HomeMy WebLinkAboutNCG551602_Compliance Evaluation Inspection_20181010 +ti'"`l5rA7E�
� i.� ,
Il 11 .
ROY COOPER NORTH CAROLINA
Governor Environmental Quality
MICHAEL S.REGAN
Secretary
LINDA CULPEPPER •
Interim Director
October 10, 2018
Mr. David Palletta
800 East Oak Dr. �Eloia\trctmE:yiDttfliiinDegriEsI�RI®��
Durham, NC 27705
201
SUBJECT: Compliance Evaluation Inspection
Certificate of Coverage: NCG551602 $e�t,o�4178 US Highway 421 North, Vilas
Watauga County
Dear Mr. Palletta,
On October 9, 2018 Kelli Park, of this office, conducted a compliance evaluation
inspection of the wastewater treatment system located at the above address. The State
requires the Division of Water Resources to inspect these types of systems every five
years.
Miss Park was able to locate the effluent discharge pipe. It is a white PVC pipe located to
the right of the driveway, nearby the drainage ditch that it flows into. There was no odor
or noticeable impacts to the stream. Effluent being discharged in the stream should be
checked periodically to ensure that no solids are being discharged and that there are no
impacts to the stream.
Ultraviolet lights are used to disinfect the wastewater before reaching the stream.
Residual chlorine monitoring is not required for this system. A light was replaced in
September of 2017 during the yearly inspection you have done to the system through
Water Management of North Carolina. While the lights are checked during the inspection,
it is strongly recommended that the lights be periodically checked throughout the year to
ensure that they are functioning properly.
The permit also requires that the septic tank contents be pumped out every 3-5 years to
prevent solids from clogging the sand filter system. Per a phone conversation with Miss
Park the system was pumped last in 2015. The system is due to be pumped. Please get
the system pumped again soon, and keep records of septic tank pumping on hand as a
historical record and proof that you had the tank pumped.
D_E
NORTH CAROUNR CO
DenmuomtofEatrormenmD RINNs
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 Hanes Mill Road,Suite 300 I Winston-Salem,North Carolina 27103
336.776.9800
4
United States Environmental Protection Agency Form Approved.
EPA Washington,D C 20460 OMB No 2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 H 2 LI 3 I NCG551602 111 12 1 18/10/09 117 18 1 2 l 19 Is I 201
2111N11 1111111111111111111111111 11111111111 166
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved
67I L-
7O I I 71 I I 72 I N I1 731 I 174 75j 1 1 1 1 1 1 18O
Section B Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 01 OOPM 18/10/09 13/09/19
4178 U S Hwy 421 North
Exit Time/Date - Permit Expiration Date
4178 US Hwy 421 N
0130P 18/10/09 16/07/31 .
Vilas NC 28692
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
David Paletta,B201 S Crestwyck Ct Raleigh NC 27615///
No
Section C Areas Evaluated During Inspection(Check only those areas evaluated)
• Permit IN Facility Site Review • Effluent/Receiving Waters
Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Kelli A Park WSRO WQ//336-776-9689/
V414_
fol lo[l8
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
)U ."Y- ( .-- °//one
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete
Page# 1
Permit: NCG551602 Owner-Facility. 4178 U S.Hwy 421 North
Inspection Date: 10/09/2018 Inspection Type: Compliance Evaluation
Permit - Yes No NA NE
(If the present permit expires in 6 months or less) Has the permittee submitted a new 00110
application?
Is the facility as described in the permit? • 000
#Are there any special conditions for the permit? 01101=1
Is access to the plant site restricted to the general public'? 0 • 00
Is the inspector granted access to all areas for inspection'? • 000
Comment. SFR
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained'? • 000
Are the receiving water free of foam other than trace amounts and other debris'? I ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating properly'? 00 • 0
Comment:
Page# 3