HomeMy WebLinkAboutWQCSD0144_Compliance Evaluation Inspection_20180718 ROY COOPER ; a Cove,nor MICHAEL S. REGAN Secretary WaterResources LINDA CULPEPPER ENVIRONMENTAL QUALITY Intenm Director July 18, 2018 Mr. Ronnie Measamer Physical Plant Manager Central Carolina Community College 1105 Kelly Dr. Sanford,NC 27330 Subject: Compliance Evaluation Inspection Central Carolina Community College Collection System Collection System Permit No: WQCSD0144 Lee County Dear Mr. Measamer: On June 20, 2018, Cheng Zhang of the Raleigh Regional (RRO) Office Division of Water Quality conducted a Compliance Evaluation Inspection of the subject facility. The assistance and cooperation from Mr. Ben Rankin were very helpful and appreciated. A checklist of items is enclosed with this letter. During the inspection, the following items were noted: 1.) Central Carolina Community College holds a deemed sewer collection system permit at Central Carolina Community College in Lee County. There have been no reportable sanitary sewage overflow (SSO) incidents from the collection system, since the last inspection in December 2015. rt 2.) The collection system is comprised of gravity sewer, force main, and three pump stations (will take over two new pump stations in the near future). 3.) The facility has developed a map for the collection system. Please add pipe sizes, materials, approximate pipe age, service taps, and pump station capacities to the current map. 4.) The Spill Response Action Plan was reviewed during the inspection and found adequate. 5.) The three existing pump stations and the two new pump stations were visited during the inspection, the following was noted: ® -The operator used a calendar to record weekly pump station inspections, it is suggested that a logbook be used to document pump station inspections in details; Division of Water Resources,Raleigh Regional Office,Water Quality Operations Section http://portal.ncdenr.org/web/wq/aps 1628 Mail Service Center,Raleigh,NC 27699-1628 Phone. (919)791-4200 Location: 3800 Barrett Drive,Raleigh,NC 27609 Fax (919)788-7159 Central Carolina Community College Collection System , Permit No. WQCSD0144 e Pump station identifications need to be added to the stickers that were posted at existing pump stations. It is suggested to replace the stickers with permanent signs; • The wet well at the Main Pump Station at Kelly Dr. needs to be pad-locked. Please respond in writing to RRO within 30 days regarding Items 3 and 5. If you have any questions regarding the attached report or any of the findings, please contact Cheng Zhang at: (919) 791- 4200 (or email: cheng.zhang cLncdenr.gov). 77 Sincerely,---N ' k. /,---) j --,.--',/,1i/' /2 ,--(..--/ - .' S. Daniel Smith Regional Supervisor Raleigh Regional Office Attachments Inspection report. cc: RRO/SWP Files reentral Files Compliance Inspection Report Permit: WQCSD0144 Effective: 03/01/00 Expiration: Owner: Central Carolina Community College SOC. Effective Expiration: Facility: CCCC Sanford Collection System County: Lee Region: Raleigh Contact Person: Matthew Garrett Title. Phone: 919-542-8200 Directions to Facility: System Classifications Primary ORC: Certification, Phone: Secondary ORC(s): On-Site Representative(s): On-site representative Ben Rankin 919-775-5401 Related Permits: Inspection Date 06/20/2018 - Entry Time: 10.00AM Exit Time 12 00PM Primary Inspector: Cheng Zhang Phone. 919-791-4200 Secondary Inspector(s): - Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type: Deemed permitted collection system management and operation Facility Status: A Compliant ❑ Not Compliant Question Areas: CA Miscellaneous Questions 2 Performance Standards Operation&Maint Reqmts Records E Inspections co Pump Station (See attachment summary) Page 1 L Permit WOCSD0144 Owner-I acility Central Carolina Community College Inspection Date. 06/20/2018 Inspectio1 Type.Collection System Inspect Non Sampling Reason for Visit: Routine Performance Standards Yes No NA NE Is Public Education Program for grease established and documented? ❑ ❑ ❑ What educational tools are used'? Is Sewer Use Ordinance/Legal Authority available? ❑ ❑ 0 Does It appear that the Sewer Use Ordinance is enforced'? ❑ ❑ 0 Is Grease Trap Ordinance available'? ❑ ❑ 0 Is Septic Tank Ordinance available(as applicable,i.e.annexation) 00E10 List enforcement actions by permittee,if any,in the last 12 moniths Has an acceptable Capital Improvement Plan(CIP)been implmented? ❑ ❑ ❑ Does CIP address short term needs and long term 1"mastel plan\"concepts'? ❑ ❑ P 0 Does CIP cover three to five year period'? 0010 Does CIP include Goal Statement'? ❑ ❑ ❑ Does CIP include description of project area'? ❑ ❑ 0 Does CIP include description of existing facilities'? ❑ ❑ 0 Does CIP include known deficiencies'? ❑ ❑ ❑ Does CIP include forecasted future needs'? 00E10 Is CIP designated only for wastewater collection and treatrpent? 00E10 Approximate capital improvement budget for collection system'? Total annual revenue for wastewater collection and treatment? CIP Comments Not required Is system free of known points of bypass'? 000 If no,describe type of bypass and location Is a 24-hour notification sign posted at ALL pump stations'? E ❑ ❑ ❑ #Does the sign include Instructions for notification'? H ❑ ❑ ❑ Pump station identifier'? ❑ E1 ❑ ❑ 24-hour contact numbers MOOD If no,list deficient pump stations, Stickers are poste at the three existing pump stations,which la.ks pump station identifiers #Do ALL pump stations have an"auto polling"feature/SCADA 0000 Number of pump stations 3 Number of pump stations that have SCADA o Number of pump stations that have simple telemetry 3 Number of pump stations that have only audible and visual alarms 0 Number of pump stations that do not meet permit requirements 0 Page 3 r Permit' WQCSD0144 Owner-Facility:Central Carolina Community College Inspection Date: 06/20/2018 Inspection Type:Collection System Inspect Non Sampling Reason for Visit. Routine #Does the permittee have a root control program? ❑ ❑ 0 #If yes,date implemented? Describe Not needed Comment. Two new pump stations had been in operations but not the College was not in possesion. Inspections Yes No NA NE Are maintenance records for sewer lines available? 0 0 ❑ Are records available that document pump station inspections? 21 0 0 El Are SCADA or telemetry equipped pump stations inspected at least once a week? ® El 0 0 Are non-SCADA/telemetry equipped pump stations inspected every day? 0 0 ❑ Are records available that document citizen complaints? ❑ ❑ . 7 0 #Do you have a system to conduct an annual observation of entire system? ® ❑ ❑ ❑ #Has there been an observation of remote areas in the last year? 0 0 ❑ Are records available that document inspections of high-priority lines? ❑ ❑ ❑ Has there been visual inspections of high-priority lines in last six months? 0 0 ® ❑ Comment. The operator uses a calender to document pump station inspections. It is suggested that the operator starts to develop a logbook to document details of pump station inspections Operation&Maintenance Requirements Yes No NA NE Are all log books available? NE 0 0 ❑ Does supervisor review all log books on a regular basis? PM El El El Does the supervisor have plans to address documented short-term problem areas? 1 0 0 0 What is the schedule for reviewing inspection,maintenance,&operations logs and problem areas? Are maintenance records for equipment available? ❑ ❑ ® 0 Is a schedule maintained for testing emergency/standby equipment? - ❑ 0 • ❑ What is the schedule for testing emergency/standby equipment? Do pump station logs include Inside and outside cleaning and debris removal? ❑ EIS ❑ El Inspecting and exercising all valves? El ❑ 0 Inspecting and lubricating pumps and other equipment? El 1 ❑ 0 Inspecting alarms,telemetry and auialiary equipment? 0 Ed ❑ ❑ Is there at least one spare pump for each pump station w/o pump reliability? ❑ ❑ ❑ Are maintenance records for right-of-ways available? El ❑ Eil ❑ Are right-of-ways currently accessible in the event of an emergency? 0 0 V. 0 Are system cleaning records available? Cl ❑ El 0 Has at least 10%of system been cleaned annually? ❑ El El El What areas are scheduled for cleaning in the next 12 months? Page 4 ti Permit. WQCSD0144 Owner-Facility:Central Carolina Community College Inspection Date. 06/20/2018 Inspection Type.Collection System Inspect Non Sampling Reason for Visit. Routine Is a Spill Response Action Plan available? 'i 0 0 0 Does the plan include 24-hour contact numbers 0 0 0 Response time 0 0 0 Equipment list and spare parts inventory ❑ 0 0 Access to cleaning equipment 0 0 0 Access to construction crews,contractors,and/or engineers 0 0 0 Source of emergency funds El 0 ❑ ❑ Site sanitation and cleanup materials E71 0 0 0 Post-overflow/spill assessment • 0 0 0 Is a Spill Response Action Plan available for all personnel? I 0 0 0 Is the spare parts inventory adequate? ❑ 0 0 Comment The SRAP Is adequate. Records Yes No NA NE Are adequate records of all SSOs,spills and complaints available? 0 0 FE 0 Are records of SSOs that are under the reportable threshold available? 0 0 ❑ Do spill records indicate repeated overflows(2 or more in 12 months)at same location? 0 ❑ `" 0 If yes,is there a corrective action plan? 0 0 ❑ Is a map of the system available'? 0 0 0 Does the map include Pipe sizes ❑ 0 0 Pipe materials ❑ E ❑ ❑ Pipe location FM ❑ ❑ ❑ Flow direction E 0 0 0 Approximate pipe age 0 t, 0 0 Number of service taps 0 El 0 0 Pump stations and capacity ❑ 0 0 If no,what percent is complete? List any modifications and extensions that need to be added to the map Pipe sizes,materials,approximate pipe age,number of service:aps,and pump station capacities need to be added to the map #Does the permittee have a copy of their permit'? ❑ 0 11 ❑ Comment Deemed permitted. JOYNER HALL - Pump Station Yes No NA NE Pump station type Duplex Are pump station logs available'? RA 0 0 0 Page 5 Permit: WQCSD0144 Owner-Facility:Central Carolina Community College Inspection Date: 06/20/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit. Routine Is it accessible in all weather conditions? ;; ❑ ❑ ❑ #Is general housekeeping acceptable? 000 Are all pumps present? l ❑ ❑ ❑ Are all pumps operable? ® 0 ❑ 0 Are wet wells free of excessive debris? 111000 Are upstream manholes free of excessive debris/signs of overflow? 0 ❑ ❑ Are floats/controls for pumps/alarms operable? ❑ ❑ ❑ Is"auto polling"feature/SCADA present? 0011i0 Is"auto polling"feature/SCADA operational? ❑ ❑ ❑ Is simple telemetry present? 0 ❑ ❑ Is simple telemetry operational? d ❑ ❑ ❑ Are audio and visual alarms present? ❑ ❑ ❑ Are audio and visual alarms operable? 000 Is the Pump station inspected as required? 000 Are backflow devices in place? ❑ ❑ • ❑ Are backflow devices operable? ❑ ❑ ❑ Are air relief valves in place? ❑ ❑ ❑ Are air relief valves operable? ❑ ❑ ❑ # Is an emergency generator available? 01E00 Can the emergency generator run the pumps? ❑ ❑ ❑ Is the pump station equipped for quick hook-up? 00E110 Is the generator operable? ❑ ❑ ❑ #Is fuel in tank and sufficient? ❑ ❑ ❑ Is the generator inspected according to their schedule? 00110 Is a 24-hour notification sign posted? EI000 Does it include Instructions for notification? 0000 Pump station identifier?- ❑ E1 ❑ ❑ Emergency phone number Ell 000 Is public access limited? Off100 Is pump station free of overflow piping? E1 ❑ ❑ ❑ Is the pump station free of signs of overflow? 0 ❑ ❑ Are run times comparable for multiple pumps? Comment A sticker was posted,which lacks station ID VET TECH LAB - Pump Station Yes No NA NE Page 6 Permit: WQCSD0144 Owner-Facility:Central Carolina Community College Inspection Date• 06/20/2018 Inspection Type Collection System Inspect Non Sampling Reason for Visit: Routine Pump station type Duplex Are pump station logs available? ® El El ❑ Is it accessible in all weather conditions? i:f El ❑ ❑ #Is general housekeeping acceptable? ❑ ❑ El Are all pumps present? E ❑ ❑ 0 Are all pumps operable? El El El Are wet wells free of excessive debris? El ❑ ❑ Are upstream manholes free of excessive debris/signs of overflow'? ❑ ❑ ❑ Are floats/controls for pumps/alarms operable? El El El ❑ Is"auto polling"feature/SCADA present? ❑ ❑ 0 Is"auto polling"feature/SCADA operational? ❑ El El Is simple telemetry present? ® El ❑ ❑ Is simple telemetry operational? El ❑ ❑ El Are audio and visual alarms present? 4J El El El Are audio and visual alarms operable? El ❑ ❑ Is the Pump station inspected as required? 4 El El El Are backflow devices in place? ❑ ❑ ❑ Are backflow devices operable? ❑ El El Are air relief valves in place? El ❑ 4 ❑ Are air relief valves operable? ❑ ❑ E 0 # Is an emergency generator available? ❑ El El ❑ Can the emergency generator run the pumps? ❑ 0 1 El Is the pump station equipped for quick hook-up? El ,❑ 0 Is the generator operable? ❑ ❑ ri ❑ #Is fuel in tank and sufficient? El ❑ 113 El Is the generator inspected according to their schedule'? El El ® ❑ Is a 24-hour notification sign posted? E. ❑ El El Does it include Instructions for notification? El El El El Pump station identifier? 0 Ea El ❑ Emergency phone number E ❑ El ❑ Is public access limited? Ei ❑ El ❑ Is pump station free of overflow piping'? El p 0 0 Is the pump station free of signs of overflow'? ;= 0 ❑ ❑ Are run times comparable for multiple pumps? Comment: A sticker was posted,which lacks station ID. The station is equpped with a lockable cover. Page 7 • D S S m S 4t S It 3' > > > S D D y N m S D D D D D * m D 'o E m 3. -o -o p 0 3. 3 m m m m 3. m 3 � N v CD Co CD co co m CD m c 3 D — c m = 6 m 0 5 0 tJ Co c co m C) o 0 Cr o- m m m 3 3 0 - o -0 * w m CO m 12 .a Z o C - c) 03 3 T 2 .A (n m (0 3 = 0 � C' C) -c° n. o a o 0 m - -o -o o m 3 N In --I g n� cQ -0 0 = 3 7 m 3 c m m = o o m m o o m 3 3 v cn �_ n O a 3 o m 0 (o 0 .-.- 3 C CD CD a (D 3 3 o o -o w m co m = = C) m — y o m -- m o o o v 3 m o o O < < g w a a m m 3 ,03„ 3 a m s m m o m a 00 0 7 N `-G p (iii c0- 0 O T 0 - 3 0 611 < < 0 0 < < 3 3 l0 3 O 'o cci = ° a r 7 m a o o 3 o 0 v N 0- 0 m m 7 _ m m o m m v v a o m m X m in -< m 3 W 3, O (D = 7 O "' N N 3 o O C) O N v> = 0 U C C O, o N o• 3 N * N ': 6 N 0 n = C = Permit. WQCSD0144 Owner-Facility:Central Carolina Community College Inspection Date 06/20/2018 Inspectio Type.Collection System Inspect Non Sampling Reason for Visit: Routine Comment Posted stick faded badly and needs to be replaced The wet well needs to be pad locked Page 9