HomeMy WebLinkAboutWQ0039488_Modification Attachments_20181017 (14)Pump Tank Buoyancy Calculations: Amphidrome Plus Reactors #1 & 2 Diameter of Tank (Inside)8 ft Wall Thickness 6 in Height of Tank (top to invert)15.83333 ft Width of extended base 14 in Thickness of top 6 in Thickness of bottom 10 in Height of top of tank out of ground 0 in Hatch Area 3.14 sqft Density of Water 62.4 #/cf Density of Concrete 150 #/cf Density Soil 95 #/cf Effective Weight of 32.6 #/cf Volume of the inside of the tank 796 cf Volume of the outside of the tank 295 cf Volume of the extended base 28 cf Volume of excavation for tank 1,119 cf Weight of tank 44,198 # Weight of water displaced 69,796 # Weight of Pumps 0 # Effective Weight of Soil in vertical column 42,996 # (above ext base + 10 degree wedge) Total Pumpstation Weight 87,195 # Sliding Resistnance R = P*(f)*perimeter = 26,220.48 lbs Slding Resistnace P = Ka*Usub*(H^2)/2 = 1,473.61 lbs/ft Ka = 0.33 Ratio of Lateral to vertical earth pressures Usub = Us*(1-1/SG) = 35.63 #/cf Effective Unit weight of soil Us = 95.00 #/cf Unit Weitht of Soil SG =1.60 Specific Gravity of Soil H = 15.83 ft Depth of Tank (exterior) f = 0.50 friction factor (0.5 for ext. base, 0.3 for smooth) Perimeter = pi*d 35.59 ft Perimeter of extended base or tank bottom d = 11.33 ft diameter of Tank Base Buoyancy Weight -43,619 # Negative number means NOT bouyant! Factor of Safety =1.62 FS (wt only) = 1.25