HomeMy WebLinkAboutNC0000019_Compliance Evaluation Inspection_20180823 ' ,�.SST�TEtwji
td..
i.' 4 1 iii°' 9�. _y,
ROY COOPER NORTH CAROLINA
Governor Environmental Quality
MICHAEL S.REGAN
Secretary
LINDA CULPEPPER
Interim Director
RECEIVEDIDE4R1D\N
August 23, 2018 SEP 0 5 Z01B
Mr. Steve Katz
Wager ReSgection
United Chemi-Con Permitting
185 Mc Neil Road
Lansing, NC 28643
SUBJECT: Compliance Evaluation Inspection
United Chemi-Con WWTP
NPDES Permit No. NC0000019
Ashe County
Dear Mr. Katz,
On August 21, 2018, Kelli Park and Gary Hudson of this office met with John
Turner, operator in responsible charge (ORC), to perform a Compliance Evaluation
Inspection on the United Chemi-Con wastewater treatment system. This type of
inspection consists of two basic parts: an in-office file review and an on-site inspection
of the treatment facility. The attached Environmental Protection Agency inspection form
notes the areas that were evaluated for this inspection. The findings and observations
are outlined below:
I. Permit
The NPDES permit became effective October 1, 2016, and expires on March 31, 2021.
There are multiple'outfalls at this plant. Primarily outfall 001 and 006 are used. Outfall
001 discharges the air compressor and cooling water effluent, while outfall 006 is the main
wastewater discharge from the plant. Outfalls 003 and 007 are not in use. Mr. Turner
mentioned that they could be used as backups to the main outfalls if there was to be a
problem.
II. Self-Monitoring Program
A review of the monthly discharge monitoring reports (DMR) for the period January 2017
through August 2018 showed that the facility complied with all permit limits.
NORTH CAROLINA
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 Hanes Mill Road,Suite 300 I Winston-Salem,North Carolina 27103
336.776.9800
United Chemi-Con,August 21,2018
Grab samples are taken from the effluent outfall 006.Time composite samples are taken "
from outfall 001. Three hundred milliliters of effluent are sampled every 30 minutes. This
is acceptable due to the flow being variable, rather than sampling proportionally to the
flow. The amount of flow through outfall 001 is directly tied to plant production and the
non-contact cooling water that is needed.
Ill. Records/Reports
The permit and visitation log are located on site and show visitation times and plant
conditions. Chain of custody forms are in good order. All required monitoring was
performed per the frequencies specified in the NPDES permit.
Miss Park noted no data transcription discrepancies from bench sheets to DMRs in her
documentation review.
IV. Flow Measurement
The instantaneous flow at outfall 006 is obtained by measuring the height of the water in
a 1-inch parshall flume and then converting it to flow.
There is a Stevens, Model 61 R flow meterat outfall 001 and it was calibrated this year.
V. Operations and Maintenance
The wastewater treatment plant appeared to be well maintained and operated. The ORC
and backup ORC are sufficiently qualified to be running the plant.
VI. Facility Site Review
All components of the 0.20 million gallons per day facility appeared to be functioning
properly. The influent goes through a bar screen, and flows through an Imhoff tank for the
solids to settle out. Mr. Turner mentioned that soda ash is sometimes added during the
summertime to help keep the pH at an acceptable level. The flow is then distributed
through a sand bed, which is evenly raked and has no odor. There was no evidence of
ponding in the sand bed. The dosing lines and concrete pads seemed to be in good
condition. Effluent is not recirculated, it goes straight from the sand beds to the receiving
stream. There is a clear path to where the effluent pipe discharges into the receiving
stream.
VII. Effluent/Receiving Waters
The effluent from the facility was clear the day of inspection at both outfall 001 and 006.
Effluent from both outfalls is discharged into the North Fork of the New River which is
classified as class C, high quality, water.
2
` United Chemi-Con,August 21,2018
i
VIII. Sludge Maintenance and Handling
Sludge was reported to be pumped about once or twice a year. Pumping is done by Doug
Cox Backhoe Service.
IX. Conclusions
The compliance evaluation inspection is satisfactory. Mr. Turner maintains and operates
the facility in a good manner. His efforts to comply with the permit are appreciated. If you
have any questions regarding the inspection or this report, please contact Kelli Park or
me at (336) 776-9800.
Sincerely,
Au,,,,i/-, 4
Sherri V. Knight, P.E.
Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments: BIMS EPA Water Compliance Inspection Report
cc: Central Files
WSRO
1 NPDES Unit 1
,
3
i
United States Environmental Protection Agency Form Approved
E PA Washington,D C 20460 OMB No 2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 , 2 [ I 3 I N00000019 111 12 I 18/08/21 117 18 Lo]I 19 12_1 2011
21111111 1111111 L1 11 1 11 1111 1 1 11 111 111111111 11 r6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved l
671 I 70 I I 71 1 I 72 L�1 �, 1 731 I 174 75i
1 1 1 1 1 1 180
Section B Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 10 30AM 18/08/21 16/10/01
United Chemi-Con
Exit Time/Date - Permit Expiration Date
185 McNeil Rd
12 OOPM 18/08/21 20/03/31
Lansing NC 28643
•
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
John Turner/ORC/336-384-2551/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Gale D Howel1,185 McNeil Rd Lansing NC 28643/Environment Health/Safety
Manager/336-384-6917/ No
Section C Areas Evaluated During Inspection(Check only those areas evaluated)
• Permit • Flow Measurement El Operations&Maintenance IN Records/Reports ,
• Self-Monitoring Program • Facility Site Review U Effluent/Receiving Waters
Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date7Q
Gary Hudson Division of Water Quality//336-776-96941 g I L"l t uR
Kelli A Park ' �G��L��� WSRO WQ//336-776-9689/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete
Page# 1
s
NPDES yr/mo/day Inspection Type 1
31 NC0000019 111 121 18/08/21 J 17 18 I-1
Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0000019 Owner-Facility: United Chemi-Con
Inspection Date' 08/21/2018 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less) Has the permittee submitted a new ❑ ❑ • ❑
application'?
Is the facility as described in the permit'? U ❑ ❑ ❑
#Are there any special conditions for the permit'? ❑ • ❑ ❑
Is access to the plant site restricted to the general public'? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection'? • 11100
Comment
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit'? • 000
Is all required information readily available, complete and current'? U ❑ ❑ ❑
Are all records maintained for 3 years(lab. reg required 5 years)? _ • 000
Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑
Is the chain-of-custody complete'? • ❑ ❑ ❑
Dates,times and location of sampling U
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs •
Are DMRs complete. do they include all permit parameters'? • ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ2 ❑ ❑ • ❑
(If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ E ❑
on each shift'?
Is the ORC visitation log available and current'? • 000
Is the ORC certified at grade equal to or higher than the facility classification'? U ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility classification'? • ❑ ❑ ❑
Is a copy of the current NPDES permit available on site'? MODE
Facility has copy of previous year's Annual Report on file for review'? ❑ ❑ • ❑
Comment
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping'? • 1: 00
Page# 3
e
Permit: NC0000019 Owner-Facility: United Chemi-Con
Inspection Date: 08/21/2018 Inspection Type* Compliance Evaluation
Operations & Maintenance Yes No NA NE
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable • El El ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Flow Measurement- Effluent Yes No NA NE
#Is flow meter used for reporting? ❑ • 0 ❑
Is flow meter calibrated annually? 0 ❑ U 0
Is the flow meter operational? • El ❑ El
(If units are separated) Does the chart recorder mach the flow meter? ❑ El ❑ •
Comment Measuring scale next to parshall flume to measure flow for outfall 006
Stevens Model 61R meter for outfall 001
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b Mechanical ❑
Are the'bars adequately screening debris? • 0 0 ❑
Is the screen free of excessive debris? • 0 El El
Is disposal of screening in compliance? ■ El 0 ❑
Is the unit in good condition? • ❑ 0 El
Comment
Sand Filters (Low rate) Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational? El ❑ El •
Is the distribution box level and watertight? • ❑ El ❑
Is sand filter free of ponding? • ❑ ❑ ❑
Is the sand filter effluent re-circulated at a valid ratic? ❑ El • ❑
#Is the sand filter surface free of algae or excessive vegetation? • ❑ El El
#Is the sand filter effluent re-circulated at a valid ram? (Approximately 3 to 1) ❑ ❑ MI El
Comment. not recirculated, goes straight to effluent pipe 006
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? El ❑ • El
Is sample collected below all treatment units? • El 0 ❑
Page# 4
a
Permit NC0000019 Owner-Facility: United Chemi-Con
Inspection Date: 08/21/2018 Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Is proper volume collected? • ❑ 0 0
Is the tubing clean? • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees • 0 0 0
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type • 0 ❑ 0
representative)?
Comment outfall 001 has a composite sampler that sampled 300m1 every 30 minutes This is
acceptable due to flow variation related to non-contact cooling water tied to plant production
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained'? • 0 0 0
Are the receiving water free of foam other than trace amounts and other debris'? • 0 0 0
If effluent (diffuser pipes are required) are they operating properly'? 0 0 • 0
Comment for outfall 001 and 006
Page# 5