HomeMy WebLinkAboutNC0025879_Compliance Evaluation Inspection_20181207 North Carolina Department of Environmental Quality | Division of Water Resources 2090 U.S. 70 Highway, Swannanoa, NC 28778 828-296-4500 December 07, 2018 Steve Hooper Town of Robbinsville PO Box 126 Robbinsville, NC 28771 SUBJECT: Compliance Inspection Report Robbinsville WWTP NPDES WW Permit No. NC0025879 Graham County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Robbinsville WWTP on 11/14/2018. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in NPDES WW Permit No. NC0025879. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". Based on the findings at the time of inspection, the facility was determined to be in compliance. The following issues were noted and should be addressed: 1. The composite sampler should be set to flow proportional. 2. The composite sampler should be checked to verify the proper volume of sample is collected. 3. A new thermometer should be placed in the composite sampler. 4. The manufacturer should be contacted for assistance in repairing the UV intensity readout. North Carolina Department of Environmental Quality | Division of Water Resources 2090 U.S. 70 Highway, Swannanoa, NC 28778 828-296-4500 If you should have any questions, please do not hesitate to contact me at 828-296-4500 or via email at bev.price@ncdenr.gov. Sincerely, Beverly Price, Environmental Specialist II Water Quality Regional Operations Section Asheville Regional Office Division of Water Resources, NCDEQ ATTACHMENTS: Inspection Report Ec: Lamar Williams WQS ARO Server LF G:\WR\WQ\Graham\Wastewater\Municipal\Robbinsville WWTP 25879\Inspections\November 15, 2018 CSI\20181207_NC0025879_CSI.docx EPA United States Environmental Protection Agency Washington, D.C. 20460 Water Compliance Inspection Report Form Approved. OMB No. 2040-0057 Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 N 52 NC0025879 18/11/14 S S31112171819 20 21 66 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved------------------- N67707172 73 74 75 80 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES permit Number) Robbinsville WWTP US Hwy 129 Robbinsville NC 28771 Entry Time/Date Permit Effective Date Exit Time/Date Permit Expiration Date 09:10AM 18/11/14 18/11/01 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) /// Everette Lamar Williams//828-498-2211 / Everette Lamar Williams/ORC/828-479-3250/ Other Facility Data 11:45AM 18/11/14 22/11/30 Name, Address of Responsible Official/Title/Phone and Fax Number Steve Hooper,4 Court St Robbinsville NC 287710129/Mayor/828-479-3250/Contacted No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date Beverly Price ARO WQ//828-296-4500/ Mikal Willmer Division of Water Quality//828-296-4686/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page#1 DocuSign Envelope ID: 47EEDDFC-36AB-47D9-BEE7-2030437D4FB8 12/7/2018 12/7/2018 12/7/2018 NPDES yr/mo/day 18/11/14 Inspection Type S3111218 1 Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) The inspection was conducted by Beverly Price and Mikal Willmer of the Asheville Regional Office. Mr. Lamar Williams assisted with the inspection. The following issues were noted during the inspection and should be addressed: 1.The composite sampler should be set to flow proportional. 2.The composite sampler should be checked to verify the proper volume of sample is collected. 3.A new thermometer should be placed in the composite sampler. 4.The manufacturer should be contacted for assistance in repairing the UV intensity readout. The facility installed a new belt-press and lime silo/feed system in 2017 for biosolids treatment. Thirty minute settleable solids results: Plant #1: 30%; Plant #2: 20% Sludge blanket: Plant #1: 2’; Plant #2: 6” Aeration Basin: DO = 2.93 mg/l; pH = 6.36; Temperature = 15.3 degrees C Split Sample Results ARO Lab: TSS = 6.2 mg/l BOD = 2 mg/l Fecal Coliform = 1 colonies/100 mls sample From Central Lab: NH3-N = 0.02 NC0025879 17 (Cont.) Page#2 DocuSign Envelope ID: 47EEDDFC-36AB-47D9-BEE7-2030437D4FB8 Permit:NC0025879 Inspection Date:11/14/2018 Owner - Facility: Inspection Type: Robbinsville WWTP Compliance Sampling Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new application? Is the facility as described in the permit? # Are there any special conditions for the permit? Is access to the plant site restricted to the general public? Is the inspector granted access to all areas for inspection? Not listed in permit description: Coarse bubble diffusers in the aeration zone; post anoxic zone; mechanical bar screen Comment: Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge Judge, and other that are applicable? MLSS, Settleable Solids, Sludge Judge, DOComment: Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Flow meter was calibrated by KDT Services Technologies on 3/16/18Comment: Aerobic Digester Yes No NA NE Is the capacity adequate? Is the mixing adequate? Is the site free of excessive foaming in the tank? # Is the odor acceptable? # Is tankage available for properly waste sludge? Page#3 DocuSign Envelope ID: 47EEDDFC-36AB-47D9-BEE7-2030437D4FB8 Permit:NC0025879 Inspection Date:11/14/2018 Owner - Facility: Inspection Type: Robbinsville WWTP Compliance Sampling Aerobic Digester Yes No NA NE Comment: Solids Handling Equipment Yes No NA NE Is the equipment operational? Is the chemical feed equipment operational? Is storage adequate? Is the site free of high level of solids in filtrate from filter presses or vacuum filters? Is the site free of sludge buildup on belts and/or rollers of filter press? Is the site free of excessive moisture in belt filter press sludge cake? The facility has an approved sludge management plan? Comment: Bar Screens Yes No NA NE Type of bar screen a.Manual b.Mechanical Are the bars adequately screening debris? Is the screen free of excessive debris? Is disposal of screening in compliance? Is the unit in good condition? Comment: Equalization Basins Yes No NA NE Is the basin aerated? Is the basin free of bypass lines or structures to the natural environment? Is the basin free of excessive grease? Are all pumps present? Are all pumps operable? Are float controls operable? Are audible and visual alarms operable? # Is basin size/volume adequate? The basin contains mixers.Comment: Page#4 DocuSign Envelope ID: 47EEDDFC-36AB-47D9-BEE7-2030437D4FB8 Permit:NC0025879 Inspection Date:11/14/2018 Owner - Facility: Inspection Type: Robbinsville WWTP Compliance Sampling Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth) Comment: Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? Are surface aerators and mixers operational? Are the diffusers operational? Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin’s surface? Is the DO level acceptable? Is the DO level acceptable?(1.0 to 3.0 mg/l) Comment: Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? Are UV bulbs clean? Is UV intensity adequate? Is transmittance at or above designed level? Is there a backup system on site? Is effluent clear and free of solids? Page#5 DocuSign Envelope ID: 47EEDDFC-36AB-47D9-BEE7-2030437D4FB8 Permit:NC0025879 Inspection Date:11/14/2018 Owner - Facility: Inspection Type: Robbinsville WWTP Compliance Sampling Disinfection - UV Yes No NA NE There are 2 banks of UV lights. The UV intensity meter was not working; reccomended contacting manufacturer for assistance. UV lamp operating status is indicated by lighting system. If the UV light is operational, the light is on. Comment: Standby Power Yes No NA NE Is automatically activated standby power available? Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? The Town has a contract with Carolina Energy Systems to maintain the generator. The Town has a service contract with Duncan Oil to service the generator. Comment: Effluent Sampling Yes No NA NE Is composite sampling flow proportional? Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? The composite sampler should be set to collect samples proportional to flow. The composite sampler was set to collect 200 mls of sample but when checked during the inspection, only 150 mls were collected. The mercury in the thermometer appeared to be separated making it hard to determine the temperature. Comment: Page#6 DocuSign Envelope ID: 47EEDDFC-36AB-47D9-BEE7-2030437D4FB8 n�fl� e���!��= �� . �� J_J.I_ --=- - �.-. Cha����Mac���� Ar � . .a� ».\ < \, / e t r �` i B ':. _ i �_ . _ ,_ � 'I y� V 1p, . �q" °' ^l� �'. -`� z_ -ram �=� �_� -- -� �`-J �„-�� �. �� 000 � r• 000 Wig:= r x � Y `� ���_. _ IIIIIIIIillilllfi11111\\NNNNNCIR, 7 r �; 2 �-.., �� i e � sa _. OUTPUT DEVICE F a©� AD VET OUOTPUT ENTRR I WA © © a DMODEY SETUP Z MONDOUTPUT KDT Service Technologies In Calibrated-16-MAR-2018 1 Due:MAR-2019 z 828-551-0804 Programming Steps a©o°sao 0©©p®O met soa a TV MOO �K�nA"L. FI.ss_ _. Na..a.if.clions . .�_ atss 0©©OOO ensaoDUE MAR � 1: HER rVEHmans WE W E.,.E .FGHTERATITH To THREAT ET AH,I WWWRHREE � . oEST :,oa..,o INTUrCHETHE EI To IV FIRIMP HARI VE �"wof _.b eo ,.. LET �.. .....••••a -_--- - d• PO Number #ARO Loc. Descr.:WWTP Effluent - Town of Robinsville Loc. Type:EFFLUENT Collector:B PRICE Collect Date:11/14/2018 Collect Time:09:00 Date Received:11/14/2018 Time Received:15:40 Location ID:NC0025879 County:Graham Region:Asheville Labworks LoginID KJIMISON2Sample Matrix:WASTEWATER Report Print Date: North Carolina Division of Water Resources Water Sciences Section Laboratory Results VisitID Sample Depth AROReport To LTNRiver Basin 12/06/2018 Emergency COC Yes/No Sample ID:AC57044 12/5/18Final Report Date: Final Report If this report is labeled preliminary report, the results have not been validated. Do not use for Regulatory purposes. Hand DeliveredDelivery Method COMPLIANCEPriority AC57044 Analysis Date Method Reference Result/ QualifierPQLAnalyte NameCAS #Units Validated by ARO SM 5210 B-2001 ESTAFFORD1mg/LUBOD, 5-Day in liquid 11/15/182.0 2.0 SM 2540 D-1997 ESTAFFORD1mg/LUResidue_Suspended in liquid 11/20/186.2 6.2 RBYRD°CSample temperature at receipt by lab 11/14/184.8 WSS Chemistry Laboratory>> 1623 Mail Service Center, Raleigh, NC 27699-1623 (919) 733-3908 Page 1 of 1 "Not Detected" or "U" does not indicate the sample is analyte free but that the analyte is not detected at or above the PQL. PO Number #ARO Loc. Descr.:WWTP Effluent - Town of Robinsville Loc. Type:EFFLUENT Collector:B PRICE Collect Date:11/14/2018 Collect Time:09:15 Date Received:11/14/2018 Time Received:15:40 Location ID:NC0025879 County:Graham Region:Asheville Labworks LoginID KJIMISON2Sample Matrix:WASTEWATER Report Print Date: North Carolina Division of Water Resources Water Sciences Section Laboratory Results VisitID Sample Depth AROReport To LTNRiver Basin 12/06/2018 Emergency COC Yes/No Sample ID:AC57045 12/5/18Final Report Date: Final Report If this report is labeled preliminary report, the results have not been validated. Do not use for Regulatory purposes. Hand DeliveredDelivery Method COMPLIANCEPriority AC57045 Analysis Date Method Reference Result/ QualifierPQLAnalyte NameCAS #Units Validated by ARO SM 9222 D-1997 ESTAFFORD1CFU/100mlB2Coliform, MF Fecal in liquid 11/14/1811 RBYRD°CSample temperature at receipt by lab 11/14/184.8 WSS Chemistry Laboratory>> 1623 Mail Service Center, Raleigh, NC 27699-1623 (919) 733-3908 Page 1 of 1 "Not Detected" or "U" does not indicate the sample is analyte free but that the analyte is not detected at or above the PQL. PO Number # Loc. Descr.:ROBBINSVILLE WWTP Loc. Type:EFFLUENT Collector:B PRICE Collect Date:11/14/2018 Collect Time:09:00 Date Received:11/16/2018 Time Received:08:05 Location ID:NC0025879 County:Graham Region:Asheville Labworks LoginID TASCENZO1Sample Matrix:WASTEWATER Report Print Date: North Carolina Division of Water Resources Water Sciences Section Laboratory Results VisitID Sample Depth AROReport To LTNRiver Basin 12/03/2018 Emergency COC Yes/No Sample ID:AC57047 11/29/18Final Report Date: Final Report If this report is labeled preliminary report, the results have not been validated. Do not use for Regulatory purposes. NC CourierDelivery Method -NONE-Priority AC57047 Analysis Date Method Reference Result/ QualifierPQLAnalyte NameCAS #Units Validated by LAB MSWIFT°CSample temperature at receipt by lab 11/16/181.1 NUT EPA 350.1 REV 2 CGREENmg/L as NUNH3 as N in liquid 11/16/180.02 0.02 WSS Chemistry Laboratory>> 1623 Mail Service Center, Raleigh, NC 27699-1623 (919) 733-3908 Page 1 of 1 "Not Detected" or "U" does not indicate the sample is analyte free but that the analyte is not detected at or above the PQL.