HomeMy WebLinkAboutNC0030422_Compliance Evaluation Inspection_20181119
North Carolina Department of Environmental Quality | Division of Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
November 19, 2018
James Francis
Green Valley Mobile Home Park
PO BOX 861
Waynesville, NC 28786
SUBJECT: Compliance Inspection Report
Green Valley Mobile Home Park WWTP
NPDES WW Permit No. NC0030422
Haywood County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Green Valley Mobile Home
Park WWTP on November 14, 2018. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0030422. Based on the
site visit, the facility was determined to be in compliance.
The following items were noted during the inspection:
EQ Basin: Significant debris is entering the basin and clogging the submersible pumps. Recommend
taking steps to reduce the amount of trash entering the collection system.
Structural: The facility is showing signs of significant rust throughout the aeration basin and clarifier.
The facility should be repainted to extend the life of the WWTP.
Alarms: Audio and visual high-water alarms are located within a shed. Recommend moving these to a
more conspicuous location.
Flow & Treatment: The system may be short-circuiting during extended pump runs. This should be
further evaluated to assess whether adequate treatment is occurring.
DocuSign Envelope ID: E463CA06-6DE4-49E7-A158-943A80B8CC1A
North Carolina Department of Environmental Quality | Division of Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
Additional findings and comments are provided in the enclosed inspection report. If you should have any
questions, please do not hesitate to contact me at 828-296-4686 or via email at mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
EC: WQS-ARO Server
LF
G:\WR\WQ\Haywood\Wastewater\Minors\Green Valley MHP 30422\Inspections\Inspect. Nov. 14, 2018\20181119_NC0030422_CEI
DocuSign Envelope ID: E463CA06-6DE4-49E7-A158-943A80B8CC1A
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0030422 18/11/14 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Green Valley Mobile Home Park
201 Freeman Rd
Waynesville NC 28786
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
01:30PM 18/11/14 16/02/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Joedavid Matthew Hall/ORC/828-586-5588/
Other Facility Data
02:30PM 18/11/14 20/01/31
Name, Address of Responsible Official/Title/Phone and Fax Number
James H Francis,PO Box 861 Waynesville NC 28786///Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Beverly Price ARO WQ//828-296-4500/
Mikal Willmer Division of Water Quality//828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: E463CA06-6DE4-49E7-A158-943A80B8CC1A
11/19/2018
11/19/2018
11/19/2018
NPDES yr/mo/day
18/11/14
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Inspectors Mikal Willmer and Beverly Price, with the Asheville Regional Office, conducted a
compliance evaluation inspection of the Green Valley MHP WWTP on November 14, 2018. This
inspection was conducted to determine whether the facility is being operated and maintained in
compliance with NPDES Permit No. NC0030422. ORC Joedavid Hall, with Environmental Inc., was
present and assisted in the inspection.
The facility is being maintained in compliance with NPDES Permit No. NC0030422; however, there
were several items of note that should be addressed to help maintain consistent compliance.
The system may be short-circuiting when the pumps kick on for an extended period of time. During the
inspection, the continuous discharge from the EQ basin into the Aeration Basin significantly raised the
water level within the clarifier effluent launder and the chlorine contact basin. This should be further
evaluated to assess whether adequate treatment is occuring during these flow events.
EQ Basin: Significant debris is entering the EQ Basin from the MHP collection system. ORC reports
this frequently clogs the pumps. Steps should be taken to reduce the amount of trash and debris
entering the collection system to prevent long term damage to the WWTP. Since the bar screen is not
easily accessible, this would help reduce the hours required to maintain the EQ basin.
Audio & Visual Alarms: The audio and visual high-water alarms are located within a shed and not
visible to passersby. Recommend moving these to a conspicuous location to help alert Green Valley
staff and residents to notify plant personnel.
Aeration Basin/Clarifier: The WWTP is showing age related wear and corrosion. Recommend painting
the facility to prevent further deterioration and prolong the life of the plant.
Chlorine and Dechlor tubes: Recommend additional caps to prevent extraneous flow from entering the
system.
Chlorine Contact Chamber: concrete is beginning to spall from the chamber and baffles are beginning
to rust.
NC0030422 17 (Cont.)
Page#2
DocuSign Envelope ID: E463CA06-6DE4-49E7-A158-943A80B8CC1A
Permit:NC0030422
Inspection Date:11/14/2018
Owner - Facility:
Inspection Type:
Green Valley Mobile Home Park
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
ORC has the ability to wash down treatment components. Green Valley staff maintain and
remove the trash from the bar screen in the EQ basin. The bar screen is not easily
accessible.
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
A manual bar screen sits below the influent pipe to the EQ basin to catch incoming debris.
The bar screen appears to be undersized and/or inadequate to handle the incoming debris.
ORC reports pumps continually clog from debris within the EQ basin. The bar screen is not
easily accessible for cleaning. The permittee to should attempt to reduce the amount of
debris entering the collection system.
Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Facility has instantaneous flow monitoring. ORC calculates flow based on volume over time.Comment:
Page#3
DocuSign Envelope ID: E463CA06-6DE4-49E7-A158-943A80B8CC1A
Permit:NC0030422
Inspection Date:11/14/2018
Owner - Facility:
Inspection Type:
Green Valley Mobile Home Park
Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
Equalization Basins Yes No NA NE
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Pumps and floats are operable. Grease is beginning to build up within the EQ basin. Audio
and visual alarms are present; however, they are located inside the shed that houses the
blowers. Recommend moving the alarms outside since telemetry is not installed. The basin
is cleaned out twice a year.
Comment:
Aeration Basins Yes No NA NE
Mode of operation Plug flow
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Only one of the blowers is operational. ORC reports they are in the process of repairing the
second motor. Blower cycles on for 15 minutes and off for 45 minutes.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Page#4
DocuSign Envelope ID: E463CA06-6DE4-49E7-A158-943A80B8CC1A
Permit:NC0030422
Inspection Date:11/14/2018
Owner - Facility:
Inspection Type:
Green Valley Mobile Home Park
Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
Pin floc was visible and exiting the clarifier when EQ pumps were active.Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
The ORC can aerate the sludge holding tank as needed. No reported issue with storage
capacity of solids. Solids are removed twice a year.
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?1
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
Comment:
De-chlorination Yes No NA NE
Type of system ?Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Page#5
DocuSign Envelope ID: E463CA06-6DE4-49E7-A158-943A80B8CC1A
Permit:NC0030422
Inspection Date:11/14/2018
Owner - Facility:
Inspection Type:
Green Valley Mobile Home Park
Compliance Evaluation
De-chlorination Yes No NA NE
Number of tubes in use?1
Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Facility is only required to collect grab samples. ORC collects samples from the effluent
pipe. Recommend removing some of the debris near the effluent pipe to improve
accessibility.
Comment:
Page#6