HomeMy WebLinkAboutWQ0000986_Compliance Evaluation Inspection_20190109DocuSign Envelope ID: 8DlBD38E-D46D-4FBA-8CB4-4229D8E775AC
ROY COOPER
Gmernor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
01te( rot
John H Chapman
Enviracon Utilities Inc
PO Box 610
Tarboro, NC 27886-0610
NORTH CAROLINA
Environmental Quality
January 25, 2019
SUBJECT: Compliance Inspection Report
Island Beach WWTP
Non -discharge Permit No. WQ0000986
Carteret County
DearPermittee:
The North Carolina Division of Water Resources conducted an inspection of the Island Beach WWTP on
January 9, 2019. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non -discharge Permit No. WQ0000986. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection that require immediate action and
therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Dean Hunkele with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
dean. hunkele(5ncdenr.gov.
Sincerely,
DocuSigned by:
E3ABA14ACIDC414_.
Morella Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENT
Cc: Lee Buck, Contract ORC (via email)
Upload to Laserfiche
DMIQNorth Caro: ne Department of Environmental Qua+ity I Dimsion of Water Resources
Wdm.ngton Regonsi Office 1 127 Card-nei Dnve Ertenson I Wilrnington, North Caro:ina 28445
��`��� 910 796-7215
DocuSign Envelope ID: 8D1BD38E-D46D-4FBA-8CB4-4229D8E775AC
Compliance Inspection Report
Permit: WQ0000986 Effective: 01/12/18 Expiration: 12/31/22 Owner: Enviracon Utilities Inc
SOC: Effective: Expiration: Facility: Island Beach WWTP
County: Carteret 2300 W Fort Macon Rd
Region: Wilmington
Atlantic Beach NC 28512
Contact Person: John H Chapman
Title: Vice President
Phone: 252-883-9223
Directions to Facility:
Located on the north side of NC Hwy. 58, approximately
2.1 miles west of the point where the bridge joins the highway in Atlantic
Beach
System Classifications: WW3•,
Primary ORC: Stanley Earl Buck
Certification: 993396
Phone: 252-503-5307
Secondary ORC(s):
John Henry Chapman
15200
252-641-2308
James Richard Proctor
23235
252-253-9938
On -Site Representative(s):
24 hour contact name
Stanley E Buck
252-503-5307
On -site representative
Stanley E Buck
252-503-5307
Related Permits:
WQCSD0634 Enviracon Utilities Inc - Envircon Utilities Deemed Collection System
Inspection Date: 01/09/2019 Entry Time: 12:45PM Exit Time:
Primary Inspector: Dean Hunkele DocuSigned by:
Secondary Inspector(s): EE 1/25/2019
E"do'��,r�Sed� 1/25/2019
Reason for Inspection: Routine Inspection Type:
E
E3ABA14AC7DC434...
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent
Treatment Flow Measurement -Water Treatment
Use Records
Treatment Filters Record Keeping
Treatment Sludge Storage/Treatment Treatment Clarifiers
End Use -Infiltration Treatment Flow Measurement
Coastal Requirements
(See attachment summary)
03:45PM
Phone: 910-796-7215
Compliance Evaluation
Miscellaneous Questions
Treatment Barscreen
Treatment Activated Sludge
Treatment Disinfection
Standby Power
Page: 1
DocuSign Envelope ID: 8D1BD38E-D46D-4FBA-8CB4-4229D8E775AC
Permit: WQ0000986 Owner - Facility: Enviracon Utilities Inc
Inspection Date: 01/09/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
Overall, the facility is looking better and performing good.
The original treatment train needs to have corrosion addressed and any structural repairs completed in the next off-season to
avoid continued degradation that could result in a structural failure like occurred with the other original treatment train several
years and as evidenced by the current seam issue on its original digester. Access grating in some areas need to be
replaced.
It was noted that the main pump station near the plant (assume other pump stations not either) was not properly posted and
did not observe proper signage on WWTF gate. Needs to have an identifier, ownership name/contact info,and full 24-Hour
emergency contact info.
Page: 2
DocuSign Envelope ID: 8D1BD38E-D46D-4FBA-8CB4-4229D8E775AC
Permit: WQ0000986 Owner - Facility: Enviracon Utilities Inc
Inspection Date: 01/09/2019 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
❑
Single Family Drip
❑
Reuse (Quality)
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Lagoon Spray, LR
❑
Infiltration System
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment:
Treatment Flow Measurement -Influent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ ❑
Is flowmeter operating properly?
❑
❑ ❑
Does flowmeter monitor continuously?
❑
❑ ❑
Does flowmeter record flow?
❑
❑ ❑
Does flowmeter appear to monitor accurately?
❑
❑ ❑
Comment
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? ❑ ❑ 0 ❑
Are the daily average values properly calculated? ❑ ❑ 0 ❑
Comment:
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
0
❑
❑ ❑
Is flowmeter operating properly?
0
❑
❑ ❑
Does flowmeter monitor continuously?
0
❑
❑ ❑
Does flowmeter record flow?
❑
❑
❑
Does flowmeter appear to monitor accurately?
❑
❑
❑
Comment: Calibrated 8-7-2018. Need to ensure meter can chart or datalog flows daily with data
downloaded weekly and preserved for at least 3 years
Standby Power
Yes No NA NE
Page: 3
DocuSign Envelope ID: 8D1BD38E-D46D-4FBA-8CB4-4229D8E775AC
Permit: WQ0000986 Owner - Facility: Enviracon Utilities Inc
Inspection Date: 01/09/2019 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is automatically activated standby power available?
0
❑
❑ ❑
Is generator tested weekly by interrupting primary power source?
❑
❑
❑
Is generator operable?
0
❑
❑ ❑
Does generator have adequate fuel?
❑
❑
❑
Comment: Generator looks ancient, but still runs well.
Treatment Barscreen
Yes No NA NE
Is it free of excessive debris?
0
❑
❑ ❑
Is disposal of screenings in compliance?
❑
0
❑ ❑
Are the bars spaced properly?
0
❑
❑ ❑
Is the unit in good condition?
0
❑
❑ ❑
Comment: Screen appears to be too small and perhaps needs to have narrower spacing
as lots of solids
and raps observed in the EQ basin with larger debris snagged on air headers.
Splitter box had
excessive solids in it. Screenings in 5--gallon buckets and on decking; should be removed and
properly disposed of daily.
Treatment Activated Sludge
Yes No NA NE
Is the aeration mechanism operable?
0
❑
❑ ❑
Is the aeration basin thoroughly mixed?
0
❑
❑ ❑
Is the aeration equipment easily accessed?
0
❑
❑ ❑
Is Dissolved Oxygen adequate?
❑
❑
❑
Are Settleometer results acceptable?
❑
❑
❑
Is activated sludge an acceptable color?
M
❑
❑ ❑
Comment: The newer treatment train was not in use due to off-season flows and staff indicated it has air
leaks in the header channel which will be plumbed with external piping before the 2019 season
begins. The older train is exhibiting some heavy corrosion in areas with some structural work
needed including grating replacement: plans should be made to have this work completed in the
next off-season. The old EQ tank should be augmented to prevent rainwater accumulation and
ideally removed from the site along with other unused or broken equipment since site is very tight
given it shares space with the HOA maintenance staff.
Treatment Clarifiers
Yes No NA NE
Are the weirs level?
❑
❑ ❑
Are the weirs free of solids and algae?
❑
❑ ❑
Is the scum removal system operational?
❑
❑ ❑
Is the scum removal system accessible?
0
❑
❑ ❑
Is the sludge blanket at an acceptable level?
❑
❑
❑
Is the effluent from the clarifier free of excessive solids?
0
❑
❑ ❑
Comment: scum removal submer-ged on both
Treatment Filters Yes No NA NE
Is the filter media present? ❑ ❑ 0 ❑
Page: 4
DocuSign Envelope ID: 8D1BD38E-D46D-4FBA-8CB4-4229D8E775AC
Permit: WQ0000986 Owner - Facility: Enviracon Utilities Inc
Inspection Date: 01/09/2019 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is the filter media the correct size and type?
❑
❑
0 ❑
Is the air scour operational?
❑
❑
❑
Is the scouring acceptable?
❑
❑
❑
Is the clear well free of excessive solids?
0
❑
❑ ❑
Is the mud well free of excessive solids and filter media?
0
❑
❑ ❑
Does backwashing frequency appear adequate?
❑
❑
❑
Comment: New filter went online couple months ago
Treatment Sludge Storage/Treatment
Yes No NA NE
Is the aeration operational?
❑
❑
❑
Is the aeration pattern even?
❑
❑
❑
If required, are Sanitary "Ts" present in tankage?
❑
❑
❑
Comment: Converted EQ tank placed on line last year after repair and corrosion coating; looks nice.
Original treatment train's digester has blown a seam/weld along base; plan to repair this year.
Treatment Disinfection
Yes No NA NE
Is the system working?
0
❑
❑ ❑
Do the fecal coliform results indicate proper disinfection?
0
❑
❑ ❑
Is there adequate detention time (-30 minutes)?
❑
❑
❑
Is the system properly maintained?
0
❑
❑ ❑
If gas, does the cylinder storage appear safe?
❑
❑
0 ❑
Is the fan in the chlorine feed room and storage area operable?
❑
❑
0 ❑
Is the chlorinator accessible?
0
❑
❑ ❑
If tablets, are tablets present?
0
❑
❑ ❑
Are the tablets the proper size and type?
❑
❑
❑
Is contact chamber free of sludge, solids, and growth?
0
❑
❑ ❑
If UV, are extra UV bulbs available?
❑
❑
0 ❑
If UV, is the UV intensity adequate?
❑
❑
0 ❑
# Is it a dual feed system?
❑
❑
0 ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
❑
❑
0 ❑
If yes, then is there a Risk Management Plan on site?
❑
❑
❑
If yes, then what is the EPA twelve digit ID Number? (1000-= _)
If yes, then when was the RMP last updated?
Comment: New tablet chlorination system and concrete contact chamber & clear well went online in Sprinq
2018; looks nice. Could smell chlorine even with wind, thus definitely dosing heavy.
Record Keeping Yes No NA NE
Is a copy of current permit available? ❑ ❑ ❑
Are monitoring reports present: NDMR? ❑ ❑ ❑ ❑
Page: 5
DocuSign Envelope ID: 8D1BD38E-D46D-4FBA-8CB4-4229D8E775AC
Permit: WQ0000986 Owner - Facility: Enviracon Utilities Inc
Inspection Date: 01/09/2019 Inspection Type : Compliance Evaluation Reason for Visit: Routine
NDAR?
❑
❑
❑ ❑
Are flow rates less than of permitted flow?
0
❑
❑ ❑
Are flow rates less than of permitted flow?
0
❑
❑ ❑
Are application rates adhered to?
❑
❑
❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
0
❑
❑ ❑
Are all samples analyzed for all required parameters?
0
❑
❑ ❑
Are there any 2L GW quality violations?
0
❑
❑ ❑
Is GW-59A certification form completed for facility?
❑
❑
❑ ❑
Is effluent sampled for same parameters as GW?
0
❑
❑ ❑
Do effluent concentrations exceed GW standards?
0
❑
❑ ❑
Are annual soil reports available?
❑
❑
0 ❑
# Are PAN records required?
❑
❑
0 ❑
# Did last soil report indicate a need for lime?
❑
❑
0 ❑
If so, has it been applied?
❑
❑
0 ❑
Are operational logs present?
❑
❑
❑
Are lab sheets available for review?
❑
❑
❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑
❑ ❑
Are Operational and Maintenance records present?
❑
❑
❑
Were Operational and Maintenance records complete?
❑
❑
❑
Has permittee been free of public complaints in last 12 months?
❑
❑
❑
Is a copy of the SOC readily available?
❑
❑
0 ❑
No treatment units bypassed since last inspection?
❑
❑
❑
Comment: Peak flow about 75K in 2018. Effluent above 2L for Nitrate in 10-2018;
above 2L for TDS past 2
years with wells showing similar exceedences in 2-2018 and 10-2018.
No well data submitted
for 6-2018.
End Use -Infiltration
Yes No NA NE
# Is the application High Rate or Low Rate?
High Rate
Are buffers maintained?
0
❑
❑ ❑
Are any supply wells within the CB?
❑
❑
0 ❑
Are any supply wells within 250' of the CB?
❑
❑
❑
Is municipal water available in the area?
0
❑
❑ ❑
Are GW monitoring wells required?
0
❑
❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑
❑
❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑
❑
Is a usable green area maintained?
0
❑
❑ ❑
Is the disposal site acceptable?
0
❑
❑ ❑
Page: 6
DocuSign Envelope ID: 8D1BD38E-D46D-4FBA-8CB4-4229D8E775AC
Permit: WQ0000986 Owner - Facility: Enviracon Utilities Inc
Inspection Date: 01/09/2019 Inspection Type : Compliance Evaluation
Is the distribution equipment acceptable?
Is the disposal site free of ponding?
Is the disposal site free of breakout?
Are the disposal sites free of solids, algae, etc.?
Do the records show that the fields are properly maintained?
Are the disposal sites free of vegetation?
Do any surface water features appear to be adversely impacted by GW discharge?
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.?
Comment:
Coastal Requirements
Are essential treatment units provided in duplicate?
Is an adequately sized aerated equalization basin present?
If so, is it operable?
If present, are diffusers cleaned regularly?
Is the equalization capacity adequate?
Comment:
Reason for Visit: Routine
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑❑❑■
■❑❑❑
❑❑❑■
❑❑■❑
Yes No NA NE
■❑❑❑
❑❑❑■
❑ ❑ ❑
Page: 7