January 22, 2019
Stan D Bryson
Tuckaseigee Water & Sewer Authority
1246 W Main St
Sylva, NC 28779
SUBJECT: Compliance Inspection Report
Jackson County WWTP
NPDES WW Permit No. NC0039578
Jackson County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Jackson County WWTP
on 1/08/2018. This inspection was conducted to verify that the facility is operating in compliance with
the conditions and limitations specified in NPDES WW Permit No. NC0039578. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact me directly at 828-296-4686 or via email at
mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist I
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
EC: WQS-ARO Server
LF
G:\WR\WQ\Jackson\Wastewater\Municipal\TWSA #1 39578\Inspections\Inspect. Jan. 8, 2018\20190122_NC0039578_CEI.draft
DocuSign Envelope ID: 3FDBBE67-6156-484A-842A-BF57BFF7AAE5
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0039578 18/01/08 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Jackson County WWTP
1871 N River Rd
Sylva NC 28779
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
09:00AM 18/01/08 13/06/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Stan D Bryson/ORC/828-586-9318/
Other Facility Data
01:00PM 18/01/08 17/10/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Stan D Bryson,1246 W Main St Sylva NC 28779//828-586-9318/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Pollution Prevention Facility Site Review
Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Beverly Price ARO WQ//828-296-4500/
Timothy H Heim ARO WQ//828-296-4665/
Mikal Willmer Division of Water Quality//828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 3FDBBE67-6156-484A-842A-BF57BFF7AAE5
1/18/2019
1/18/2019
1/18/2019
NPDES yr/mo/day
18/01/08
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Inspector Mikal Willmer, with the Asheville Regional Office, conducted a compliance evaluation
inspection of the TWSA #1 WWTP on January 8, 2018. This inspection was conducted to determine
whether the facility is being operated and maintained in compliance with NPDES Permit No.
NC0039578. Stan Bryson, TWSA Wastewater Plant Operations Superintendent, was present for the
inspection. Inspectors Bev Price and Tim Heim, with the ARO, assisted in the inspection.
Overall the facility is being operated and maintained in compliance with the current NPDES Permit. No
major findings were noted during the inspection. Inspectors recommended a few additional items at the
time of the inspection.
Float Checks: The facility primarily uses transducers as level alarms; however, floats are used as
back-ups. ORC, Stan Bryson, states they routinely check float operation; however, it is not recorded.
Recommend staff record any and all checks performed for future reference.
Sampler Aliquots: Composite sampler is flow proportional. Currently the aliquot volume dispensed by
the sampler is not checked. A minimum of a 100 mLs should be dispensed during each sample pull.
Recommend checking this annually with a graduated cylinder and adjust as needed.
Flow Measurement: Effluent flow is turbulent directly below the flow meter, which produces inaccurate
measurements. The issue with the flume length and flow meter location was noted after the
prefabricated flume was installed during upgrades. TWSA has been aware of this; however, it cannot
be easily fixed. A stilling well would have to be installed and/or the length of flume would need to be
increased to allow for a quiescent area for flow measurements. This should be addressed in the future
plans for TWSA #1 to provide the facility and permitting unit with more accurate daily flows.
NC0039578 17 (Cont.)
Page#2
DocuSign Envelope ID: 3FDBBE67-6156-484A-842A-BF57BFF7AAE5
Permit:NC0039578
Inspection Date:01/08/2018
Owner - Facility:
Inspection Type:
Jackson County WWTP
Compliance Evaluation
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Annual Report is distributed in the local newspaper.Comment:
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
TWSA analyzes most parameters for their permit. Metals are subcontracted to PACE and
Toxicity is sent to ETS for analysis.
Comment:
Operations & Maintenance Yes No NA NE
Page#3
DocuSign Envelope ID: 3FDBBE67-6156-484A-842A-BF57BFF7AAE5
Permit:NC0039578
Inspection Date:01/08/2018
Owner - Facility:
Inspection Type:
Jackson County WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Monitor tank levels, settleable solids, MLSS, MLVSS, ZSV and SVI. Additionally estimate
lbs/day of WAS.
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Copy of current permit is onsite. TWSA #1's permit is expired, but currently under review in
central office.
Comment:
Influent Sampling Yes No NA NE
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is sampling performed according to the permit?
Influent sampling is time composite. Flow meters are calibrated quarterly. Sample aliquot
volumes are not currently checked. Recommend checking aliquot volume (at least 100 mL)
once a year to ensure a representative sample is being collected.
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Page#4
DocuSign Envelope ID: 3FDBBE67-6156-484A-842A-BF57BFF7AAE5
Permit:NC0039578
Inspection Date:01/08/2018
Owner - Facility:
Inspection Type:
Jackson County WWTP
Compliance Evaluation
Bar Screens Yes No NA NE
Comment:
Grit Removal Yes No NA NE
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Mechanical grit removal is being worked on to extend the life of the wear bar. Debris is being
disposed of in a dumpster on a concrete pad.
Comment:
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Primary means of notification is the SCADA system. A transducer is used for primary level
control with float back-ups. Floats are checked, but not currently recorded. Recommend
staff record any maintenance checks that are occurring.
Comment:
Sequencing Batch Reactors Yes No NA NE
Type of operation:Duplex
Is the reactor effluent free of solids?
Does minimum fill time correspond to the peak hour flow rate of the facility?
Is aeration and mixing cycled on and off during fill?
The operator understands and can explain the process?
One SBR is filling while the other is reacting. Both SBRs waste at the end of a cycle (5
cycles per day). Facility can operate off one SBR if needed. No flow meter on WAS.
Comment:
Equalization Basins Yes No NA NE
Is the basin aerated?
Page#5
DocuSign Envelope ID: 3FDBBE67-6156-484A-842A-BF57BFF7AAE5
Permit:NC0039578
Inspection Date:01/08/2018
Owner - Facility:
Inspection Type:
Jackson County WWTP
Compliance Evaluation
Equalization Basins Yes No NA NE
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
These are post EQ Basins. High level sensors connected to SCADA.Comment:
Disinfection-Liquid Yes No NA NE
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Recently had a leak within the feed line and a pump went down, but have since been
repaired. Contact chambers, post EQ, are cleaned out once a year one side at a time.
Chlorine is fed through the EQ basins to keep algal growth to a minimum.
Comment:
De-chlorination Yes No NA NE
Type of system ?Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Page#6
DocuSign Envelope ID: 3FDBBE67-6156-484A-842A-BF57BFF7AAE5
Permit:NC0039578
Inspection Date:01/08/2018
Owner - Facility:
Inspection Type:
Jackson County WWTP
Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Facility has the flow meters calibrated quarterly. No significant variation in measurements
between calibrations noted. Inspectors did note significant turbulence directly under the
ultrasonic flow meter at the effluent flume. TWSA is aware of the issue, but there is not an
easy solution. A stilling well or extension of the flume would allow for more accurate flow
measurements.
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Sample aliquot volume is not checked. Recommend verifying the sample aliquot volume to
ensure a minimum of a 100 mLs is being pulled. Flow proportional sampling is 20,000
gallons per pulse.
Comment:
Pumps-RAS-WAS Yes No NA NE
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
All pumps are operable, WAS rates are estimated.Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Page#7
DocuSign Envelope ID: 3FDBBE67-6156-484A-842A-BF57BFF7AAE5
Permit:NC0039578
Inspection Date:01/08/2018
Owner - Facility:
Inspection Type:
Jackson County WWTP
Compliance Evaluation
Aerobic Digester Yes No NA NE
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment:
Solids Handling Equipment Yes No NA NE
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Solids from TWSAs plants are aerobically digested before being fed to a belt filter press,
sent to a dryer and distributed under their Class A Residuals Permit WQ0005763.
Comment:
Chemical Feed Yes No NA NE
Is containment adequate?
Is storage adequate?
Are backup pumps available?
Is the site free of excessive leaking?
In the event of a spill, all liquid would drain back to the head of the facility.Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Tested under load Fridays at 0800.Comment:
Page#8
DocuSign Envelope ID: 3FDBBE67-6156-484A-842A-BF57BFF7AAE5
Certificate Of Completion
Envelope Id: 3FDBBE676156484A842ABF57BFF7AAE5 Status: Completed
Subject: Please DocuSign: 20190122_NC0039578_CEI.draft.docx, 20190122_NC0039578_CEI.inspect.pdf
Source Envelope:
Document Pages: 9 Signatures: 1 Envelope Originator:
Certificate Pages: 2 Initials: 3 Mikal Willmer
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-05:00) Eastern Time (US & Canada)
217 W. Jones Street
Raleigh, NC 27699
Mikal.willmer@ncdenr.gov
IP Address: 149.168.204.10
Record Tracking
Status: Original
Jan 18, 2019 | 10:37
Holder: Mikal Willmer
Mikal.willmer@ncdenr.gov
Location: DocuSign
Signer Events Signature Timestamp
Mikal Willmer
mikal.willmer@ncdenr.gov
Environmental Specialist
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)
Signature Adoption: Drawn on Device
Using IP Address: 149.168.204.10
Sent: Jan 18, 2019 | 10:40
Viewed: Jan 18, 2019 | 10:40
Signed: Jan 18, 2019 | 10:41
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
Beverly Price
bev.price@ncdenr.gov
North Carolina Department of Environmental Quality
Security Level: Email, Account Authentication
(None)Signature Adoption: Pre-selected Style
Using IP Address: 149.168.204.10
Sent: Jan 18, 2019 | 10:41
Viewed: Jan 18, 2019 | 10:44
Signed: Jan 18, 2019 | 10:45
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
Tim Heim
tim.heim@ncdenr.gov
DWR
DEQ
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 149.168.204.10
Sent: Jan 18, 2019 | 10:41
Viewed: Jan 18, 2019 | 10:55
Signed: Jan 18, 2019 | 10:55
Electronic Record and Signature Disclosure:
Not Offered via DocuSign
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted Jan 18, 2019 | 10:41
Certified Delivered Security Checked Jan 18, 2019 | 10:55
Signing Complete Security Checked Jan 18, 2019 | 10:55
Completed Security Checked Jan 18, 2019 | 10:55
Payment Events Status Timestamps