Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 15 1 3 I NCO047091 111 12 I 18/11/27 I17 18 I S I 19 I G I 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 131 CA ---------------------- Reserved -------------------
671
70 I g 71 I tyI 72 I r I 73 I I 174 751 I I I I I I I80
uI I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
12:OOPM 18/11/27
14/01/01
Silver Maples Community
2812 Plantation Rd
Exit Time/Date
Permit Expiration Date
Concord NC 28027
01:12PM 18/11/27
18/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Dustin Kyle Metreyeon/ORC/704-506-4255/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Logan A Boggs,80 S Lake Ave Pasadena CA 91101//626-795-7755/6264400378
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Roberto Scheller ES� MRO WQ//252-946-6481/ 12/4/2018
91C2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger Division of Water Quality//704-2;
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
12/5/2018
AlaccsalAFvazs... Page#
NPDES yr/mo/day Inspection Type (Cont.)
NCO047091 I11 121 18/11/27 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Permit renewal application not on file -
In accordance with 15A NCAC 2H .0100; .0105 Appllication: Permit Fees: Assessment For New
Sources, (e) Applications for permit renewals shall be accompliched by filing the appropriate
application form, at least 180 days prior to expiration of a permit.
Bar screen needs to be repaired or replaced -
In accordance with your NPDES Permit NC0047091, Part II, Section C, Item 2. Proper Operation and
Maintenance; The Permittee shall at all times properly operate and maintain all facilities and systems of
treatment and control (and related appurtenances) which are installed or used by the Permittee to
achieve compliance with the conditions of this permit.
Flow meter chart recorder not operating properly (not recording flow) -
In Accordance with 15A NCAC 2B .0500; .0505 Monitoring Requirement, (b)(1); All water pollution
control facilities shall install, operate, and maintain continous flow measuring with recording devices..
Page#
Permit: NCO047091 Owner - Facility: Silver Maples Community
Inspection Date: 11/27/2018 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
0
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: This facilitv is a 0.040 MGD wastewater treatment facilitv that discharges into the Rock River
which is class C waters in the Yadkin -Pee Dee River Basin. The permit for this facility
expired on November 30, 2018. During this inspection the ORC requested an extension for
permit renewal. The ORC was directed to the permitting section for permit renewal
extension.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: 30 minute settleable test is used for process control.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
0
❑
❑
❑
Is the site free of excessive foaming in the tank?
E
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: Bio-soilds are removed as needed for disposal by L&L Environmental Services, LLC, of
Charlotte, NC. Bio-solids are hauled to Rocky
River WWTP or land application for final
disposal.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
❑
0
❑
❑
Is the screen free of excessive debris?
❑
0
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
❑
0
❑
❑
Page# 3
Permit: NCO047091
Inspection Date: 11/27/2018
Bar Screens
Owner - Facility: Silver Maples Community
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: It was noted in the previous inspection that the bar screen should be repaired or replaced.
Unit is not in good condition and is missing bars allowing large rags
and debris to enter
treatment units and block air lift pumps..
Primary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the sludge blanket level acceptable?
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
❑
❑
0
❑
Comment:
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
❑ ❑
❑
❑
Are surface aerators and mixers operational?
0 ❑
❑
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
❑ 0
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
❑ ❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑ ❑
❑
Comment: Percent of MLSS was low due to Dlant washout from Rockv River floodina Dlant. Surface of
aeration basin had white foam and appeared to be making
a comeback. ORC indicated that
aeration basin may be reseeded.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0 ❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑ ❑
0
❑
Are weirs level?
0 ❑
❑
❑
Page# 4
Permit: NC0047091 Owner - Facility:
Inspection Date: 11/27/2018 Inspection Type:
Silver Maples Community
Compliance Evaluation
Secondary Clarifier
Yes No NA NE
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
0
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth)
❑
❑
❑
Comment: Effluent was clear with few visible suspended solids going over weir.
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0❑
❑
❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment:
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
0 ❑
❑
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
0 ❑
❑
❑
Comment:
Are the tablets the proper size and type? ❑ ❑ ❑
Are tablet de -chlorinators operational? ❑ ❑ ❑
Number of tubes in use? 2
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ 0 ❑ ❑
Is sample collected below all treatment units? 0 ❑ ❑ ❑
Page# 5
Permit: NCO047091
Inspection Date: 11/27/2018
Owner - Facility: Silver Maples Community
Inspection Type: Compliance Evaluation
Effluent Sampling
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
Comment: At time of inspection effluent sampler was recorded at < 6 degrees Celsius. Flow
measurment is acomplished with V-notch weir and ultrasonic flow meter. It was noted that
chart printer on flow meter was not operating properly at time of inspection.
Page# 6