HomeMy WebLinkAboutNCG550402_Compliance Evaluation Inspection_20181008 far r\
ROY COOPER NORTH CAROLINA
Governor Environmental Quality
MICHAEL S.REGAN
Secretary
LINDA CULPEPPER
Interim Director
October 8, 2018
Ms. Darlene Deyton
158 Deep Gap Estates Rd.
Deep Gap, NC 28618 RECEO�ED/DEi2018��®W�
SUBJECT: Compliance Evaluation Inspection
Certificate of Coverage: NCG550402 \NeterOCT Resources
17
158 Deep Gap Estates Rd, Deep Gap Permitting Section
Ashe County
Dear Ms. Deyton,
On October 3, 2018 Kelli Park, of this office, conducted a compliance evaluation
inspection of the wastewater treatment system located at the above address. The State
requires the Division of Water Resources to inspect these types of systems every five
years.
Miss Park was unable to locate the effluent discharge pipe, however there was no odor
and there were no noticeable impacts to the stream. It is a permit requirement to have the
area around the effluent pipe cleared and maintained. Effluent being discharged in the
stream should also be checked periodically to ensure that no solids are being discharged
and that there are no impacts to the stream. Via a phone conversation with Miss Park you
reported that you are not sure where the effluent pipe is. Please investigate this matter
and determine where the outflow is, as it is critical to check the effluent and a permit
requirement to maintain the area to and around the outfall.
Chlorine is not required in your system since it was installed in 1986.
The permit also requires that the septic tank contents be pumped out every 3-5 years to
prevent solids from clogging the sand filter system. Via a phone conversation with Miss
Park the system was pumped last in 2012. The system is overdue to be pumped. Please
get the system pumped again immediately, let Miss Park know that it was pumped, and
keep records of septic tank pumping on hand as a historical record and proof that you
had the tank pumped.
Since you have been unable to locate the effluent pipe, discharge samples have not been
analyzed. Water samples from the effluent are required to be analyzed at least once a
NORTH CAROuN
OepmCnenl of Environmental Cuallryy
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 Hanes Mill Road,Suite 300 I Winston-Salem,North Carolina 27103
336.776.9800
, United States Environmental Protection Agency Form Approved.
EPA Washington,D C 20460 OMB No 2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A.National Data System Coding(i.e,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 E 2 IL I 3 NCG550402 111 12(1 18/10/03 117 18 (11, 191 c I 2011
21111111 1111111111111111111111111 11111111111 p6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA -Reserved-
67I I 70 I I 71 1 I 72 I N IL—I 731 1 1' 751 I I I 1 1 1 180
Section B Facility Data J
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 02 20PM 18/10/03 13/08/01
158 Deep Gap Estates Road
Exit Time/Date Permit Expiration Date
158 Deep Gap Estates Rd
02 45PM 18/10/03 18/07/31
Deep Gap NC 28618
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
/1/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Darlene Deyton,PO Box 152 Deep Gap NC 28618/1336-877-3178/
No
Section C Areas Evaluated During Inspection(Check only those areas evaluated)
Permit • Facility Site Review • Effluent/Receiving Waters
Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Kelli A Park WSRO WQ//336-776-9689/
4/vik./6071._
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete
Page# 1
v t
Permit: NCG550402 Owner-Facility: 158 Deep Gap Estates Road
Inspection Date: 10/03/2018 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0 ❑ • ❑
application?
Is the facility as described in the permit? MI ❑ ❑ El
#Are there any special conditions for the permit? ❑ • ❑ El
Is access to the plant site restricted to the general public'? 0 U ❑ 0
Is the inspector granted access to all areas for inspection? In ❑ ❑ ❑
Comment. SFR
Effluent Pipei Yes No NA NE
Is right of way to the outfall properly maintained? ❑ • El 0
Are the receiving water free of foam other than trace amounts and other debris'? U ❑ El ❑
If effluent (diffuser pipes are required) are they operating properly'? ❑ ❑ U 0
Comment' The effluent pipe was not located and Mrs. Dayton is unaware of where the pipe is.Via the
inspection letter I have asked her to find the pipe and maintain the right of way.