,
DocuSigned by:
A14CC681 AF27425...
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Water Quality Regional Operations Section
Division of Water Resources
CC: NPDES Unit, MRO Files (Laserfiche)
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
704 663 1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCO071943 111 12 I 19/01/22 I17 18 LC] I 19 I G I 201 I
211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
1.0 70 71 [„ I 72 n 73 L_LJ74 751
u u I I I I I I I80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:05AM 19/01/22
18/09/01
Boiling Springs WWTP
2556 Rockyford Rd
Exit Time/Date
Permit Expiration Date
Boiling Springs NC 28017
11:45AM 19/01/22
23/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Michael Todd Humphries/ORC/704-300-8641/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Mike Gibert,PO Box 1014 Boiling Springs INC 280171014//704-434-2357/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Ori A Tuvia MRO WQ//704-663-1699/ 1/28/2019
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger Division of Water Quality//704-2;
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
1/28/2019
AtaccsatAFz�azs... Page#
NPDES yr/mo/day Inspection Type
N C O071943 I11 121 19/01 /22 117 18 ISI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Split samples were taken during the inspection.
Page#
Permit: NCO071943 Owner - Facility: Boiling Springs WWTP
Inspection Date: 01/22/2019 Inspection Type: Compliance Sampling
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The subject permit expires on 8/31/2023.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CM
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Comment: The records reviewed during the inspection were organized and well maintained. DMRs,
COCs, Calibration logs and ORC visitation logs were reviewed for the
period October 2018
throuah December 2018.
Laboratory
Yes No NA NE
Page# 3
Permit: NCO071943 Owner - Facility: Boiling Springs WWTP
Inspection Date: 01/22/2019 Inspection Type: Compliance Sampling
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: On -site field analyses (pH and temperature) are performed under the Town's laboratory
certification #5013. Pace Analytical Services, Inc. (BOD, TSS, ammonia, nutrients, fecal
coliform) has also been contracted to perform analytical support.
The pH meter appeared to be properly calibrated and documented
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment: Composite sampling of influent BOD and TSS is required by the permit.
The facility staff should implement (and document) periodic aliquot verifications to ensure
that both composite samplers (influent and effluent) are collecting the proper volume as
required in the NPDES Permit (100 mis. at a minimum).
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
0
❑
❑
❑
representative)?
Comment: Composite sampling and grab are required by the permit.
Operations & Maintenance Yes No NA NE
Page# 4
Permit: NCO071943 Owner - Facility: Boiling Springs WWTP
Inspection Date: 01/22/2019 Inspection Type: Compliance Sampling
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility appeared to be properly operated and well maintained. All process control
measurements were being properly documented and maintained on -site.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment:
Grit Removal
Yes
No
NA
NE
Type of grit removal
a.Manual
b.Mechanical
❑
Is the grit free of excessive organic matter?
0
❑
❑
❑
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
0
❑
❑
❑
Comment:
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
E ❑
❑
❑
Are surface aerators and mixers operational?
0 ❑
❑
❑
Are the diffusers operational?
❑ ❑
0
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
0 ❑
❑
❑
Page# 5
Permit: NCO071943 Owner - Facility: Boiling Springs WWTP
Inspection Date: 01/22/2019 Inspection Type: Compliance Sampling
Aeration Basins Yes No NA NE
Is the DO level acceptable?(1.0 to 3.0 mg/1) 0 ❑ ❑ ❑
Comment: Lime is added on an as -needed basis to maintain appropriate pH levels.
At the time of the inspection 1 of the 3 blowers was out of service.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
0
❑
❑
❑
Comment: Both secondaries were in service.
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
❑
❑
❑
Comment:
Disinfection - UV
Yes No NA NE
Are extra UV bulbs available on site?
0
❑
❑
❑
Are UV bulbs clean?
0
❑
❑
❑
Is UV intensity adequate?
0
❑
❑
❑
Is transmittance at or above designed level?
0
❑
❑
❑
Is there a backup system on site?
0
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment:
Page# 6
Permit: NCO071943 Owner - Facility:
Inspection Date: 01/22/2019 Inspection Type:
Boiling Springs WWTP
Compliance Sampling
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
❑
❑
Comment: The flow meter is calibrated twice a vear and was last calibrated on 15/10/2018 by Clear
Water Inc
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: At the time of the inspection the effluent appeared clear with no foam.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
0
❑
❑
❑
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: The facility is equipped with two aerobic digesters with one of the digesters currently being
used as backup. The bio-solids are land applied (by
PRC or staff) under the authority of
permit WQ0018352. In case of excessive rain which
prevents land application the staff
pumps the solids to Shelby WWTP.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment: The standby generator is tested weekly.
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Page# 7
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
Mike Gibert, Public Works Director
Town of Boiling Springs
2556 Rockyford Road
Boiling Springs, NC 28017
Dear Mr. Gibert:
NrORTH CAROL INA
Enrtronmerrfal griorrly
February 22, 2019
Subject: Compliance Sampling Inspection
Town of Boiling Springs WWTP
NPDES Permit No. NCO071943
Cleveland County
Enclosed is a copy of the laboratory results for the effluent samples collected during the
Compliance Sampling Inspection performed at the subject facility on January 22, 2019 by Ori Tuvia. Please
advise the staff involved with this NPDES Permit by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning this
report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvianncdenr.gov.
cc: NPDES, MRO files (Laserfiche)
Sincerely,
DocuSigned by:
cf;:JF��
BB057A2DE017498...
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources, DEQ
D� E
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office 1 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115
704 663 1699
AC59000 North Carolina Division of Water Resources Water Sciences Section Laboratory Results
Loc. Descr.:
14C 00 71943 1301UNG SPRINGS
County_
Cleveland Collector:
0TUVIA
VisitlD
Region:
Mooresville Report To
MRO
Location ID:
MRO NLC
River Basin
Collect Date:
0112212019
Priority
COMPLIANCE
Emergency
CollectTlme:
11:00
Sample Matrix:
SURFACEWATER
COC YesfNo
Sample Depth
Loc. Type:
Effluent
Sample ID:
AC59OOO
PO Number#
Date Received:
0112312019
Time Received:
11:05
Labworks LoginlD
TASCENZO7
Delivery Method
Hand Delivered
Final Report Date:
2.?I19
Report Prirrt Date:
OTOW2619
Final Report
If this report is labeled prefiminary report, the results have not
been validated.
Donor use for Regulatory purposes.
ResuIt'
Method
Analysis
Units
CAS # Analyte Name
PQL
Qualifier
Reference
Date
Validated by
LAB
Sample temperature at receipt by lab
3.2
°C
11=19
RBYRD
MIC
BdD. 5-Day in liquid
2.0
4.B
mg1L
SM 521D 13-2001
1124119
ESTAFFORDI
NUT
NH3 as N in liquid
0.02
3.7
mgiLas N
EPA 35D.1 REV 2
V24M9
CGREEN
NO2+NO3 as N in liquid
0.02
6.4
mglLas N
EPA 353.2 REV 2
1r24M9
CGREEN
Phosphorus total as P in liquid
0.02
1.74
mglLas P
EPA 365.1 REV
11310119
CGREEN
Total Kjeldahl N as N in liquid
02
4.6
mglLas N
EPA 3512 REV 2
V31119
CGREEN
WET
Residue —Total in liquid
12
162
mgiL
SM 254D B-1997
V24119
CGREEN
AC58999 North Carolina Division of Water Resources Water Sciences Section Laboratory Results
Loc. Descr.:
NCO071943 BOILING SPRINGS
County:
Cleveland Collector:
OTUVIA
VisitlD
Region:
Mooresville Report To
MRO
Location ID:
IMRO NLC
River Basin
Collect Date:
0112212019
Priority
COMPLIANCE
Emergency
Collect Time:
10:58
Sam pie Matrix:
SURFACEWATER
COC YesiNo
Sample Depth
Loc. Type:
Effluent
Sample ID:
AC58999
PO Nurn ber#
Date Received:
0112MO19
Time Received:
11:05
Labworks LoginlD
TASCENZOI
Delivery Method
Hand Delivered
Final Report Date:
1f3OhI9
Report Print Date:
01130J2019
If this report is labeled preliminary report, the results have not been validated. Do not use for Regulatory purposes.
Resultf Units Method Analysis
CAS # Analyte Name PQL Qualifier Reference Date Validated by
LAB
Sample temperature at receipt by lab 3.2 °C 1r23119 RBYRD
MIC
COIIfOfm, MF Fecal in liquid 1 1 Q1 CFU110Dm1 SM 9222 0-1997 V23119 ESTAFFORDI
Sample Comments
:Fecal Colifarm-01Sample exceeded holding time prior to receipt at lab.