HomeMy WebLinkAboutNC0023191_Inspection_20181102NORTH CAROL NA
ROY COOPER Errvrranrh#1t1G1 QUdlfly
G&V 01tw
MICHAEL S. REGAL
Secr�rary
LfNDA CULPEPPER
In redm D,'rsctor
2 November 2018
Mr. David Millsaps, Owner
Seven Cedars MHP
Post Office Box 1143
Statesville, North Carolina 28687
Subject: Compliance Sampling Inspection
Seven Cedars MHP WWTP
NPDES Permit No. NCO023191
Iredell County
Dear Mr. Millsaps:
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on
October 25, 2018, by Mr. Wes Bell of this Office. Please inform the facility's Operator -in -Responsible Charge (ORC) of our
findings by forwarding a copy of the enclosed report. The results of the effluent samples collected during the inspection will
be forwarded to you under separate cover.
Should you have any questions concerning this letter, please do not hesitate to contact Mr. Bell at (704) 235-2192, or via
email at wes.bell@ncdenr.gov.
Enclosure:
Inspection Report
Sincerely,
DocuSigned by:
F161 FB69A2D84A3...
For W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
EQ.:>
"-mr
North Carolina Department of Environmental Quality I Division of Water Resources
610 East Center Avenue I Suite 301 I Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NC0023191 111 12 I 18/10/25 I17 18 i � i 19 i G i 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 70 71 [.. I 72 73 L_LJ74 751 I I I I I I I80
u u
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
12:40PM 18/10/25
14/06/01
Seven Cedars Mobile Home Park WWTP
Village Dr
Exit Time/Date
Permit Expiration Date
Statesville NC 28677
02:OOPM 18/10/25
19/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Todd Franklin Robinson/ORC/704-881-4598/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
David Lynn Millsaps,PO Box 1143 Statesville NC
28687/Owner/704-902-9521/7048725515 Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
EDocusigned by: 11/1/2018
Wes Bell �� � MRO WQ//704-663-1699 Ext.2192/
A61696D90CC3437...
Signature of Man 8ff6 9vwer Agency/Office/Phone and Fax Numbers Date
CA*,t"11/2/18
H PRO
Andrew WQ//704-663-1699 Ext.21
1`161 FB69AMUA3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NC0023191 I11 121 18/10/25 117 18 ISI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On -site Representatives:
The following Envirolink, Inc. personnel were in attendance during the inspection: Mr. Chris Bitterman,
Mr. Chip White, Mr. Todd Robinson, and Mr. Dennis Murdock.
Page#
Permit: NCO023191 Owner - Facility: Seven Cedars Mobile Home Park WWTP
Inspection Date: 10/25/2018 Inspection Type: Compliance Sampling
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The Division received the permit renewal documentation on 9/11/18.
The last compliance evaluation inspection was performed at the facility
on 8/8/17 by DWR
staff.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
Page# 3
Permit: NCO023191
Inspection Date: 10/25/2018
Record Keeping
Owner - Facility: Seven Cedars Mobile Home Park WWTP
Inspection Type: Compliance Sampling
Yes No NA NE
Comment: The records reviewed durina the inspection were oraanized and well maintained. Discharae
Monitoring Reports (eDMRs) were reviewed for the period September 2017 through August
2018. Daily maximum effluent BOD and TSS violations were reported in February 2018.
Only one effluent ammonia sample (twice per month required) was collected and reported in
January 2018 and August 2018. The Division has previously addressed these limit and
monitoring violations through the issuances of either a NOV or civil penalty assessment.
The 10-day interval between the collection of the twice per month effluent ammonia samples
was not adhered to in March 2018. The ORC and staff will amend the August 2018 eDMR
to accurately reflect the facility visitations (five days per week instead of three).
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
0
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
0
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
0
❑
Comment: On -site field analvses (DH and temperature) are performed under Envirolink. Inc.'s field
laboratory certification #5212. Statesville Analytical, Inc. (Certification #440) has also been
contracted to provide analytical support for all remaining permit -required parameters (BOD,
TSS, ammonia, total nitrogen, total phosphorus).
The ORC and staff must ensure to perform post -analysis calibration checks on the pH
meter following field analyses at multiple sites. Post -analysis calibration checks must be
performed in accordance with the NC Wastewater/Groundwater laboratory certification
approved procedures for the analyses of PH. Note: Post analysis checks would also be
required for dissolved oxygen and total residual chlorine meters if applicable.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: The subject permit requires effluent grab samples.
Operations & Maintenance
Yes No NA NE
❑ ❑ ■ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Yes No NA NE
Page# 4
Permit: NCO023191 Owner - Facility: Seven Cedars Mobile Home Park WWTP
Inspection Date: 10/25/2018 Inspection Type: Compliance Sampling
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facility appeared to be properly operated and well maintained.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: Screenings are disposed at a permitted landfill.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
0 ❑
❑
❑
Are surface aerators and mixers operational?
❑ ❑
0
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
0 ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
❑ ❑
0
❑
Is the DO level acceptable?
0 ❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑ ❑
0
❑
Comment:
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Page# 5
Permit: NCO023191
Inspection Date: 10/25/2018
Secondary Clarifier
Is the site free of excessive floating sludge?
Is the drive unit operational?
Owner - Facility: Seven Cedars Mobile Home Park WWTP
Inspection Type: Compliance Sampling
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Comment: Instantaneous flow measurements are performed by the bucket and stop watch method.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: The effluent aDDeared sliahtiv turbid with no floatable solids or foam.
The effluent dissolved oxygen, PH, and temperature were measured (during the inspection)
at 7.82 mg/L (DO), 7.74 SU (PH), and 14.4 degrees Celsius (temperature). In addition,
DWR staff collected effluent BOD, TSS, ammonia, fecal coliform, total nitrogen and total
phosphorus samples during the inspection. The results of these effluent samples will be
forwarded under separate cover.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
0
❑
❑
❑
Is the mixing adequate?
0
❑
❑
❑
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: Wastewater solids from the aerated sludge holding tanks are removed on an as -needed
basis by a contracted company (L&L Environmental).
Page# 6
AC56810 North Carolina Division of Water Resources Water Sciences Section Laboratory Results
Loc. Descr.:
SEVEN CEDARS MHP WWTP
County:
Iredell
Collector:
W BELL
VisitlD
Region:
Mooresville
Report To
MRO
Location ID:
NCO023191
River Basin
YADKIN PEE DEE
Collect Date:
10/2912018
Priority
COMPLIANCE/COC
Emergency
Collect Time:
12_50
Sample Matrix:
WASTEWATER
COC Yes/No
YES
Sample Depth
Loc. Type:
Effluent
Final Report
Sample ID:
AC56810
PO Number #
Date Received:
1012612018
Time Received:
08:10
Labworks LoginlD
TASCENZ01
Delivery Method
NC Courier
Final Report Date:
11/1411 B
Report Print Date:
1111612018
If this report is labeled preliminary report, the results have not been validated. Do not use for Regulatory purposes.
Result)
Method
Analysis
Units
CAS # Analyte Name
PQL
Qualifier
Reference
Date
Validated by
LAB
Sample temperature at receipt by lab
1.1
aC
10/26/18
MSWIFT
MIC
BOD, 5-Day in liquid
2.0
4.2
mg1L
SM 5210 B-2001
10/26/18
ESTAFFORDi
Coliform, MF Fecal in liquid
1
1600 B5,01
CFU1100ml
SM 9222 D-1997
10/26/10
ESTAFFORDI
NUT
NH3 as N in liquid
0.02
0.02 U
mg1L as N
EPA 350.1 REV 2
10/31/18
CGREEN
NO2+NO3 as N in liquid
0.02
33
mg1L as N
EPA 353.2 REV 2
10131/18
CGREEN
Phosphorus —total as P in liquid
0.02
4.9
mg1L as P
EPA 365.1 REV 2
1112118
CGREEN
Total Kjeldahl N as N in liquid
0.2
1.9
mg1L as N
EPA 351.2 REV 2
1119118
CGREEN
WET
Residue —Suspended in liquid
6.2
12
mg/L
SM 2540 D-1997
10131118
CGREEN
WSS Chemistry Laboratory» 1623 Mail Service Center, Raleigh, NO 27699-1623 (919) 733-3908
"Not Detected" or "U" does not indicate the sample is analyte free but that the analyte is not detected at or above the PQL.
Page 1 of 3
NC rD'MAK La6oratory Section (�sufts/Sarnpf- Comrnents/Quafifier (Definitions
Sample ID: ACS6810
Result/ Method Analysis
ualifier Units Reference Date validated by
Sample Comments
MIC:Fecal Coliform-e5-Too Numerous To Count.
MIC:Fecal Coliform-Q 1-Sample exceeded holding time prior to receipt at lab.
NCDEQ-WSS-Chemistry Lab Data Qualifiers
Al The reported value is an average, where at least one result is qualified with a "U". The PQL is used for the qualified result(S) to call
B1 Coliform-Countable membranes with less than 20 colonies. Reported value is estimated or is a total of the counts on all filters repor
B2 Coliform-Counts from all filters were zero. The value reported is based on the number of colonies per 100 ml that would have been
83 Coliform-Countable membranes with more than 60 or 80 colonies. The value reported is calculated using the count from the smalle
B4 Coliform-Filters have counts of both >60 or 80 and <20. Reported value is estimated or is a total of the counts on all filters reported
B5 Coliform-Too many colonies were present; too numerous to count (TNTC). TNTC is generally defined as >150 colonies.
B6 Coliform-Estimated Value. Blank contamination evident.
B7 Coliform-Many non-coliform or non-enterococcus colonies or interfering non-coliform or non-enterococcus growth present. In this cc
BB1 MPN-No wells or tubes gave a positive reaction. Value based upon the appropriate MPN Index and reported as a less than "<" valu
BB2 MPN-AII wells or tubes gave positive reactions. Value based upon the MPN Index and reported as a greater than ">" value.
C Total residual chlorine was present in sample upon receipt in the laboratory; value is estimated.
G1 BOD-The dissolved oxygen (DO) depletion of the dilution water blank exceeded 0.2 mg/L.
G2 BOD-The bacterial seed controls did not meet the requirement of a DO depletion of at least 2.0 mg/L and/or a DO residual of at lea:
G3 BOD-No sample dilution met the requirement of a DO depletion of at least 2.0 mg/L and/or a DO residual of at least 1.0 mg/L.
G4 BOD-Evidence of toxicity. This is generally characterized by a significant increase in the BOO value as the sample concentration de
G5 BOD-The glucose/ glutamic acid standard exceeded the range of 198 ± 30.5 mg/L.
G6 BOD-The calculated seed correction exceeded the range of 0.6 to 1.0 mg/L.
G7 BOD-Less than 1 mg/L DO remained for all dilutions set. The reported value is an estimated greater than value and is calculated fo
G8 BOD-Oxygen usage is less than 2 mg/L for all dilutions set. The reported value is an estimated less than value and is calculated for
G9 BOD-The DO depletion of the dilution water blank produced a negative value.
it Surrogate recovery limits have been exceeded.
J2 The reported value failed to meet the established quality control criteria for either precision or accuracy.
WSS Chemistry Laboratory>> 1623 Mail Service Center, Raleigh, NC 27699.1623 (919) 733-3908
"Not Detected" or "U" does not indicate the sample is anayte free but that the analyte is not detected at or above the PQL.
Page 2 of 3
NC (D`A Laboratory Section 9?Ssurta/Sample Comments/Quarifi'er (Definitions
Sample ID: AC66810
Result/ Method Analysis
uuallrler Unns Lelereliw Uale
J3 The sample matrix interfered with the ability to make any accurate determination.
J4 The data is questionable because of improper laboratory or field protocols (e.g., composite sample was collected instead of grab, p
J5 Temperature limits exceeded (samples frozen or >6°C) during transport or not verifiable (e.g., no temperature blank provided): non-
J6 The laboratory analysis was from an unpreserved or improperly chemically preserved sample. The data may not be accurate.
J7 This qualifier is used to identify analyte concentration exceeding the upper calibration range of the analytical instrument/method. Th
J8 Temperature limits exceeded (samples frozen or>60C) during storage, the data may not be accurate.
J9 The reported value is determined by a one -point estimation rather than against a regression equation. The estimated concentration
J10 Unidentified peak: estimated value.
J11 The reported value is determined by a one -point estimation rather than against a regression equation. The estimated concentration
J12 The calibration verification did not meet the calibration acceptance criterion for field parameters.
M Sample and duplicate results are "out of control'. The sample is non -homogenous (e.g., VOA soil). The reported value is the lower,
N1 Presumptive evidence and estimated value. The component has been tentatively identified base on mass spectral library.
N2 There is an indication that the analyte is present, but quality control requirements for confirmation were not met (i.e., presence of e
N3 This code shall be used if the level is too low to permit accurate quantification, but the estimated concentration is less than the labo
N4 This code shall be used if the level is too low to permit accurate quantification, but the estimated concentration is less than the labo
N5 The component has been tentatively identified based on a retention time standard.
Q1 Holding time exceeded prior to receipt by lab.
Q2 Holding time exceeded following receipt by lab.
P Elevated PQL` due to matrix interference and/or sample dilution.
S Not enough sample provided to prepare and/or analyze a method -required matrix spike (MS) and/or matrix spike duplicate (MSD).
U Indicates that the analyte was analyzed for but not detected above the reported practical quantitation limit'. The number value repo
X1 Sample not screened for this compound.
X2 Sampled, but analysis lost or not performed -field error.
X3 Sampled, but analysis lost or not performed -lab error.- - - - - - - -- -
V Indicates the analyte was detected in both the sample and the associated method blank. Note: The value in the blank shall not be s
Y Elevated PQL` due to insufficient sample size.
Z1 Inability to analyze the sample.
Z2 Questions concerning data reliability.
U, J6 The laboratory analysis was from an unpreserved or improperly chemically preserved sample. The data may not be accurate.
UU Indicates that the analyte was not detected by a screen analysis. The number value was determined by a one -point estimation at tt
WSS Chemistry Laboratory>> 1623 Mall Service Center, Raleigh, NC 27699.1623 (919) 7334908
"Not Detected" or "U" does not indicate the sample is analyte free but that the analyte is not detected at or above the PQL.
Page 3 of 3
NORTH CAROL NA
ROY COOPER Envrranrh#1t1G1 QUdlfly
G&V0 tw
MICHAEL S. RE AN
Secr�rary
LfNDA CULPEPPER
In redm D,'rsctor
20 November 2018
Mr. David Millsaps, Owner
Seven Cedars MHP
Post Office Box 1143
Statesville, North Carolina 28687
Subject: Effluent Sampling Results
Seven Cedars MHP WWTP
NPDES Permit No. NCO023191
Iredell County
Dear Mr. Millsaps:
Enclosed is a copy of the laboratory results for the effluent samples collected during the Compliance Sampling Inspection
performed at the subject facility on October 25, 2018, by Mr. Wes Bell of this Office. Effluent grab samples were collected at
Outfall 001 during this inspection. The facility complied with all applicable permit limits (daily maximums). Please attach this
correspondence with the previously issued inspection report (dated November 2, 2018) to complete your records.
Should you have any questions concerning this letter, please do not hesitate to contact Mr. Bell at (704) 235-2192, or via
email at wes.bell@ncdenr.gov.
Enclosure:
Effluent Results
Sincerely,
DocuSigned by:
A14CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
EQ.:>
"-mr
North Carolina Department of Environmental Quality I Division of Water Resources
610 East Center Avenue I Suite 301I Mooresville, North Carolina 28115
704.663.1699