HomeMy WebLinkAboutNC0088838_Compliance Evaluation Inspection_20181012NORTH CAROLINA
ROY COOPER ErrVfr "Fh#1trdf Qrtorrry
Govwnw
MICHAEL S. REGAN
54hT ary
LI DA CULPEPPER October 12, 2018
lnrerfm &'rea w
Mr. Stuart Kerkoff (via email)
Environmental Health and Safety Manager
Radiator Specialty Company
600 Radiator Road
Indian Trail, North Carolina 28079
Subject: Compliance Evaluation Inspection
Radiator Specialty Company
NPDES Permit #NC0088838
Groundwater Remediation
Union County
Dear Mr. Kerkoff:
Thank you your time and assistance during the October 10, 2018, inspection. Enclosed you will find the report for
the compliance inspection. The treatment and disposal system appears to be performing well.
There are, however, a few items that should be addressed should a permit modification be required for system re-
location and potential additional required treatment:
• Please keep the MRO informed of changes in the location of the treatment system and collection tank.
• Please advise the MRO if additional treatment is planned to be added to the system to aid in the reduction
of the new 1 A Dioxane constituent.
• Please advise the MRO if the buyer is able to obtain a Brownfield Status.
The report should be self-explanatory. Should you have any questions regarding this report, feel free to contact Ed
Watson at edward.watson(a)ncdner.gov, or 704-235-2198.
Attachment: Compliance Inspection Report
Sincerely,
DocuSig ned by:
Loti ? .5_'J �T
For An reW94E� tt ' P.G., Assistant Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources
QE 3
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 I Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 IF I 3 I NCO088838 111 12 I 18/10/10 I17 18 I S J 19 L G] 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
1.0 70 I z I 71 I p JI 72 I I 73 I I I74 751 I I I I I I I80
I —I I I i
Section B: FacilityDataI�
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
10:OOAM 18/10/10
18/07/01
Radiator Specialty Company
600 Radiator Rd
Exit Time/Date
Permit Expiration Date
Indian Trail NC 28079
11:30AM 18/10/10
23/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Stuart A Kerkhoff/ORC/704-684-1815/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Stuart Kerkhoff,600 Radiator Rd Indian Trail NC 28079//704-684-1815/7046841868
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Facility Site Review Compliance Schedules Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Maria Schutte Division of Water Quality//704-663-1699)
Edward Watson MRO GW///
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
Lon Snider Lam- 'r S'ac, 1--
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NCO088838 I11 12, 18/10/10 117 18 JCJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
This permit recently renewed with new permit conditions for monitoring 1,4 Dioxande to be maintained
at a level of 80ug/L or below. The newly installed RW is being pumped on 10 minute cycles to avoid
exceeding the 80ug/I requirement. Alternate additional treatment may be required to maintain the 1,4
Dioxane parameter.
The facility ceased production at the end of August 2018. The property is in the process of being sold
and is currently under contract. The buyer may wish to have the tank farm removed and have the
treatement system and recovery tank re -located. The possibility of additional treatment and the
re -location of the tank and air stripper will likely require a permit modification. These changesd are yet
to be determined, but likely to occur. The cost to re -locate the treatement system has to be negotiated
between the two parties.
Being aware of the presence of the chlorinated solvent plume, the buyer has applied for a Brownfield
classification. The buyer is also aware that the treatment system will be required to be maintained.
However, Radiator Specialty is retaining ownership of the contaminant and will continue to maintain the
treatment system.
Page#
Permit: NCO088838 Owner - Facility: Radiator Specialty Company
Inspection Date: 10/10/2018 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The current Dermit was Dresent onsite and available for review. There is a sDecial condition
of monitoring 1 A Dioxane as this chemical is considered to be an emerging contminant.
Compliance Schedules Yes No NA NE
Is there a compliance schedule for this facility? M ❑ ❑ ❑
Is the facility compliant with the permit and conditions for the review period? 0 ❑ ❑ ❑
Comment: The first Dart of the October 2018 Chronic Toxicitv sample was collected on 10/09/2018
This facility historically Passes Chronic Toxicity testing.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility ceased manufactoring operations on August 31, 2018. The facility is currently
going through a slow shut -down phase as there is a significant quantity of manufactored
product that needs to be shipped or stored elseware.
The 2018 O&M records were reviewed during the sitie visit. The records are current and
complete.
Page# 3