HomeMy WebLinkAboutNC0089052_Renewal Application_20190108 4'tseAtAt
,i,,,,...— .,,,,,*0 er, ....1.\
li.
ROY COOPER NORTH CAROLINA
Gore nor Environmental Quality
MICHAEL S_REGAN
Secretary
LINDA CULPEPPER
Interim Director
January 08, 2019
Alec Chaplin,Jr
Zooland Family Campground LLC
PO Box 12187
Columbia, SC 29211
Subject: Permit Renewal
Application No. NC0089052
Zooland Family Campground
Randolph County
Dear Applicant:
The Water Quality Permitting Section acknowledges the December 31, 2018 receipt of your permit renewal application
and supporting documentation. Your application will be assigned to a permit writer within the Section's NPDES WW
permitting branch. Per G.S. 150B-3 your current permit does not expire until permit decision on the application is made.
Continuation of the current permit is contingent on timely and sufficient application for renewal of the current permit.The
permit writer will contact you if additional information is required to complete your permit renewal. Please respond in a
timely manner to requests for additional information necessary to allow a complete review of the application and renewal
of the permit.
Information regarding the status of your renewal application can be found online using the Department of Environmental
Quality's Environmental Application Tracker at:
https://deq.nc.gov/permits-regulations/permit-guidance/environmental-application-tracker
If you have any additional questions about the permit, please contact the primary reviewer of the application using the
links available within the Application Tracker.
Sincerely,
..3CINJA4-41A
Wren Thedford
-
Administrative Assistant
Water Quality Permitting Section
ec: WQPS Laserfiche File w/application
D_EQ
-?),
,„ ,„„ ......,.\.„.,,
North Carolina Department of Environmental Quality I Division of Water Resources
1617 Mail Service Center I Raleigh,North Carolina 27699-1617
919-807-6300
DIEHL & PHILLIPS, P.A.
CONSULTING ENGINEERS WILLIAM C.DIEHL,P.E.
1500 Piney Plains Road,Suite 200 JOHN F.PHILLIPS,P.E.
Cary,North Carolina 27518 ALAN IL KEITH,P.E.
Telephone(919)467-9972—Fax(919)467-5327 RECEIVED/UENR/DWRR
TRANSMITTAL JAN 0 3 2019
December 31, 2018
Water Resources
TO: NC DEQ / DWR/ NPDES Permitting Section
91
FROM: John F. Phillips, P.E.,on behalf of permittee Alec H. Chaplin, Jr.
RE: Renewal Application for NPDES Permit NC0089052
Zooland Family Campground
No. Of Description Remarks
Copies
Please note the description of the existing
wastewater treatment system in the
current issue of this permit is incorrect. The
2 Form D 6/2017 description provided in item 9 of the
enclosed application is correct, and reflects
the system that was approved under the
Authorization to Construct.
Please contact me if you have any questions regarding the enclosed application.
Cc: Mr. Alec H. Chaplin, Jr.
Mr. Alan Gaddis, ORC
NPDES APPLICATION - FORM D
For privately-owned treatment systems treating 100%domestic wastewaters<1.0 MGD
Mail the complete application to:
NC DEQ/DWR/NPDES
1617 Mail Service Center, Raleigh, NC 27699-1617
NPDES Permit NC0089052
If you are completing this form in computer use the TAB key or the up—down arrows to move from one field to
the next. To check the boxes, click your mouse on top of the box. Otherwise,please print or type.
1. Contact Information:
Owner Name Alec H.Chaplin,Jr.
Facility Name Zooland Family Campground
Mailing Address P.O. Box 12187
City Columbia
State/Zip Code S.C.29211
Telephone Number (803)799-9683
Fax Number ( )
e-mail Address alecjr@chaplin-co.com
2. Location of facility producing discharge:
Check here if same address as above 0
Street Address or State Road 3671 Pisgah Covered Bridge Road
City Asheboro
State/Zip Code N.C. 27205
County Randolph
3. Operator Information:
Name of the firm,public organization or other entity that operates the facility. (Note that this is not referring to the
Operator in Responsible Charge or ORC)
Name AG Environmental Management, LLC
Mailing Address 6119 Asheton Drive
City Trinity
State/Zip Code N.C. 27370
Telephone Number (336)5619178
Fax Number ( )
e-mail Address Arg619@northstate.net
1 of 3 Form-D 6I2017
NPDES APPLICATION -FORM D
For privately-owned treatment systems treating 100%domestic wastewaters<1.0 MGD
4. Description of wastewater:
Facility Generating Wastewater(check all that apply):
Industrial ❑ Number of Employees
Commercial ❑ Number of Employees
Residential ❑ Number of Homes
School ❑ Number of Students/Staff
Other Explain: See below
Describe the source(s)of wastewater(example:subdivision, mobile home park,shopping centers, restaurants,
etc.):
Source of wastewater is an RV park/campground. Design flow of the constructed treatment plant is 6,000 gpd,
based on 68 gpd per campsite and a maximum of 88 campsites(design flows were based on water records).
Number of persons served: NA—see flow explanation above
5. Type of collection system
® Separate(sanitary sewer only) ❑Combined (storm sewer and sanitary sewer)
6. Outfall Information:
Number of separate discharge points 1
Outfall identification number(s) 001
Is the outfall equipped with a diffuser? ❑ Yes ►14 No
7. Name of receiving stream(s) (NEW applicants:Provide a map showing the exact location of each outfal):
Little River
8. Frequency of Discharge: ® Continuous ❑ Intermittent
If intermittent:
Days per week discharge occurs: Duration:
9. Describe the treatment system
List all installed components, including capacities,provide design removal for BOD, TSS,nitrogen and
phosphorus. If the space provided Is not sufficient, attach the description of the treatment system in a separate
sheet of paper.
One 8,000 gallon septic tank,one 2,000 gallon flow equalization tank with duplex submersible pumps,
one 9,600 gallon Moving Bed Biofilm Reactor with duplex blowers and diffused aeration system,one
3,500 gallon clarifier,one 1,500 gallon filter feed tank with duplex submersible filter feed pumps, one 24-
inch diameter pressure sand filter,two ultra-violet disinfection systems,one 1,500 gallon clearwell with
duplex submersible filter backwash pumps and diffused post-aeration,alkalinity feed system with duplex
feed pumps,and one 36 KW standby power generator and automatic transfer switch.
Design removals for BOD5—99%removal;TSS—97% removal;Ammonia-N—98%;,TP reduction not
required by NPDES permit
10. Flow Information:
Treatment Plant Design flow 0.006 MGD
2 of 3 Form-D 612017
NPDES APPLICATION -FORM D
For privately-owned treatment systems treating 100%domestic wastewaters<1.0 MGD
Annual Average daily flow 0.002598 MGD (for the previous 3 years)
Maximum daily flow 0.0153 MGD(for the previous 3 years)
11. Is this facility located on Indian country?
❑ Yes g3 No
12. Effluent Data
NEW APPLICANTS:Provide data for the parameters listed. Fecal Coliform, Temperature and pH shall be grab samples,for
all other parameters 24-hour composite sampling shall be used. If more than one analysis is reported,report daily maximum
and monthly average. If only one analysis is reported,report as daily maximum.
RENEWAL APPLICANTS: Provide the highest single reading(Daily Maximum)and Monthly Average over the
past 36 months for parameters currently in your permit. Mark other parameters"N/A"
Parameter Daily Monthly Units of
Maximum Average Measurement
Biochemical Oxygen Demand (BODS) 116 6.17 Mg/L
Fecal Coliform 2420 108 #/100m1
Total Suspended Solids 30.30 2.77 Mg/L
Temperature(Summer) 28.0 24.95 degC
Temperature(Winter) 22 17.13 degC
pH 8.63 8.28 Su
13. List all permits,construction approvals and/or applications:
Type Permit Number Type Permit Number
Hazardous Waste(RCRA) NESHAPS(CAA)
UIC(SDWA) Ocean Dumping(MPRSA)
NPDES 0089052 Dredge or fill(Section 404 or CWA)
PSD(CAA) Other
Non-attainment program(CM)
14. APPLICANT CERTIFICATION
I certify that I am familiar with the information contained In the application and that to the best of my
knowledge and belief such information Is true,complete,and accurate.
Alec H.Chaplin.Jr. Owner
Printed name of Person Signing Title
4- 44° 2_ /2 ( C2//j3
Signature of Applicant �� Date
North Carolina General Statute 143-215.6 )(2)states: Any person who knowingly makes any false statement representation,or certification in any
application,record,report,plan,or other document files or required to be maintained under Article 21 or regulations of the Environmental Management
Commission implementing that Article,or who falsifies,tampers with,or knowingly renders inaccurate any recording or monitoring device or method
required to be operated or maintained under Article 21 or regulations of the Environmental Management Commission implementing that Article,shall be
guilty of a misdemeanor punishable by a fine not to exceed$25,000,or by imprisonment not to exceed six months,or by both. (18 U.S.C.Section 1001
provides a punishment by a fine of not more than$25,000 or imprisonment not more than 5 years,or both,for a similar offense.)
3 of 3 Form-D 612017