HomeMy WebLinkAboutWQ0040398_Application (FTSE)_20180814State of North Carolina
Department of Environmental Quality
DWR Division of Water Resources
I5A NCAC 02T .0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION
Division of Water Resources FTA 04-16 & SUPPORTING DOCUMENTATION
rr r�
Application Number: U Q L103 i S oo be completed by DWR) J fI
All items must be completed or the application will be returned
1. APPLICANT INFORMATION: -�
I. Applicant's name: Johnston County Public Utilities (company, municipality, HOA, utility, etc.)
2. Applicant type: ❑ Individual ❑ Corporation ❑ General Partnership ❑ Privately -Owned Public Utility
❑ Federal ® State/County ❑ Municipal ❑ Other
3. Signature authority's name: Chandra C. Farmer. PE per 15A NCAC 02T .0106(b)
Title: Public Utility Director Y.
4. Applicant's mailing address: P.O. Box 2263
O
City: Smithfield State: NC Zip: 27577-
5. Applicant's contact information:
Phone number: (919) 989-5075 Email Address: chandra.farmer@iohnstonnc.com
II. PROJECT INFORMATION:
1. Project name: McGee's Crossroads Sewer Upgrade Phase_2B
2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project
If a modification, provide the existing permit number: WQ00 _ and issued date:
If new construction but part of a master plan, provide the existing permit number: WQ00_
3. County where project is located: Johnston
4. Approximate Coordinates (Decimal Degrees): Latitude: 35.54783 Longitude:-78.54074
5. Parcel ID (if applicable):
(or Parcel ID to closest downstream sewer)
III. CONSULTANT INFORMATION:
I. Professional Engineer: Jamie Guerrero, PE License Number: 034417
Firm: Morris and Ritchie Associates of NC PC
Mailing address: 5605 Chapel Hill Road, Suite 112
City. Raleigh State: NC Zip: 27607-
Phone number: (984) 200-2103 Email Address: jauerrero(@mragta.com
IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION:
1. Facility Name: Central Johnston County WWTF Permit Number: NCO030716
Owner Name: Johnston County Public Utilities A-
V. RECEIVING DOWNSTREAM SEWER INFORMATION (if different than WWTF):
1. Permit Number(s): WQ0020340 Downstream (Receiving) Sewer Size: N:A inch Landfill Equalization Facility
stem W1dC Collection System rrnk Numbers ifapplicable): WQCS00060
Owner Name(s): Johnston County Public Utilities
FORM: FTA 04-I6 Pagel of 5
VI. GENERAL REQUIREMENTS
I. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached?
[:]Yes []No N'A See t O-11ai r
2. If the Applicant is a Developer of lots to be sold, has a Dcvcluper's Operational Agreement 1FORM: DE V) been attached?
❑ Ycs ❑No ON. -:A
3. If the Applicant is a Ilome Prupert-Clwiiers' Associati❑n_hz3s.,in Qperatiornul A�=mcmcnr (FORM: 140AI been attached?
❑ Yes ❑No XiA
4. Origin of wastewater: (check all that apply):
❑ Residential Owned ❑ Retail (stores, centers, malls) ❑ Car Wash
❑ Residential Leased ❑ Retail with food preparation/service ❑ Hotel and/or Motels
❑ School!' preschool / day care ❑ Medical!" dental i veterinary facilities ❑ Swimming Pool Clubhouse
❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash
❑ Businesses 1 offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment)
5. Nature of wastewater: % DomesticlCommcrcial % Commercial
% Industrial (See, 15A NCAC 021 _0103f20)
�Is there a Pretreatment Program in effect? ❑ Yes ❑ No
6. Hasa flow reduction been approved under 1.5A NCAC 02T .01 1 �JL? [:]Yes []No
t If yes, Provide a copy of flow reduction aporeval letter
7. Summarize wastewater generated by project:
Establishment Type (see k1L.011
Daily Design Flow'"
No. of Units
Flow
gall
GPD
gall
GAD
gall
GPD
gall
GPD
gall
GPD
gall
GPD
7olal
GPD
a See 15A NCAC 02T .01 14(b), (d), (c)(.1) and (c1121 for caveats to wastewater design flow rates (i.e., minimum flow per
dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas;
and residential property located south or cast of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined
in Q.S. 42A4).
b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table .15A NCAC 02'r.01141 shall be
determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data.
8. Wastewater generated by project: 0 GPD (per )5A N Z C 02T .0l 14)
D Do not include future flows or previously permitted allocations
If permitted flow is zero, indicate why:
® Pump Station o ravity Sewer here flow will be permitted in subsequent permits that connect to this line
❑ Flow has already been allocated in Permit Number:
® Rehabilitation or replacement of existing sewer with no new flow expected
❑ Other (Explain):
FORM: FTA 04-16 Page 2 of 5
VI1. GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T .0305 & MDC(Gravity Sewers
1. Summarize gravity sewer to be permitted:
Size (inches)
Length (feet)
Material
27
2,624
SDR-35
27
5,615
SDR-26
dF
i- Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria
D Section III contains information related to minimum slopes for gravity sewer(s)
Oversizing lines to meet minimum slope requirement is not allowed and a violation of the MDC
VIII. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC(Pump Stations/Force Mains):
COMPLETE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT
1. Pump station number or name:
2. Approximate Coordinates (Decimal Degrees): Latitude: _ . Longitude: -�
3. Design flow of the pump station: millions gallons per day (firm capacity)
4. Operational point(s) of the pump(s): gallons per minute at — feet total dynamic head (TDH)
5. Summarize the force main to be permitted (for this Pump Station):
Size (inches) Length (feet) Material
6. Power reliability in accordance with 15A NCAC 02T .0305 h I :
❑ Standby power source or pump with automatic activation and telemetry - 15A NCAC 02T .0305(h)(1)(B),
Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day
Must be permanent to facility
Or if the pump station has an average daily flow less than 15,000 gallons per day:
❑ Portable power source with manual activation, quick -connection receptacle and telemetry - 15A NCAC 02T
.0305(h)(1)(C)
or
❑ Portable pumping unit with plugged emergency pump connection and telemetry - I5A NCAC 02T .0305(h)(1)(C):
z It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant (draft agreement)
and is compatible with the station.
i- If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage
capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided
in the case of a multiple station power outage.
FORM: FTA 04-16 Page 3 of 5
IX. SETBACKS & SEPARATIONS - (02B .0200 & 15A NCAC 02T .0305(f)):
I. Does the project comply with all separations found in 15A NCAC 0'2T .0305(o & (9-) ® Yes ❑ No
15A NCAC 02T.0305(f) contains minimum separations that shall he nrnvided far sewer svoemv
Setback Parameter*
Separation Required
Storm sewers and other utilities not listed below (vertical)
24 inches
Water mains (vertical -water over sewer including in benched trenches)
18 inches
Water mains (horizontal)
10 feet
Reclaimed water lines (vertical - reclaimed over sewer)
18 inches
Reclaimed water lines (horizontal - reclaimed over sewer)
2 feet
**Any private or public water supply source, including any wells, WS-I waters of Class I or
Class II impounded reservoirs used as a source of drinking water
100 feet
**Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal
high water (or tide elevation) and wetlands (sec item IX.2)
50 feet
**Any other stream, lake, impoundment, or ground water Iowering and surface drainage
ditches
10 feet
Any building foundation
5 feet
Any basement
10 feet
Top slope of embankment or cuts of 2 feet or more vertical height
10 feet
Drainage s stems and interce for drains
5 feet
Any swimming pools
10 feet
Final earth grade (vertical)
36 inches
D I5A NCAC 02T.0305(e) contains alternatives where separations in 02T.0305(f1 cannot be achieved.
> **Stream classifications can be identified using the Division's NC Surfacc Water Classifications webRai,c
If noncompliance with 02T.0305 origh see Section X of this application
2. Does the project comply with separation requirements for wetlands? (50 feet of separation) csA No ❑ N"A
Seethe Division's draft separation requirements for situations where separation cannot be mec 4 4p a FA4) �p r
No variance is required if the alternative design criteria specified is utilized in design and construction
As built documents should reference the location of areas effected
3. Does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .0200? ®Yes ❑ No ❑ N A
z This would include Trout Buffered Streams per 15A NCAC 213.0202
4. Does the project require coverage. -authorization under a 404 Nationwide or ® Yes ❑ No
individual permits or 401 Water Quality Certifications?
D Information can be obtained from the 401 & Buffer Pcrmiuint* Rran clt
5. Does project comply with 15A NCAC 02T.0105(c)(6) (additional permitslcertifications)? ® Yes ❑ No
Per 15A NCAC 02T.0 I 05-WL61, directly related environmental permits or certification applications are being prepared, have
been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and
sedimentation control plans, stormwater management plans, etc.).
6. Does this project include any sewer collection lines that are deemed "high -priority?"
Per 15A NC -AG 02T,0402, "high -priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer
positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer.
[:]Yes ® No ❑ N.-'A
If yes, include an attachment with details for each line, including type (aerial line, size, material, and location).
High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections
documented per 15A NCAC 02T.0403(a)(5) or the permitee's individual System -Wide Collection permit.
FORM: FTA 04-16 Page 4 of 5
;Jkr4s '-oO
X. CERTIFICATIONS:
I. Does the submitted system comply with 15A NCAC 02T, the Minimum Design _Criteria.for thc.Permittinr, of Pump Stations
arW fte Mains flatest version), and the Gravity Sewer Minimum Design C'ritcria. lgicst version as applicable?
® Yes ❑ No
If No, complete and submit the Variance/Alternative Design Request application (VADC 10-14) and supporting documents for
review. Approval of the re nest is required prior to submittal of the Fast Track Application and supporting documents.
2. Professional Engineer's Certification:
-attest that this application for
Engineer's name from Application Item 111.1.)
has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications,
engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best
of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer
Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Permitting
of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this
submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and
have judged it to be consistent with the proposed design.
NOTE - In accordance with General Statutes 143-215.6A and 143-215.613, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed S 10,000, as well as civil penalties up to S25,000 per violation.
North Carolina Professional Engineer's seal, signature, and date:
3. Applicant's Certification per I SA NCAC 02T .0106(b):
I,
A*
(Signature Authority's name & title from Application Item I.3.)
i ............ I
.... . . ..... _- ------ _....
,,��IIIIIIIk�II
r A C •
SEAL p
= 034417 ! d TABU
r •
attest that this application for
has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of
this application are not completed and that if all required supporting documentation and attachments are not included, this
application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non -
discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties,
injunctive relief, and/or criminal prosecution. 1 will make no claim against the Division of Water Resources should a condition
of this permit be violated. I also understand that if all required parts of this application package are not completed and that if
all required supporting information and attachments are not included, this application package will be returned to me as
incomplete.
NOTE In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed SI0,000 as well as civil penalties up to S25,000 per violation.
Signature: C . Date:
FORM: FTA 04-16 Page 5 of 5
MORRIS & RITCHIE ASSOCIATES OF NC, PC
AN AFFILIATE OF MORRIS & RITCHIE ASSOCIATES, INC. WHICH
PROVIDES ENGINEERING, ARCHITECTURE, PLANNING, SURVEYING &
LANDSCAPE ARCHITECTURE THROUGHOUT THE MID -ATLANTIC REGION
August 2, 2018
Raleigh Regional Office Water Quality Section
1628 Mail Service Center
Raleigh, NC 27699-1628
Re: Fast Track Sewer Extension Application
McGee's Crossroads Sewer Upgrade Phase 2B (CS370560-16)
Johnston County, North Carolina
Dear Sir or Madam:
NC Dept "Environmental QI,LjijIv
AUG 14 2018
Raleigh Regional Office
Please find enclosed the Fast Track Sewer System Application, Flow Tacking/Acceptance for Sewer
Extension Applications, and Location Map for the above referenced project. The proposed project consists
of the construction of 8,239 LF of 27" gravity sewer line that will connect to the proposed Middle Creek
Regional Pump Station (permitted as a separate project).
Johnston County has experienced dramatic increase in residential and commercial growth especially in
areas within the County's sewer service area. Current flow within the existing force main serving the
McGee's Crossroads sewer area is close to exceeding the maximum allowable pressure. This project is
required to provide additional capacity, relieve the flow on an existing force main, and construct a regional
pump station (as a separate project) to meet current and future sewer demands. The above reference phase
proposes a gravity sewer main parallel to Middle Creek to the proposed regional pump station.
Construction of this sewer main will replace two pump stations and ultimately a third pump station at full
build -out Since this a new sewer main, there will be no existing flow that will require bypass during the
construction of the project.
The future projected in the gravity sewer line is estimated as follows:
Future ADF w/o equalization: 1,175 GPM Peak Hour: 2,937.5 GPM
Future ADF w/ equalization: 1,304 GPM Peak Hour: 3,260 GPM
Please let me know if you need additional information.
AThyou
ameGuerrero
Associate
Enclosures: Fast Track Sewer System Application
Flow Tracking/Acceptance for Sewer Extension Applications
Aerial Location Map
Application Fee of $480.00 payable to NCDEQ
5605 Chapel Hill Road, Suite 112, Raleigh, NC 27607 (984) 200-2103 www.mragta.com
Abingdon, MD 4 Bakimore, MD ♦ Laurel, MD i Towson, MD ♦ Georgetown, DE ♦ New Castle, DE t Steding, VA ♦ Raleigh, NC
(410) 515-9000 (410) 935-5050 (410) 792-9792 (410) 821-7 690 (302) 855-5734 (302) 326-2200 (703) 674.0161 (984) 200-2103
State of North Carolina
Department of Environment and Natural Resources
DWR Division of Water Resources
Division of Water Resources Flow Tracking/Acceptance for Sewer Extension Applications
(FTSE 08-13)
Project Applicant Name: Johnston County
Project Name for which flow is being requested: McGee's Sewer Upgrade Phase 2
More than one FTSE may be required for a single project if the owner of the WWTP is not responsible for all pump
stations along the route of the proposed wastewaterflow.
I. Complete this section only if you are the owner of the wastewater treatment plant.
a. WWTP Facility Name: Central Johnston County WWTP
b. WWTP Facility Permit #: NC0030716
All flows are in MGD
c. WWTP facility's permitted flow 9.5 MGD C-
d. Estimated obligated flow not yet tributary to the WWTP 1.8728
e. WWTP facility's actual avg. flow 5.4020 N
f Total flow for this specific request _0.0 0 �,-
g. Total actual and obligated flows to the facility 7.3011
h. Percent of permitted flow used 76.9% Q
II. Complete this section for each pump station you are responsible for along the route of fis
proposed wastewater flow. Z
List pump stations located between the project connection point and the WWTP:
(A) (B) (C) (D)=(B+C) (E)=(A-D)
Design Obligated,
Pump Average Daily Approx. Not Yet Total Current
Station Firm Flow** Current Avg. Tributary Flow Plus
(Name or Capacity,* (Firm ' p0, Daily Flow, Daily Flow, Obligated Available
Number) MGD MGD MGD MGD Flow Capacity***
New Middle
Creek 1.44 0.576 0 0 0 0.576
Landfill EQ 1.9296 1.67184 0.67180 0.39265 1.06445 0.6074
* The Firm Capacity of any pump station is defined as the maximum pumped flow that
can be achieved with the largest pump taken out of service.
** Design Average Daily Flow is the firm capacity of the pump station divided by a peaking
factor (po not less than 2.5.
*** A Planning Assessment Addendum shall be attached for each pump station located
between the project connection point and the WWTP where the Available Capacity is ¢ 0.
NS
e
Page l of 6
FTSE 08-13
I1I. Certification Statement:
I Chandra C. Coats, P.E. certify to the best of my knowledge that the addition of
the volume of wastewater to be permitted in this project has been evaluated along the route to the
receiving wastewater treatment facility and that the flow from this project is not anticipated to
cause any -capacity -related sanitary -sewer -overflows or -overburden any -downstream -pump station
en route to the receiving treatment plant under normal circumstances, given the implementation of
the planned improvements identified in the planning assessment where applicable. This analysis
has been performed in accordance with local established policies and procedures using the best
available data. This certification applies to those items listed above in Sections I and II plus all
attached planning assessment addendums for which I am the responsible party. Signature of this
form indicates acceptance of this wastewater flow.
Signing Official Signature
Page 2 of 6
I+TSE 08-13