HomeMy WebLinkAboutNC0038709_Compliance Evaluation Inspection_20181228 ROY COOPER \OR r'-+CAROLINA Governor Environmental Quality MICHAEL S.REGAN Sea etary LINDA CULPEPPER Interim Director December 28, 2018 Mr. Tommy Spicer Wilkes County Schools 613 Cherry St. North Wilkesboro, NC 28659 Subject: Compliance Evaluation Inspection Roaring River Elementary School WWTP NPDES Permit# NC0038709 Wilkes County Dear Spicer: A Compliance Evaluation Inspection was performed by.Division of Water Resources, Winston Salem Regional Office, staff person Justin Henderson, on December 18, 2018. Mr. Tommy Spicer, Operator in Responsible Charge (ORC), was present for this inspection. This type of inspection consists of two basic parts: an in-office review of the facility files and self-monitoring data and an on-site inspection of the facility. While this inspection mostly reflects compliance with Permit No. NC0038709, the following concerns requires your attention and action: 1) Proper maintenance of the surface sands filters must be performed at a frequency that will prevent ponding of effluent and/or vegetative growth. Weekly raking is highly recommended to comply with Permit Condition Part II Section C. (2.) which requires the Permittee to properly operate and maintain all facilities and systems of treatment and control at all times. 2) Two broken lateral pipes were observed in the surface sand filters during this inspection, and in need of immediate repair. Bi-weekly or monthly observation of sand filter dosing, should be included as routine maintenance. Biological treatment may be adversely impacted by failure to evenly distribute effluent within the treatment filters. 3) The audible component of the effluent pump station alarm failed to operate when tested during this inspection. Immediately repair or replace to ensure proper operation of this audible/visual alarm. All audible/visual alarms should be tested monthly to ensure proper operation at all times. North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office 1450 Hanes Mill Road,Suite 300 I Winston-Salem.North Carolina 27103 336.776 9800 Please refer to the enclosed compliance inspection report form for additional observations and comments. If you have any questions regarding this correspondence, please contact Justin Henderson or me at (336) 776-9800. Sincerel , Sherri V. Knight, P.E. Regional Supervisor Water Quality Regional Operations Divisions of Water Resources enc: BIMS Inspection Report cc: WSRO Central Files NPDES Unit E Q)NO»,F,-r;�t f ep fl,r tof FpWenm ctaf 1;1u37 North Carolina Department of Environmental Quality Division of Water Resources Winston-Salem Regional Office 1450 Hanes Mill Road,Suite 300 Winston-Salem,North Carolina 27103 336.776.9800 - • United States Environmental Protection Agency Form Approved E PA Washington,D C 20460 OMB No.2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A National Data System Coding(i e,PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 L ( LJ 2 I� LJ l 3 I NC0038709 I11 12 I 18/12/18 117 18 I I 19 I s I 20I Li � LI LJ 21IIII I I ICI I III I I I I I I I I I I I I I I I I I I I I I I [ II I I1 111`66 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved 67 I I 70 I I - 71 u 72 l I l 73I I 174 71111111180 Section B Facility Data I-J Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 08 30AM 18/12/18 13/12/01 Roaring River Elementary School Exit Time/Date Permit Expiration Date 283 White Plains Rd 11 OOAM 18/12/18 18/09/30 Roaring River NC 28669 Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data /// Thomas J Spicer/ORC/336-651-4010/ Name,Address of Responsible Official/Title/Phone and Fax Number Contacted Berge Speaks,613 Cherry St North Wilkesboro NC No 28659//336-667-2021/3366679688 Section C.Areas Evaluated During Inspection(Check only those areas evaluated) Permit II Operations&Maintenance II Records/Reports Self-Monitoring Program I. Sludge Handling Disposal • Facility Site Review Effluent/Receiving Waters Laboratory Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s)and Signature(s)of Inspector(s), Agency/Office/Phone and Fax Numbers Date Justin L Henderson WSRO WQ//336-776-9701/ Signature of anag rnt Q A Reviewer Agency/Office/Phone and Fax Numbers Date • I/9/1 EPA Form 3560-3(Rev 9-94)Previous editions are obsolete Page# 1 NPDES yr/mo/day Inspection Type (Cont) 1 31 N C 0038709 111 121 18/12/18 117 18 LI Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) The following concerns were identified during this inspection, and require your attention and action' 1)Vegeative growth and evidence of effluent ponding was observed on the surface of the sand filters. Weekly maintenance including raking of the sand filter shall be performed to prevent this from occunng. 2)Two broken lateral pipes were observed during this inspection resulting in uneven distribution of effluent within the treatment filter. Repair/replace immediately to avoid potential adverse impacts to biological treatment. _ 3)Audible alarm for the efflent pump station failed to perform during testing at the time of this inspection. Replace/repair immediately. Montly testing should be included as part of routine maintenance procedures to ensure proper operation of all alarms at all times. Page# 2 • • Permit: NC0038709 Owner-Facility: Roaring River Elementary School Inspection Date: 12/18/2018 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑ Does the facility analyze process control parameters,for ex MLSS, MCRT, Settleable ❑ ❑ II ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? _ Comment* Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ III ❑ application? Is the facility as described in the permit? • 0 ❑ ❑ #Are there any special conditions for the permit? ❑ ❑ II ❑ Is access to the plant site restricted to the general public'? • ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑ Comment: It is recommended that a fence be constructed to further isolate the septic tank and dosing tank from public access. The dosing tank did contain locks at access points, and the septic tank access lids are fairly heavy currently Pump Station - Effluent Yes No NA NE Is the pump wet well free of bypass lines or structures'? • ❑ ❑ ❑ Are all pumps present'? II ❑ ❑ ❑ Are all pumps operable? • ❑ ❑ ❑ Are float controls operable'? • ❑ ❑ ❑ Is SCADA telemetry available and operational'? ❑ ❑ • ❑ Is audible and visual alarm available and operational'? ❑ • ❑ ❑ Comment: The audible alarm failed to properly operate upon testing at time of inspection Septic Tank Yes No NA NE (If pumps are used) Is an audible and visual alarm operational'? ❑ 0 IN ❑ Is septic tank pumped on a schedule'? • ❑ ❑ ❑ Are pumps or syphons operating properly? • ❑ ❑ ❑ Are high and low water alarms operating properly'? ❑ ❑ • ❑ Comment Sand Filters (Low rate) Yes No NA NE (If pumps are used)Is an audible and visible alarm Present and operational? ❑ ❑ I ❑ Is the distribution box level and watertight? • 0 ❑ ❑ Page# 3 Permit NC0038709 Owner-Facility: Roaring River Elementary School Inspection Date: 12/18/2018 Inspection Type: Compliance Evaluation Sand Filters (Low rate) Yes No NA NE Is sand filter free of ponding? ❑ III ❑ ❑ Is the sand filter effluent re-circulated at a valid ratio'? 0 0 II 0 #Is the sand filter surface free of algae or excessive vegetation'? ❑ • 0 0 #Is the sand filter effluent re-circulated at a valid ratio'?(Approximately 3 to 1) ❑ ❑ II ❑ Comment. Evidence of pondinq and vegetative growth was observed on sand filter surface at time of this inspection. Failure to perform proper maintenace at appropriate frequencies is the likely primary contributor to these observations. Effluent Sampling Yes No NA NE Is composite sampling flow proportional'? ❑ ❑ MI ❑ Is sample collected below all treatment units'? • ❑ 0 ❑ Is proper volume collected'? I 0 ❑ 0 Is the tubing clean'? 0 0 II ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees 0 ❑ U ❑ Celsius)? Is the facility sampling performed as required by the permit(frequency,sampling type • ❑ ❑ ❑ representative)? Comment: Page# 4