HomeMy WebLinkAboutNC0070289_Compliance Evaluation Inspection_20181031 (2)ROY- COOPER NORTH CAROLINA
Catiarnar EizvbT mental Quafrty
ECHAEL S_ RE _^X
3aorafw:r
LLNDA CT,-LPEPPER
IntsriFn Diracmr
Certified Mail # 7016 1370 0000 2591 1094
Return Receipt Requested
October 30, 2018
Wayne Huntley
Stones Throw Homeowners Association
PO Box 690725
Charlotte, NC 28227
SUBJECT: NOTICE OF VIOLATION & INTENT TO ASSESS CIVIL PENALTY
Tracking Number: NOV-2018-PC-0403
Permit No. NCO070289
Ridgewood Farms Subdivision
Cabarrus County
Dear Mr. Huntley:
The North Carolina Division of Water Resources conducted an inspection of the Ridgewood Farms Subdivision on
October 22, 2018. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0070289. A summary of the findings and
comments noted during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Mooresville
Regional Office. The following violation(s) were noted during the inspection:
Inspection Area Description of Violation
Permit As of the inspection date, no application for permit renewal has been received. The
current permit expires November 30, 2018.
Please be advised that in accordance with North Carolina Administrative Code (NCAC) T15A:
02H .0211, PERMIT RENEWALS, Request for permit renewals are to be submitted to the
Director at least 180 days prior to expiration...
D-EQ§
NFn� G1Wf
North Carolina Department of Environmental Quality I Division of Water Resources
610 East Center Avenue, Suite 301, Mooresville, NC 28115
704-663-1699
Inspection Area Description of Violation
Aeration Basins Diffusers in aeration tank appeared to be broken or missing. MLSS did not have a smooth
roll and was devoid of fine bubbles. Oxygen transfer appeared to be ineffective and wasting
energy. Diffusers should be repaired or replaced.
Sludge Handling Disposal Hole rusted in bulkhead between aeration basin and waste sludge tank.
Aerobic Digester Top of bulkhead between digester and aeration basin has rusted out and bulkhead may
collapse if digester is pumped all the way down. The rusted -out hole in bulkhead makes it
ineffective to waste and dewater sludge at this facility.
In addition, the issues below must also be addressed:
Compliance Issue(s): Please be advised that in accordance with NCAC T15A: 02H .0211, Permit
Renewals, permit renewal should be submitted at least 180 days prior to expiration. Permit renewal
application and required fees should be completed and sent to the Division. If you should have any
questions regarding this process you may contact Mr. Derek Denard in Raleigh at 919-707-3618.
Please also note that in accordance with your NPDES Permit, Number NCO070289, Part II, Section C.
Operation and Maintenance of Pollution Controls, 2., The Permittee shall at all times properly operate
and maintain all facilities and systems of treatment and control (and related appurtenances) which
are installed or used by the Permittee to achieve compliance with Conditions of the permit. Therefore,
it is necessary to perform repairs to diffusers and sludge waste tank for treatment facility to operate
at optimal efficiency.
A Notice of Violation/Intent to Issue Civil Penalty is being issued for the noted violation of North Carolina General
Statute (G.S.) 143-215.1 and the facility's NPDES WW Permit. Pursuant to G.S. 143-215.6A, a civil penalty of
not more than twenty-five thousand dollars ($25,000.00) may be assessed against any person who violates or
fails to act in accordance with the terms, conditions, or requirements of any permit issued pursuant to G.S.
143-215.1.
If you wish to provide additional information regarding the noted violation, request technical assistance, or discuss
overall compliance please respond in writing within ten (10) business day after receipt of this Notice. A review of
your response will be considered along with any additional information provided. You will then be notified of any
civil penalties that may be assessed regarding the violations. If no response is received in this Office
within the 10-day period, a civil penalty assessment may be prepared.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law. If the violations are of a continuing nature, not related to operation and/or maintenance problems, and
you anticipate remedial construction activities, then you may wish to consider applying for a Special Order by
Consent.
Reminder: Pursuant to Permit Condition 6 in Section E, the Permittee is required to verbally notify the Regional
Office as soon as possible, not to exceed 24 hours, from first knowledge of any non-compliance at
the facility including limit violations, bypasses of, or failure of a treatment unit. A written report may
be required within 5 days if directed by Division staff. Prior notice should be given for anticipated or
potential problems due to planned maintenance activities, taking units off-line, etc.
D_EQ§
Ikys�. n NFn�w.e�W G1Wf�
North Carolina Department of Environmental Quality I Division of Water Resources
610 East Center Avenue, Suite 301, Mooresville, NC 28115
704-663-1699
If you should have any questions, please do not hesitate to contact Roberto Scheller with the Water Quality
Regional Operations Section in the Mooresville Regional Office at 704-663-1699.
Sincerely,
DocuSigned by:
A14CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Mooresville Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit - Enforcement File
D-EQ
NFn�w�e�W G1Wf�
North Carolina Department of Environmental Quality I Division of Water Resources
610 East Center Avenue, Suite 301, Mooresville, NC 28115
704-663-1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCO070289 111 12 I 18/01/22 I17 18 I S I 19 I G I 201 I
211111 1 1 I I I I II I I I I I I I I I I I I 1 I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
671
70 I2 71 I tyI 72 I r I 73 I I 174 751 I I I I I I I80
uI I I i
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:OOAM 18/01/22
14/02/01
Ridgewood Farms Subdivision
Olde Creek Trl
Exit Time/Date
Permit Expiration Date
Concord NC 28025
11:03AM 18/01/22
18/11/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Kellie H Hedrick/ORC/980-202-2377/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Wayne Huntley,PO Box 690725 Charlotte INC 28227//704-455-5463/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
- - SQL MRO WQ//252-946-6481/ 10/30/2018
Roberto Scheller Cj91C2A007838943E—
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger Division of Water Quality//704-2'
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
e� 10/30/2018
AlaccsalAi=vazs... Page#
NPDES yr/mo/day Inspection Type
NCO070289 I11 121 18/01/22 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
As of date of this inspection the Division has not received a renewal permit application.
Diffusers in aeration basin require repair or replacement.
Sludge waste tank requires repair of replacement.
Although at the time of inspection the ORC was doing an exceedingly good job of operating the subject
wastewater treatment plant (WWTP). The above noted plant deficiencies will hamper plant
performance and the ability of operator to effectively and efficiently operate WWTP at peak
performance.
Page#
Permit: NCO070289 Owner - Facility: Ridgewood Farms Subdivision
Inspection Date: 01/22/2018 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
0
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: As of the inspection date, no application for permit renewal has been received. The current
permit expires November 30, 2018.
Please be advised that in accordance with North Carolina Administrative Code T15A: 02H
.0211, PERMIT RENEWALS, Request for permit renewals are to be submitted to the
Director at least 180 days proir to expiration...
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
0
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
M
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
0
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
❑
Comment: K&W Laboratories (Certification #559) is used as contract lab. Field Darameters are
conducted under field Certification #5695.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: At time of insepction 30 minute settleability test was on going and apx 40 minutes had
elapased. MLSS had settled to a defined sludge blanket with clear supernatant above.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
❑
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Page# 3
Permit: NCO070289
Inspection Date: 01/22/2018
Bar Screens
Owner - Facility: Ridgewood Farms Subdivision
Inspection Type: Compliance Evaluation
Yes No NA NE
Is the unit in good condition? 0 ❑ ❑ ❑
Comment: Old bar screen has been replaced. New bar screen appeared to be operating properly.
Aeration Basins
Yes No NA NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
❑ 0
❑
❑
Are surface aerators and mixers operational?
❑ ❑
0
❑
Are the diffusers operational?
0 ❑
❑
❑
Is the foam the proper color for the treatment process?
E ❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0 ❑
❑
❑
Is the DO level acceptable?
❑ ❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
❑ ❑
❑
Comment: Diffusers in areation tank appeared to be broken or missing. MLSS did not have a smoth roll
and was devoid of fine bubbles. Oxygen transfer appeared
to ineffective and wasting energy.
Diffusers should be repaired or replaced.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: Effluent from secondary clarifier was clear with few visible suspended solids.
Disinfection -Tablet
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Yes No NA NE
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
■
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
Yes No NA NE
■
❑
❑
❑
❑
❑
❑
Page# 4
Permit: NCO070289
Owner - Facility: Ridgewood Farms Subdivision
Inspection Date: 01/22/2018
Inspection Type: Compliance Evaluation
Disinfection -Tablet
Yes No NA NE
Number of tubes in use?
4
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment:
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
M ❑
❑
❑
Is storage appropriate for cylinders?
❑ ❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
❑
Comment:
Are the tablets the proper size and type? 0 ❑ ❑ ❑
Are tablet de -chlorinators operational? 0 ❑ ❑ ❑
Number of tubes in use? 4
Comment:
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
0
❑
❑
❑
Comment: Flow meter was calibrated by Delta Systems Environmental. Next calibration due November
2018.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Yes No NA NE
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 5
Permit: NCO070289 Owner - Facility: Ridgewood Farms Subdivision
Inspection Date: 01/22/2018 Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Comment: At time of inspection effluent sampler storage was noted at 3 degrees Celsius.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: At time of inspection the discharge point effluent was clear with no visible solids. Foam
being generated at point of discharge disipated 20 feet downstream.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
❑
0
❑
❑
Is the mixing adequate?
❑
0
❑
❑
Is the site free of excessive foaming in the tank?
❑
❑
0
❑
# Is the odor acceptable?
❑
❑
0
❑
# Is tankage available for properly waste sludge?
❑
0
❑
❑
Comment: Top of bulkhead between digester and aeration basin has rusted out and bulkhead may
collapse if digester is pumped all the way down. The rusted out hole in bulkhead makes it
ineffective to waste and dewater sludge at this facility.
Page# 6