HomeMy WebLinkAboutWQ0024756_Permit Correction_20120403NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water. Quality
Reverly Fave� Perdue Chgrler Wakild, P.F. l-eP FrPernpn
4 C C' . u f ►11C� Di► Clo! �CCi U LUi
April 3, 2012
Fred M. Bunn, Manager
FMB 'at the Grove, LLC.
2231 Nash Street, NW, Suite D
Wilson, North Carolina 27896
David Walker, Town Manager
Town of Atlantic Beach
Post Office Box 10
Atlantic Beach, North Carolina 28512
Subject:, Permit No. WQ0024756
The .Grave
Wastewater Treatment and High
Rate Infiltration System
Carteret County
Dear Mr. Bunn. and Mr. Walters:
In accordance with an email request from Mr. Ronald D. Cullipher, PE received on March 27,
2012; we are forwarding herewith a revised permit for the permit issued 'on March 26, 2012. The
corrections to these items are as follows. -
The footnote which reads "Except where a Buffer Waiver Form (BWF 09-02) has been
properly recorded with the Register of Deeds" was inadvertently omitted from the permit
issued March 26, 2012. The footnoted buffer waiver applies to the 50 foot buffers between
the high rate infiltration unit and property lines and public right of ways as well as the 50 foot
buffer between the treatment units and the property lines.
• Condition, II.8 has' -been deleted.
• Condition III.4. has -been revised to read: Adequate measures shall be taken to prevent
effluent ponding in or runoff from the infiltration sites listed in attachment B. If ponding is
experienced, .steps shall be taken to remediate the poorly performing areas.
• ' Condition III.5 has been deleted.
Please replace -the permit issued March 26, 2012 with -the enclosed corrected ' ermit.
LE3
PR 0 4
AQUIFER PROTECTION SECTION 1636 Mail Service Center, Raleigh, North Carolina 27699-1636 Location: 512 N.' Salisbury St., Raleigh. North Carolina 27604�"
One
Phone: 919-807-64641 FAX: 919-807-6496
��-� . _-.�.•
NofthCarohna
Internet: www.ncwaterqualitY.orq � .
An Equal Opportunity 1 Affirmative Action Employer ;VaturaI111-
I
Mr. Bunn and Mr. Walters -
April. 3, 2012
Page 2 of 2
If you need additional information concerning this matter, please contact Alice M. Wessner. at
i l}`1'%'._) l i aa.i 3GL I }
}
Sincerely,
ha s Wakild, P.E.
Attachment: -revised Permit WQ0024756
cc: Carteret County Health Department
Wilmington Regional Office, Aquifer Protection Section
Ronald D. Cullipher, PE, Stroud Engineering, PA., Hestron Plaza Two, 151-A Highway
24, Morehead City, North Carolina 28557
Permit File 'WQ0024756
Notebook File WQ002475 6
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION. -
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
HIGH -RATE INFILTRATION SYSTEM PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General. Statutes of North Carolina as
amended, and other applicable Laws, Rules and Regulations
PERMISSION IS HEREBY GRANTED TO
FMB- at the Grove, LLC.. and Town of Atlantic Beach
Carteret County
FOR THE
continued operation of a 120,000 gallon per day (GPD) wastewater treatment and high rate infiltration
facility consisting of one 36,346 gallon flow equalization basin with two (2) 125 GPM pumps and one 7.5
horsepower (HP) aerator, a manually cleaned bar screen, a flow splitter box, two (2) 58,643 gallon
aeration tanks with two (2) 140 GPM pumps and three (3) 15 HP aerators, two (2) 13,100 gallon clarifiers
each with two 27 GPM waste sludge pumps and each with one 111.11 GPM return sludge pump, a 29,930
gallon sludge holding basin with one 10 GPM pump and three (3) 15 F1P aerators, tertiary treatment to
include one sand filter air scour blower with a 3 HP motor, ultraviolet disinfection, a 3,360 gallon clear
well with two (2) 336 GPM pumps, a 5,446 gallon mudwell with two (2) 50 GPM pumps, an. 11,440
gallon irrigation pump tank with one 152 GPM pump, audible and visual high water alarms, a permanent
auxiliary power source with automatic transfer switch capable of powering 'all essential units and 24,000
square feet of drip irrigation area to serve The Grove, with no discharge. of wastes to surface waters,
pursuant to the permit application name change request received on March 9, 2012 and the minor
modification request received February 10, 2012, and in conformity with the project plans, specifications,
and other supporting data subsequently filed and approved by the Department of Environment and
Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until March 31, 2014, shall void Permit No.
WQ0024756 issudd May 3; 2006 and shall be subject to the following specified conditions and
limitations:
I. SCHEDULES
1. In accordance with. 15A NCAC 02T .0116, upon completion of construction and prior to operation of
this permitted facility, a certification (attached) shall be submitted ' from a licensed North Carolina
Professional Engineer certifying that the permitted facility has been installed in accordance with this
permit, Division approved plans and specifications, and other supporting documentation, including
the location of all monitoring wells as applicable. If this project is to be completed in phases and
partially certified, the Permittee shall retain the responsibility to track further construction approved
under the same permit, and shall provide a final certificate of completion once the. entire project has
been completed. Mail the Certification to the Division of Water Quality, Aquifer Protection Section,
1636 Mail Service Center, Raleigh, NC 27699-1636.
WQ0024456 Version 1.2 Shell Version 120224 Page 1 of 10
2. The Wilmington Regional Office, telephone number (910) 796-7215, shall be notified at least 4$-
hours in advance (excluding weekends and. holidays) of operation of the installed facilities such that
an in -place inspection can be made. Notification to the Aquifer Protection Section's regional
supervisor shall be made from 8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State
Holidays.
3. The Wilmington Regional Office, felenhone,num.ber (91.0) 796-7715_ sha11 a.nprove monitorin.g wellq
PrNJ �1ir_ t� --i" f'?� jit ��ii C2it.:����;ki�l1 `• �t.fC, 1 ii� �!:� i; C,. :1 •f` { 11
beginning waste disposal operations. The regional office shall be notified at least 48 hours prior to
the construction of any monitoring well, and such notification to the Aquifer Protection Section's
regional supervisor shall be made from 8:00 a.m. until 5:00 p.m. on Monday through Friday,
excluding State Holidays. The monitoring wells shall be constructed such that the water level in the
well is never above or below the screened (open) portion of the well at any time during the year, and
in accordance with 15A NCAC 02C .0108. The general location and name for each monitoring well
is marked on Figure A.
4. Within 60 days of completion of the monitoring wells, the Permittee shall submit two original copies
of a site map with a scale no greater than 1-inch equals 100 feet; however, special provisions may be
granted upon prior approval for large properties. At a minimum, the map shall include the following
information:
a. The location and identity of each monitoring well.
b. The location of major components of the waste *disposal system.
c. The location of property boundaries within 500 feet of the disposal areas.
d. The latitude and longitude of the established horizontal control monument.
e. The elevation of the top of the well casing (i.e., measuring point) relative'to a conunon datum..
f. The depth of water below the measuring point at the time the measuring point is
established.
g.. The location of compliance and review boundaries.
h. The date the map is prepared and/or revised,.
Control monuments shall be installed in such a manner and made of such materials that the
monument wi11• not be destroyed due to activities taking place on the property. The map and any
supporting documentation shall be sent to the Division of Water Quality, Aquifer Protection Section,
1636 Mail Service Center, Raleigh, NC 27699-163 6.
5. No later than six months prior to the expiration of this permit, the Permittee shall request renewal of
this permit on official Division forms. Upon receipt of the request, the Division will review the
adequacy of the facilities described therein, and if warranted, will renew the permit for such period of
time and under such conditions and limitations as it may deem appropriate. Please note Rule 15A
NCAC 02T .01 o5(d) requires an updated site map to be submitted with the permit renewal
application. In accordance with Rule-.16A NCAC 02T .0115, the Permittee shall submit a copy of the
declarations and bylaws documenting compliance with the attached Operational.• Agreement.
6. In accordance with 15A NCAC 02H .0404(e), if the subject wastewater treatment or • infiltration
facilities are in noncompliance with the terms and .conditions of this permit, governing statutes or
regulations, the subject facilities shall be connected to an operational publicly owned wastewater
collection system within 180 days of its availability.. Prior to the initiation of these connection
activities, appropriate Division approval shall be -received.
WQ0024456 version 12 Shell Version 120224 Page 2 of 10
;I PERFO CE .STANDARDS. .
1. The subject non -discharge facilities shall be effectively maintained and operated at all times, so there
is no discharge to surface waters, nor any contravention of groundwater, or surface .water standards.
In the event the facilities fail to perform satisfactorily, including the creation of nuisance conditions
due to improper operation and maintenance, or failure of the infiltration areas to adequately assimilate
' Y Z-� .l) f- ) ( {tt i ` !! Y•' i )'
L s. 1.•� .. l i t.. +. Z i l l 7 _� x. i-: r J ..l':. s. ��2 .1 < t..l i. i.t:.�1 L I T� �. 1. ! J { i 1.. 4, �1 i� L.� \l . ... 7 r J j ! l L f .� 1 i ) :
1 1 �.. L! : c i i a L J_ 1 i l i
such as the constructiozz of.aaaxtionai or repiacemenL wastewater Utaw:zenL or ialiozz. �a.cIII ies.
2. This permit shall not relieve the Permittee of their responsibility for damages to groundwater or
surface water resulting from the operation of this facility.
3. All wells constructed for purposes of groundwater monitoring shall be constructed in accordance with
15A NCAC 02C .0108 (Standards of Construction for Wells Other than Water Supply), and any other
jurisdictional laws and regulations pertaining to well construction.
4. The wastewater collection facilities shall be properly maintained and operated at all times. The
Permittee shall maintain compliance with an individual system -wide collection system permit for the
operation and maintenance of these facilities- in accordance with 15A NCAC 02T .0400. If 'an
individual permit is not required, 'the following performance criteria shall be met as provided in 15A
NCAC 02T .0403.
a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to
land or surface waters, and any contravention of groundwater or surface water standards.
b. A map of the sewer system shall be developed and actively maintained.
c. An operation and maintenance plan shall be_ developed, implemented and maintained.
d. Pump stations not connected to a telemetry system shall be inspected every day (i.e., 365 days per
year). Pump stations connected to a telemetry system shall be inspected at least once per week.
e. High -priority sewers shall be inspected at. least once every six months.
f. A. general observation -of the entire sewer system shall be conducted at least once per year.
g. Overflows and bypasses shall be reported to the Wilmington Regional Office in accordance with
15A NCAC 02B .0506(a), and public notice shall be provided as required per North Carolina
General Statute § 143 -215.1 C .
h. A grease control program shall be developed, implemented and maintained.
i. Right-of-ways and easements shall be maintained.
j . Inspection and maintenance records for Conditions II.4.a. through II.4. i. shall be maintained for a
period of at least three years, except for Conditions II.4.b. and II.4.c., which shall be maintained
for the life of the system.
5. Effluent limitations shall not exceed those specified in Attachment A.
6. Application rates, whether hydraulic, nutrient or other pollutant, shall not exceed those specified in
Attachment B.
7. The Operational Agreement (attached) between the Permittee .and the Environmental Management
Commission is incorporated herein by reference and shall be a condition of this permit.
Noncompliance with the terms of the Operational Agreement shall subject the Permittee to all
sanctions provided by North Carolina General Statutes §143-215.6A to §143-215.6C for violation of
or failure to act in accordance with the terms and conditions of this permit.
WQ0024456 Version 1.2 Shell Version 120224 Page 3 of 10
- i
8. A usable green area shall be maintained for effluent disposal. The green area shall have the capability a
Of accommodating the facility's average daily flow. without exceeding the green area- loading rates.
As defined in 15A NCAC 02H .0404(g)(7), a "green area" is an area suitable for waste disposal,
either in its natural state or which has been modified by planting a vegetative cover of grasses or low
growing shrubbery.
9. As a co-Permittee_ the Town of. Atlantic, PeRcb. shall be, HIxf responsible for tl,e e-ncrngcbrn(-,nt
V J'
.-1 .. , st�V.:.1s
;_.`CSr(} �J :��1 : needed. This responsibility shall include full oversight of installation, operation and maintenance of
the sewer line running from the wastewater treatment facility to the green area.
10. The compliance boundary for the disposal system shall be specified in accordance with 15A NCAC
02L .0107(b). This disposal system was individually permitted on or after December 30, 1983;
therefore, the compliance boundary is established at either 250 feet from the effluent. disposal area, or
50 feet within- the property boundary, whichever is closest to the effluent disposal area. An
exceedance of groundwater standards at or beyond the compliance boundary is subject to remediation
action according to 15A NCAC 02L .0106(d)(2) as well as enforcement actions in accordance. with
North Carolina General Statute 143-215.6A through 143-215.6C.
I L In accordance with -15A NCAC 02L .0108; the review boundary is established midway between the
compliance boundary and the effluent disposal area. Any exceedance of groundwater standards at the
review boundary shall require action in accordance with 15A NCAC 02L .0106..
12. The. Permittee shall apply for a. permit modification to establish a new compliance boundary prior to
any sale or transfer of property affecting a compliance boundary.
13. In accordance with 15A NCAC 02L .0107(d), no wells, excluding Division approved monitoring
wells, shall be constructed within the compliance boundary except as provided for in 15A NCAC 02L
.0107(g).
14. Except as provided for in 15A NCAC 02L .0107(g), the Permittee shall ensure any landowner who is
not the Permittee and owns land within the compliance boundary shall execute and file with the
Carteret County Register of Deeds an easement running with the land containing the following items:
a. A notice of the permit and number or other description as allowed in 15A NCAC 02L .0107(fl(1);
b. Prohibits construction and operation of water supply wells within the compliance boundary; and
c. Reserves the right of the Permittee or the State to enter the property within the compliance
boundary for purposes related to the permit.
15. The facilities permitted herein shall be constructed according to the following setbacks:
a. The setbacks for high -rate infiltration sites permitted under 15A NCAC 02T .0700 shall
be as follows (all distances in feet):
i. Any on -property residential units that are to be sold (e.g. condominiums, 10
subdivisions):
ii. Any impounded public surface water supply or public shallow (less than 50 feet
ground water supply: 5 00
deep) grou'
iii. Any private or public water supply source: .100
iv. Any streams classified as wS or B: - 200
v. ' Mean high water and any "SA" or "SB" classified surface waters: 200
vi. Normal high water and any other stream, canal, marsh, or coastal waters: 200
vii. Normal high water and any Class I or Class II impounded reservoir used as a source
drinking water: 200
of
viii. Any other lake or impoundment: 200
WQ0024456 Version 1.2 Shell Version 120224 Page 4 of 10
'' , _ . • The setbacks for high -rate infiltration sites permitted under 15A NCAC 02T .0700 -shall .
be as follows (all distances in feet) continued:
ix. Groundwater lowering ditches (where the bottom of the ditch intersects the SHWT) 200
x. Subsurface. groundwater lowering drainage systems: _ 200
xi. Any property line 5 0 *
xiii. Surface water diversions (ephemeral streams, waterways, ditches50
b. The setbacks for storage and treatment units permitted under 15A NCAC 02T .0700 shall
be as follows (all distances in feet):
50*
i. Any property line:
*Except where a Buffer Waiver Form (BWF 09-02) has been properly recorded with the
Register of Deeds
III. OPERATION AND MAINTENANCE REOU]I EMiENTS
1. The facilities shall be properly. maintained and operated at all times. The facilities shall be effectively
maintained and operated as a non -discharge system to prevent the discharge of any wastewater
resulting from the operation of this, facility. The Permittee shall maintain an Operation and
Maintenance Plan pursuant to 15A NCAC 02T .0707, which at a minimum shall include operational
functions, maintenance schedules, safety measures and a spill response plan.
2. Upon the Water Pollution Control System Operators Certification Commission's (WPCSOCC)
classification of the subject non -discharge facilities, in accordance with 15A NCAC 08G .0200 the
Permittee shall designate and employ a certified operator in responsible charge (ORC) and one or
more certified operator(s) as back-up ORC(s). The ORC or their back-up shall visit the facilities in
accordance with 15A NCAC 08G .0200, and shall comply with all other conditions specified in the
previously cited rules.
3. A suitable year round vegetative cover shall be maintained at all times, such that .crop health is
optimized, allows for even distribution of effluent and allows inspection of the infiltration system.
4. Adequate measures shall be taken to prevent effluent ponding in or runoff from the infiltration sites
listed 'in Attachment B. If ponding is experienced, steps shall be taken to remediate the poorly
performing areas.
5. All infiltration equipment shall be tested and calibrated at least once per permit cycle. Calibration
records shall be maintained at the facility for a period of no less than five years, and shall be made
available to the Division upon request.
6. Only effluent from The Grove WWTF shall be infiltrated on the sites listed in Attachment B.
7. An automatically activated standby power source capable of powering all essential treatment units
shall be on site and operational at all times. If a generatof is employed as an alternate power supply,
it shall be. tested weekly by interrupting the primary power source.
8. No automobiles or machinery shall be allowed on the infiltration sites except during equipment
installation or while maintenance is being performed.
9. Public access to the infiltration sites and wastewater treatment facilities shall be prohibited.
WQ0024456 Version 1.2 Shell Version 120224 Page 5 of 10
`. ...r - ...
J
14
10. The residuals generated from the wastewater treatment facilities shall be disposed or utilized- in
accordance with 15A NCAC 02T .1.100. The Permittee shall maintain a residual "management plan
pursuant to .15A NCAC 02T .0708.
11. Diversion or bypassing of untreated or partially treated wastewater from the treatment facilities is
prohibited.
�. ��(' fF3�•j(1�%f{' l%��i'.iLti;•l �..i,i� r'� r`f n1t ��(, L tY"{`�1 lie
y �a{{', t"tii15�♦. } f'/4i{yt j`f T}*Tilt' \
cr /. ��� L L.L ♦.. Y ; _L ..1� l.. ?i.� e.11ie�J C>[��. A�..1.1 1.1,�1'• ! t '_�e tl tl �,•.�1 ..�...1 _,r _l C.ILI 1 i'
outside toe of • embankment to maximum -allowable temporary storage elevation on the inside of the
embankment), berms, pipe runs., erosion control areas, and surface water diversions. Trees, shrubs,
and other woody vegetation shall not be allowed to grow on the earthen dikes or embankments.
Earthen embankment areas shall be kept mowed or otherwise controlled and accessible.
IV. MONITORING ,AND REPORTING REQUIREMENTS
1. Any Division required monitoring (including groundwater, plant tissue, soil and surface water
-analyses) necessary to ensure groundwater and surface water protection shall be established, and an
acceptable sampling reporting schedule shall be followed.
2. Per 15A NCAC 02H .0800, a Division certified laboratory shall conduct all laboratory analyses for
the required effluent, groundwater or surface water parameters.
3. Flow through the treatment facility shall be continuously monitored, and daily flow values shall be
reported on Form NDMR. •
The Permittee shall install and maintain an appropriate flow measurement device to ensure _ the
accuracy and reliability of flow measurement consistent with accepted engineering and scientific
practices. Selected flow measurement devices shall be capable of measuring flows with a maximum
deviation of less than ten percent from true flow; accurately calibrated at a minimum of once per year;
and maintained to ensure the accuracy of measurements is consistent with the selected device's
accepted capability. The Permittee shall maintain records of flow measurement device calibration on
file for a period of at least five years. At a minimum, documentation shall include:
a." Date of flow measurement device calibration,
b. Name of person performing calibration, and
c. , Percent from true flow.
4. The Permittee shall monitor the effluent -from the subject facilities at the frequencies and
locations for the parameters specified in Attachment A.
5. The Permittee shall maintain adequate records tracking the amount of effluent infiltrated. At a
minimum, these records shall include." the following information for each infiltration site listed in
Attachment B :
a. Date of infiltration.;
b. Volume of effluent infiltrated;
c. Site infiltrated;
d. Length. of time site is infiltrated;
e. Continuous weekly, monthly, and year-to-date hydraulic (inches/acre) loadings;
f. Continuous monthly and year-to-date loadings for any non -hydraulic parameter specifically
limited in Attachment B;
g. Weather conditions; and
h. Maintenance of cover crops.
WQ0024456 Version 12 Shell Version 120224 Page 6 of 10
Three copies of all monitoring data(ass ecifie ' '
g specified m Conditions IV.3. and N.4.) on Form.NbMR for
each PPI and three copies of all operation and disposal records (as specified in . ConditionsIV.5) on
Form NDAR-1 for every site in Attachment B shall be submitted on or before the last day of the
following month. If no activities occurred during the monitoringmonth, monitoring reports are still
g P
required documenting the absence of the activity. All information shall be submitted to the following
address:
-
I I st,01 (n. F.A�,` Q1 I a
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
7. A record shall be maintained of all residuals removed from this facility. -This record shall be
maintained at the facility fora period of no less than five years, and shall be made available to the
Division upon request. At a minimum, this record shall include:
a. Name of the residuals hauler;
b. Non -Discharge permit number authorizing the residuals disposal, or a letter from a municipality
P p ty
agreeing to accept the residuals;
c. Date the residuals were hauled; and
d. Volume of residuals removed-.
8. A maintenance log shall be maintained at this facility. This log shall be maintained at the facility for
a period of no less than five years, and shall be made., available to the Division upon request. At a
minimum, this. log shall include:
a. Date .and results of power interruption testing on alternate power supply;
p
b. Date of calibration of flow measurement device;
c. Visual observations of the plant and plant site; and
d. Record of preventative maintenance (e.g., changing of equipment, adjustments, testing,
inspections and cleanings, etc.).
9. Monitoring wells shall be . sampled after construction and within 3 months prior to initiating non -
discharge disposal operations. Monitoringwells shall be sampled thereafter at the frequencies and for
the parameters specified in Attachment C. All mapping, well construction forms, well abandonment
forms and monitoring data shall refer to the permit number and the well nomenclature as provided in
Attachment C and Figure A.
10. For initial sampling of monitoring wells, the Permittee shall submit a Compliance Monitoring Form
(GW-59) and a Well Construction Record Form (GW-1) listing this permit number and the
appropriate monitoring well identification number. Initial Compliance Monitoring Forms (GW-59)
without copies of the Well Construction Record Forms (GW-1) are deemed incomplete, and may be
returned to the Permittee without being processed.
11. Two copies of the monitoring well sampling and analysis results shall be submitted on a Compliance
Monitoring Form (GW-59), along with attached copies of laboratory analyses, on or before the last
working day of the month following the sampling month. The Compliance Monitoring Form. (GW-
59) shall include this permit number, the appropriate well identification number; and one GW-59a
certification form shall be submitted with each set of sampling results. All information shall be
submitted to the following address:
Division of Water Quality
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
WQ0024456 Version 1.2 Shell Version 120224 Page 7 of 10
V.
An annual representative. soils analysis(i.e., Standard Soil Fertility Analysis) shall be conducted on
12. p Y each infiltration site listed in Attachment B. These, results shall be maintained at the facility for a
period of no less than five ears, and shall be made available to the Division upon request. At a
p Y
minimum, the Standard Soil Fertility Analysis shall include the following parameters:
Acidity
Exchangeable Sodium Percentage
Phosphorus
,� �' tff Y ��., f `a
se s- .f.t_I-1 �I.l.i.t)1i ��'..�, CI.� i{.ia^�
��`�.+�I'i���iijtt:
i
i ii1i�:.�xlafi,
Calcium
Cation Exchange Capacity
Manganese
Sodium
Percent Humic Matter
Zinc
Copper
pH
13. Noncompliance Notification:
The Permittee shall report by telephone to the Wilmington Regional Office, telephone number (910)
796-7215, as soon as possible, but 1n no case more than 24 hours, or on the next working day
following the occurrence or first knowledge of the occurrence of any of the following:
a. Any occurrence at the facility resulting in the treatment of significant amounts of wastes that is
abnormal in quantity or characteristic, including the known passage of a hazardous substance.
b. An process unit failure(e.g.,- mechanical, electrical, etc.}, due to known or unknown reasons,
Yp
rendering the facility incapable of adequate wastewater treatment.
c. Any � facili failure_ resulting in a by-pass directly to receiving surface waters.
d. An time self -monitoring indicates the facility has gone out of compliance with its permit
Y g -
.limitations.
e. Ponding in or runoff from the infiltration sites.
f. Effluent breakout from the infiltration basin(s).
Any emergency requiring immediate reporting (e.g., discharges to surface waters, imminent failure of
a storage structure, etc.) outside normal business hours shall be reported to the Division's Emergency
Response personnel at telephone number. (800) 662-7956, (800) 858-0368,, or (919) 733-3300.
Persons reporting such occurrences by telephone shall also file a written report in letter form within
five days following first knowledge of the occurrence. This report shall outline the actions taken or
proposed to be taken to ensure the problem does not recur.
INSPECTIONS
1. The Permittee shall provide adequate inspection and maintenance to ensure proper operation
of the wastewater treatment and infiltration facilities.
2. The Permittee or their designee shall. inspect the wastewater treatment and infiltration facilities to
p
prevent malfunctions, facility deterioration and operator errors I resulting in discharges, which may
cause the release of wastes to the environment, a, threat to human health or a public nuisance. The
Permittee shall maintain an inspection log that includes, at a minimum, the date and time of
inspection, observations made, and any maintenance, repairs, or corrective actions taken. The
Permittee shall maintain this inspection log for a period of five years from the date of the inspection,
and this log shall be made available to the Division upon request.
I Any duly authorized Division representative may, upon presentation of credentials, enter and inspect
Y property, p
an e remises or place on or related to the wastewater treatment and infiltration. facilities
permitted herein at any reasonable time for the purpose of determining compliance with this permit;
may inspect or copy any records required to be maintained under the terms and conditions of this
permit, and may collect groundwater, surface water or lea•chate samples.
WQ0024456 Version 1.2 Shell Version 120224' Page 8 of 10
vie - GENERAL CONDITIONS
1. Failure to comply with the conditions and limitations contained herein may subject the Permittee to
• _ an enforcement action by the Division in accordance with. North Carolina General Statutes- 143 -
215.6A to 143-215.6C.
�r1�. � //}7i C� '' t.a .=2j cC JTl�� 1i'.r'i�yid' i7 I'"li'l� ?r�C ;i"F> 'i.11j�,�lt?l�¢ y�^jf'(� �ii `:1.���)i:�Caij('.r, \ Jf .
1ft1. �)l1CLi_ �_ 1. 1 t l,L1C 1�J 1� tfi 1. 11 1�.L \_, t_L�.t1 i 1 (tt 1 _ ✓•
tilt conctlaorls of Lolls peri1't, the Division a.ppfovud plans a.lspl4 1���'
documentation.
3. This permit is effective only with respect to the nature and volume of wastes described in the permit
p _ Y p
application;. Division approved plans and specifications, and other supporting documentation. No
variances to applicable rules governing the construction or operation of the permitted facilities are
granted,. unless specifically requested and approved in this permit pursuant -to 15A NCAC 02T
.0105(n).
4. The issuance. of this permit does not exempt the _Permittee from complying with any and all statutes,
rules, regulations, or ordinances, which may be imposed by other jurisdictional government agencies
(e.g., local, state, and federal). 4f particular concern to the Division are applicable -river buffer rules
in 15A NCAC• 02B .0200; erosion and sedimentation control requirements -in 15A NCAC Chapter 4
and under the Division's General Permit NCG010000; any requirements pertaining to wetlands under
15ANCAC` 028` .0200 and 02H .0500; and documentation of compliance with Article 21 Part 6 of
Chapter 143 of the General Statutes.
5. In the event the permitted facilities change ownership or the Permittee changes their name, a formal
permit modification, request shall be submitted to the Division. This request shall be made on official
Division forms, and shall include appropriate property ownership documentation and other supporting
documentation as necessary. The Permittee of record shall remain fully responsible for maintaining
and operating the facilities permitted herein until a permit is issued to the new owner.
6. The Permittee shall retain a set of -Division approved plans and specifications for the life of the
facilities- permitted herein.
7. The Permittee shall maintain this permit until all permitted facilities herein are properly closed or
permitted under another permit issued by the appropriate permitting authority pursuant to 15A NCAC
02T .01050).
8. This permit is subject to revocation or unilateral modification upon 60 days notice from the Division
Director, in whole or part for the requirements listed in' 15A NCAC 02T .0110.
9. Unless the Division Director grants a variance, expansion of the permitted facilities contained herein
shall not be granted if the Permittee exemplifies any of the criteria in 15A NCAC 02T .0120(b).
10. The Permittee shall pay the annual fee within 30 days after being billed by the Division. Failure to
pay the annual fee accordingly shall be cause for the Division to revoke this permit pursuant to 15A
NCAC 02T .0105(e)(3).
Permit issued this the 26th day of March 2012
NORTH CAROLiNA ENVIRONMENTAL MANAGEMENT COMMISSION
�,. axles akild, Director
ivision of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0024756
WQ0024456 Version 12 Shell Version 120224 Page 9 of 10
Permit No. WQ0024756
FMB at the Grove, LLC. and Town of Atlantic Beach
The Grove WWTF
.... '
Wastewater Treatment and High Rate Infiltration
March 26, 2012
Carteret County
ENGINEERING CERTIFICATION
n Partial ❑ Final
In accordance with 15A NCAC 02T .0116,
s lliy)'' if✓t, >7_taCC1.}r�.�.:'`�.i�lf��C1i S:i.l��Ai�.t�i i.i� i.il'� i_}LCI�� t.}! i`tljl��.� �_l�.it.�Li11:i
Permittee' S authorization to periodically weekly I j fully observe the construction of the
permitted facility, hereby state to the best of my abilities that due care and diligence was used in
the observation of the construction, such that the. facility was built within substantial compliance.
and intent of this permit, the Division approved plans and specifications, and other supporting
documentation.
❑ Any variation to this permit, the Division approved plans' and specifications, and other
supporting documentation has been documented in the attached as -built drawings, and shall
serve as the Permittee's minor modification request to amend the permit accordingly.
Provide a brief narrative description of any variations:
THE COMPLETED ENGINEERING CERTIFICATION, INCLUDING ALL
SUPPORTING INFORMATION AND MATERIALS, SHALL BE SENT TO THE
FOLLOWING ADDRESS:
NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL
RESOURCES
DIVISION OF WATER QUALITY
AQUIFLR PROTECTION SECTION
LAND APPLICATION UNIT
By U.S. Postal Service:
By Courier/Secial Delivery:
163 6 MAIL SERVICE CENTER 512 N. SALISBURY ST.
RALEIGH, NORTH CAROLINA 27699-1636 RALEIGH,-NORTH CAROLINA 27604
WQ0024456 Version 1.2 Shell Version 120224 Page 10 of 10
ATTACHMENT A -LIMITATIONS AND MONITORING REQUIREMENTS Permit Number: WQ0024756
PPI 001—The Grove WWTF
V�_- on: 1.2
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
Mo.'N FORING
REQp? :- A_ .EMENTS
Measureme Sample
Frequency- Type
PCS
Code
Parameter Description
Monthly Average
Monthly Geometric
Mean
Daily Minimum
Daily Maximum
50050
Flow, in a conduit or through a treatment plant
105,420
gpd
gpd
gpd
gpd
Continuous
Recorder
00310
BOD, 5-Day (20 Deg. C)
10
mg/l
mg/1
mg/1
mg/1
2.x Month
Composite
00940
Chloride (as Cl)
mg/1
mg/1
mg/1
mg/1
3 x Year2
5 x week
Grab
50060
Chlorine, Total Residual
mg/1
mg/1
mg/1
mg/l
Grab .
31616
Coliform, Fecal MF-FC Broth, 44.5C
14
#/100m1
#/100m1
#/100m1
25
#/100m1
2 x Month
Grab
00610
Nitrogen, Total Ammonia (as N)
4
mg/1
mg/1
mg/1
mg/1
2 x Month'
3 x Year2
Composite
00620
Nitrogen, Nitrate Total (as N)
10
mg/1
mg/1
mg/1
mg/1
Grab
00400
pH
S.U.
S.U.
6
S.U.
9
S.U.
5 x week
3 x Year2
Grab '
70295
Solids, Total Dissolved
trig/1
mg/1
mg/1
mg/1
Grab
00530
Solids, Total Suspended
.20
mg/1
mg/1
mg/l .
mg/1
2 x Month;
Composite
1. 2 x Month sampling frequency only during the months of April through October. During the remainder of the year, these parameters shall be monitored monthly.
2. 3 x Year sampling shall be conducted during February, June and October.
WQ00247 5 6 Version 1.2
THIS PAGE BLANK
1
I
WQ0024756 Version 1.2 Attachment A
i
ATTACHMENT B - APPROVED. LAND APPLICATION SITES
AND LIMITATIONS Permit Number. : WQ0024756 % ersion:l.2
FMB at the Grove, LLC. and Town of Atlantic Beach — The Grove WWTF
INFILTRATION AREA INFORMATION APPLICATION LIMITATI®' '-
Field Owner County Latitude Longitude Net Dominant Hourly Year
Acreage Soil Series Parameter Rate ' Max Units
A FMB at the Grove, LLC. Carteret . 34051'55" 76044'20" 0.55 Corolla 01284 - Non -Discharge Application Rate 0.34 124.1 ixlches
Total 0.55
WQ0024756 Version 1.2
Attachment B
THIS PAGE BLANK
Y
WQ0024756 Version 1.2 Attachment B Page 2 of'2
--------------
ATTACHMENT C — GROUNDWATER MONITORING AND LIMITATIONS
Monitoring wells: MW-.1, MW-2, MW-3
Permit Number: WQ0024756 Ver s ., n: 1.2
GROUNDWATER CHARACTERISTICS
GROUNDWATER STANDARDS
MONITORING REQUIREMENTS
Frequency Measurement Sample Type. Footnotes
PCS Code
Parameter Description
Daily Maximum
82546
Water level, distance from measuring point
feet
3 x year.
Calculated
1,2
00400
pH
6.5-8.5
S.U.
3 x year
Grab'
1,2
31616
Coliform, Fecal MF, M-FC Broth, 44.5 C
# 100/m1
3 x year
Grab
1
1
195
1
70300
Solids, Total Dissolved —180 Deg. C
500
mg/1
3 x year
Grab
00680
Carbon, Total Organic (TOC)
mg/1
3 x year
Grab
.00940
Chloride (as Cl)
250
mg/1
3 x year
Grab
00610
Nitrogen, Ammonia Total (as N)
1500
mg/1
3 x year
Grab
1
00620
Nitrogen, Nitrate Total (as N)
10
mg/1
3 x year
Grab
1
00665
Phosphorus, Total (as P)
mg/l
3 x year
Grab
1
78732
Volatile Compounds (GC/MS)
mg/1
Annually
Grab
1,354
1. 3 x Year monitoring shall be conducted in February, June and & October; Annual monitoring shall be conducted every October. -
2. The measurement of water levels shall be made prior to purging the wells. The depth to water in each well shall be measured from the surveyed point on the top of the ►: -Ig. The measurement
of pH shall be made after purging and prior to sampling for the remaining .parameters.
3. The measuring points (top of well casing) of all monitoring wells shall be surveyed to provide the relative elevation of the measuring point for each monitoring well. Thy° measuring points (top
of casing) of all monitoring wells shall be surveyed relative to a common datum. Volatile Organic Compounds (VOC) - In October only, analyze by one of the following . j -n -thods:
a. Standard Method 6230D, PQL at 0.5 µg/L or less.
b. Standard Method 6210D, PQL at 0.5 µg/L or less
C. EPA Method 8021, Low Concentration, PQL at 0.5 µg/L or less
d. EPA Method 8260, Low Concentration, PQL at 0.5 µg/L or less
e. Another method with prior approval by the Aquifer Protection Section Chief
Any method used must meet the following qualifications:
a. A laboratory must be DWQ certified to run any method used.
b. The method used must, at a minimum, include all the constituents listed in Table VIII of'Standard Method 6230D.
c. The method used must provide a PQL of 0.5 µg/L or less that must be supported by laboratory proficiency studies as required by the DWQ Laboratory Certificati0 iI ' Tnit. `Any constituents:
detected above the MDL but below the PQL of 0.5 µg/L must be qualified (estimated) and reported.
4. If any volatile organic compounds (VOC) are detected as a result of monitoring as provided in Attachment C, then .the Wilmington Regional Office Aquifer Protect oa ' Supervisor, telephone ,.
number (910)796-7215, must be contacted immediately for further instructions regarding any additional follow-up analyses required.
5. If TOC concentrations greater than 10 mg/L are detected in any downgradient monitoring well, additional sampling and analysis must be conducted to identify ta-, e ndividual constituents
comprising this TOC concentration. If the TOC concentration as measured in the background monitor well exceeds 10 mg/L, this concentration will be taken to represe;:01 the naturally occurring
TOC concentration. Any exceedances of this naturally occurring TOC concentration in the downgradient wells shall be subject to the additional sampling and analysis ,:1f,.scribed above.
6. Monitoring wells shall be reported consistent with the nomenclature and location information provided in Figure A and this attachment.
WQ0024756 Version 1.2 Attachment C Page 1 of 2