HomeMy WebLinkAboutWQ0036766_Final Permit_20140110A4
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Resources
Water Quality Programs
Pat McCrory Thomas A. Reeder Johr E. Skvarla, III
Governor Director Secretary
January 10, 2014
E. Stephen Stroud — Owner
CP Plant, LLC
3605 Glenwood Ave., Suite 100
Raleigh, NC 27612
Dear Mr. Stroud:
Subject: Permit No. WQ0036766
Cedar Point WWTP
High -Rate Infiltration System
Carteret County
In accordance with your permit application received October 7, 2013, and subsequent additional
information received November 8, 2013, December 17, 2013, and January 6, 2014, we are forwarding
herewith Permit No. WQ0036766 dated January 10, 2014, to CP Plant, LLC for the construction and
operation of the subject wastewater treatment and high -rate infiltration facilities.
This permit shall be effective from the date of issuance until February 28, 2019, and shall be
subject to the conditions and limitations as specified therein. Please pay particular attention to the
monitoring requirements listed in Attachments A, B and C. Failure to establish an adequate system for
collecting and maintaining the required operational information shall result in future compliance
problems.
For your convenience, customized electronic copies of your facility's NDMR, and NDAR-2
reporting forms are available for download at: htt :/g /portal.nedenr.org//web/wqlaps/lau/reporting.
If any parts, requirements or limitations contained in this permit are unacceptable, the Permittee
has the right to request an adjudicatory hearing upon written request within 30 days following receipt of
this permit. This request shall be in the form of a written petition, conforming to Chapter 150B of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings at 6714 Mail
Service Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and
binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this permit, please contact Chonticha McDaniel at (919) 807-6337 or
chonticha.medainiel@ncdenr.gov.
Sincerely,
r
. 'ho as A. Reeder
WATER QUALITY PERMITTING SECTION
1636 Mail Service Center, Raleigh, North Carolina 27699-1636
Location: 512 N. Salisbury St., Raleigh, North Carolina 27604
Phone: 919-807-6464 h FAX: 919-807-6496
Internet: htt;11 ortal.ncdenr.or Iweb1w
An Equal Opportunity 1 Affirmative Action Employer
Mr. Stroud
January 10, 2014
Page 2 of 2
cc: Carteret County Health Department
Wilmington Regional Office, Water Quality Regional Operations Section
Robert G.Burgin, Jr., PE — Burgin Engineering, Inc. (PO Box 1844, Irmo, SC 29063)
Beth Buffington, Public Water Supply Section — Protection and Enforcement Branch
Permit File WQ0036766
Notebook File WQ0036766
I.
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
HIGH -RATE INFILTRATION SYSTEM PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules and Regulations
PERMISSION IS HEREBY GRANTED TO
CP Plant, LLC
Carteret County
FOR THE
construction and operation of a 15,000 gallon per day (GPD) wastewater treatment and high -rate
infiltration facility consisting of:
an influent duplex pump station; a flow splitter device; 2 parallel Magellan treatment trains, each train
includes a 3,880 -gallon primary clarifier/sludge holding tank, a 1,856 -gallon flow equalization tank, a
1,012 gallon pre -anoxic Moving Bed BiofiIm Reactor (MBBR), a 1,519 -gallon BOD removal MBBR, a
1,856 -gallon nitrification MBBR, a 1,013 -gallon post anoxic MBBR, a 1,613 -gallon secondary clarifier
stage one, a 1,613 -gallon secondary clarifier stage 2; one (1) 470 -gallon post aeration tank; one UV
disinfection unit (4 banks); chemical feed stations (for pH control, carbon, and alum feeds); a
turbidimeter; flow measuring devices; an auxiliary generator; a 77,578 gallon 5 -day upset lined pond; two
(2) 0.046 -acre infiltration basins; three (3) groundwater lowering wells; a level spreader (for groundwater
discharge to wetlands); and associated pumps, blowers, mixers, valves, and piping,
to serve Cedar Point WWTP, with no discharge of wastes to surface waters, pursuant to the application
received October 7, 2013, and subsequent additional information received by the Division. of Water
Resources, and in conformity with the project plans, specifications, and other supporting data
subsequently filed and approved by the Department of Environment and Natural Resources and
considered a part of this permit.
This permit shall be effective from the date of issuance until February 28, 2019, and shall be subject to
the following specified conditions and limitations:
SCHEDULES
In accordance with 15A NCAC 02T .0116, upon completion of construction and prior to operation of
this permitted facility, a certification (attached) shall be submitted from a licensed North Carolina
Professional Engineer certifying that the permitted facility has been installed in accordance with this
permit, Division approved plans and specifications, and other supporting documentation, including
the location of all monitoring wells as applicable. If this project is to be completed in phases and
partially certified the Permittee shall retain the responsibility to track further construction approved
under the same permit, and shall provide a final certificate of completion once the entire project has
been completed. Mail the Certification to the Division of Water Resources, Water Quality Pennitting
Section, 1636 Mail Service Center, Raleigh, NC 27699-1636.
WQ0036766 Version 1.0 Shell Version 131016 Page l of 10
Upon completion of construction and prior to operation of high rate infiltration basin, the basin shall
be inspected by a licensed Professional Geologist to verify that the constructed basins will be capable
of receiving the wastewater at the permitted loading rates. The results of this inspection, along with
the results of any testing performed shall be signed, sealed and submitted to the Water Quality
Permitting Section, Non -Discharge Permitting Unit, 1636 Mail Service Center, Raleigh, NC 27699-
1636.
3. The Wilmington Regional Office, telephone number (910) 796-7215, shall be notified at least 48
hours in advance (excluding weekends and holidays) of operation of the installed facilities such that
an in-place inspection can be made. Notification to the regional supervisor shall be made from 8:00
a.m. until 5:00 p.m. on Monday through Friday, excluding State Holidays.
4. Prior to operation of the facility, the Permittee shall submit annual registration and withdrawal
reporting forms for groundwater users of more than 10,000 gallons per day in accordance with the
Central Coastal Plain Capacity Use Area (CCPCUA) program. For more information, please visit
http://www.newater.org/CCPCUAreportonline.
The Wilmington Regional Office, telephone number (910) 796-7215, shall approve monitoring wells
MW -1, MW -2, and MW -3 prior to installation, and the monitoring wells shall be installed prior to
beginning waste disposal operations. The regional office shall be notified at least 48 hours prior to
the construction of any monitoring well, and such notification to the regional supervisor shall be
made from 8.00 a.m. until 5:00 p.m. on Monday through Friday, excluding State Holidays. The
monitoring wells shall be constructed such that the water level in the well is never above or below the
screened (open) portion of the well at any time during the year, and in accordance with 15A NCAC
02C .0108. The general location and name for each monitoring well is marked on Figure 2.
6. Within 60 days of completion of the monitoring wells, the Permittee shall submit two original copies
of a site map with a scale no greater than 1 -inch equals 100 feet; however, special provisions may be
granted upon prior approval for large properties. At a minimum, the map shall include the following
information:
a. The location and identity of each monitoring well.
b. The location of major components of the waste disposal system.
c. The location of property boundaries within 500 feet of the disposal areas.
d. The latitude and longitude of the established horizontal control monument.
e. The elevation of the top of the well casing (i.e., measuring point) relative to a common datum.
f. The depth of water below the measuring point at the time the measuring point is established.
g. The location of compliance and review boundaries.
h. The date the map is prepared and/or revised.
Control monuments shall be installed in such a manner and made of such materials that the
monument will not be destroyed due to activities taking place on the property_ The map and any
supporting documentation shall be sent to the Division of Water Resources, Water Quality Permitting
Section, 1636 Mail Service Center, Raleigh, NC 27699-1636,
7. A gauge to monitor waste levels in the five day upset pond shall be installed prior to operation.
Caution shall be taken not to damage the integrity of the liner (if present) when installing the gauge.
8. No later than six months prior to the expiration of this permit, the Permittee shall request renewal of
this permit on official Division forms. Upon receipt of the request, the Division will review the
adequacy of the facilities described therein, and if warranted, will renew the permit for such period of
time and under such conditions and limitations as it may deem. appropriate. Please note Rule 15A
NCAC 02T .0105(d) requires an updated site map to be submitted with the permit renewal
application.
WQ0036766 Version 1.0 Shell Version 131016 Page 2 of 10
9. In accordance with 15A NCAC 02H .0404(e), if the subject wastewater treatment or infiltration
facilities are in noncompliance with the terms and conditions of this permit, governing statutes or
regulations, the subject facilities shall be connected to an operational publicly owned wastewater
collection system within 180 days of its availability. Prior to the initiation of these connection
,activities, appropriate Division approval shall be received.
II. PERFORMANCE STANDARDS
1. The subject non -discharge facilities shall be effectively maintained and operated at all times so there
is no discharge to surface waters, nor any contravention of groundwater or surface water standards.
In the event the facilities fail to perform satisfactorily, including the creation of nuisance conditions
due to improper operation and maintenance, or failure of the infiltration areas to adequately assimilate
the effluent, the Permittee shall take immediate corrective actions including Division required actions,
such as the construction of additional or replacement wastewater treatment or infiltration facilities.
2. This permit shall not relieve the Permittee of their responsibility for damages to groundwater or
surface water resulting from the operation of this facility.
3. All wells constructed for purposes of groundwater monitoring shall be constructed in accordance with
15A NCAC 02C .0108 (Standards of Construction for Wells Other than Water Supply), and any other
jurisdictional laws and regulations pertaining to well construction.
4. The wastewater collection facilities shall be properly maintained and operated at all times. The
Permittee shall maintain compliance with an individual system -wide collection system permit for the
operation and maintenance of these facilities in accordance with 15A NCAC 02T .0400. If an
individual permit is not required, the following performance criteria shall be met as provided in 15A
NCAC 02T.0403.
a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to
land or surface waters, and any contravention of groundwater or surface water standards.
b. A map of the sewer system shall be developed and actively maintained.
c. An operation and maintenance plan shall be developed, implemented and maintained.
d. Pump stations not connected to a telemetry system shall be inspected every day (i.e., 365 days per
year). Pump stations connected to a telemetry system shall be inspected at least once per week.
e. High-priority sewers shall be inspected at least once every six months.
f. A general observation of the entire sewer system shall be conducted at least once per year.
g. Overflows and bypasses shall be reported to the Wilmington Regional Office in accordance with
15A NCAC 02B .0506(a), and public notice; shall be provided as required per North Carolina
General Statute §143-215.IC.
h. A grease control program shall be developed, implemented and maintained.
i. Right-of-ways and easements shall be maintained.
Inspection and maintenance records for Conditions II.4.a. through II.4.i. shall be maintained for a
period of at least three years, except for Conditions 11.4.b. and II.4.c., which shall be maintained
for the life of the system.
5. Effluent quality shall not exceed the limitations specified in Attachment A.
6. Application rates, whether hydraulic, nutrient or other pollutant, shall not exceed those specified in
1 Attachment B.
WQ0036766 Version 1.0 Shell Version I31016 Page 3 of 10
7. A usable green area shall be maintained for effluent disposal. The green area shall have the capability
of accommodating the facility's average daily flow without exceeding the green area loading rates.
As defined in 15A NCAC 02H .0404(g)(7), a "green area" is an area suitable for waste disposal,
either in its natural state or which has been modified by planting a vegetative cover of grasses or low
growing shrubbery.
The compliance boundary for the disposal system shall be specified in accordance with 15A NCAC
02L .0107(b). This disposal system was individually permitted on or after December 30, 1983;
therefore, the compliance boundary is established at either 250 feet from the effluent disposal area, or
50 feet within the property boundary, whichever is closest to the effluent disposal area. An
exceedance of groundwater standards at or beyond the compliance boundary is subject to remediation
action according to 15A NCAC 02L .0106(d)(2) as well as enforcement actions in accordance with
North Carolina General Statute 143-215.6A through 143-215.6C.
9. In accordance with 15A NCAC 02L .0108, the review boundary is established midway between the
compliance boundary and the effluent disposal area. Any exceedance of groundwater standards at the
review boundary shall require action in accordance with 15A NCAC 02L.0106.
10. The Permittee shall apply for a permit modification to establish a new compliance boundary prior to
any sale or transfer of property affecting a compliance boundary.
11. In accordance with 15A NCAC 02L _0107(d), no wells, excluding Division approved monitoring
wells, shall be constructed within the compliance boundary except as provided for in 15A NCAC 02L
.0107(g).
12. Except as provided for in 15A NCAC 02L .0107(g), the Permittee shall ensure any landowner who is
not the Permittee and owns land within the compliance boundary shall execute and file with the
Carteret County Register of Deeds an easement running with the land containing the following items:
a. A notice of the permit and number or other description as allowed in 15A NCAC 02L .0107(f)(1);
b. Prohibits construction and operation of water supply wells within the compliance boundary; and
Reserves the right of the Permittee or the State to enter the property within the compliance
boundary for purposes related to the permit.
The Director may terminate the easement when its purpose has been fulfilled or is no longer needed.
13. The facilities permitted herein shall be constructed according to the following setbacks:
a. The setbacks for high -rate infiltration sites permitted under 15A NCAC 02T .0700 shall be as
follows (all distances in feet):
i. Any habitable residence or place of public assembly under separate ownership;
ii. Any habitable residence or place of public assembly owned by the Permittee:
iii. Any private or public water supply source:
iv. Surface waters:
v. Groundwater lowering ditches:
vi. Surface water diversions:
vii. Any well with exception of monitoring wells:
viii. Any property line:
ix. Top of slope of embankments or cuts of two feet or more in vertical height:
x. Any water Iine from a disposal system:
xi. Subsurface groundwater lowering drainage systems:
xii. Any swimming pool:
100
50
100
100*
100*
50
100
50
100
10
100*
100
WQ0036766 Version 1.0 shell Version 131016 Page 4 of 10
xiii. Public right of way: 50
xiv. Nitrification field: 20
xv. Any building foundation or basement: 15
xvi. Impounded public water supplies: 500
xvii. Public shallow groundwater supply: 500
* Setbacks to surface waters, groundwater lowering ditches and subsurface groundwater
lowering drainage systems have been reduced to 100 feet because the treatment units are
designed to meet a Total Nitrogen of 7 mg/1 and a Total Phosphorus of 3 mg/l in accordance
with 15A NCAC 02T .0706(b).
b. The setbacks for storage and treatment units permitted under 15A NCAC 02T .0700 shall be as
follows (all distances in feet):
i. Any habitable residence or place of public assembly under separate ownership: 100
ii. Any private or public water supply source: 100
iii. Surface waters: 50
iv. Any well with exception of monitoring wells: 100
v. Any property line: 50
Ili. OPERATION AND MAINTENANCE RE UIREMENTS
I . The facilities shall be properly maintained and operated at all times. The facilities shall be effectively
maintained and operated as a non -discharge system to prevent the discharge of any wastewater
resulting from the operation of this facility. The Permittee shall maintain an Operation and
Maintenance Plan pursuant to 15A NCAC 02T .0707, which at a minimum shall include operational
functions, maintenance schedules, safety measures and a spill response plan.
2. Upon the Water Pollution Control System Operators Certification Commission's (WPCSOCC)
classification of the subject non -discharge facilities, in accordance with 15A NCAC 08G .0200 the
Permittee shall designate and employ a certified operator in responsible charge (ORC) and one or
more certified operator(s) as back-up ORC(s). The ORC or their back-up shall visit the facilities in
accordance with 15A NCAC 08G .0200, and shall comply with all other conditions specified in the
previously cited rules.
3. The facilities shall have 24-hour, 7 days per week operator support in order to effectively maintain
proper operation and ensure compliance with effluent limits.
4. The Permittee shall maintain a Sediment Control Plan for groundwater discharge at the level spreader
to ensure that sediment is not running into the wetlands.
5. Only effluent from Cedar Point WWTP shall be infiltrated on the sites listed in Attachment B.
6. An automatically activated standby power source capable of powering all essential treatment units
shall be on site and operational at all times. If a generator is employed as an alternate power supply,
it shall be tested weekly by interrupting the primary power source.
7. No automobiles or machinery shall be allowed on the infiltration sites except during equipment
installation or while maintenance is being performed.
8. Public access to the infiltration sites and wastewater treatment facilities shall be prohibited.
WQ0036766 Version 1.0 Shell Version 131016 Page 5 of 10
9. The residuals generated from the wastewater treatment facilities shall be disposed or utilized in
accordance with. 15A NCAC 02T .1100. The Permittee shall maintain a residual management plan
pursuant to 15A NCAC 02T.0708.
10. Diversion or bypassing of untreated or partially treated wastewater from the treatment facilities is
prohibited.
11. Freeboard in the five day upset pond shall not be less than two feet at any time.
12. A gauge to monitor waste levels in the five day upset pond shall be provided. This gauge shall have
readily visible permanent markings, at inch or tenth of a foot increments, indicating the following
elevations: maximum liquid level at the top of the temporary liquid storage volume; minimum liquid
level at the bottom of the temporary liquid storage volume; and the lowest point on top of the dam.
13. A protective vegetative cover shall be established and maintained on all earthen embankments (i.e.,
outside toe of embankment to maximum allowable temporary storage elevation on the inside of the
embankment), berms, pipe runs, erosion control areas, and surface water diversions. Trees, shrubs,
and other woody vegetation shall not be allowed to grow on the earthen, dikes or embankments.
Earthen embankment areas shall be kept mowed or otherwise controlled and accessible.
14. All effluent shall be routed to the five day upset pond should the limit for fecal coliform (e.g., daily
maximum concentration of 25 colonies per 100 mL) or turbidity (e.g., instantaneous maximum of 10
NTU) be exceeded, until the problems associated with the wastewater treatment plant have been
corrected. The wastewater in the five day upset pond shall be pumped back to the treatment plant
headworks for re -treatment or treated in the five day upset pond prior to infiltration.
15. The infiltration basin(s) shall be periodically swept to remove deposited materials that may impede
the infiltration process. Cleaning records shall be maintained at the facility for a period of no less
than five years, and shall be made available to the Division upon request. The Wilmington Regional
Office, telephone number (910) 796-7215, shall be notified prior to each cleaning.
IV. MONITORING AND REPORTING REQUIREMENTS
1. Any Division required monitoring (including groundwater, plant tissue, soil and surface water
analyses) necessary to ensure groundwater and surface water protection shall be established, and an
acceptable sampling reporting schedule shall be followed.
2. Per 15A NCAC 02H .0800, a Division certified laboratory shall conduct all laboratory analyses for
the required effluent, groundwater or surface water parameters.
3. Flow through the treatment facility shall be continuously monitored, and daily flow values shall be.
reported on Form NDMR.
The Permittee shall install and maintain an appropriate flow measurement device to ensure the
accuracy and reliability of flow measurement consistent with accepted engineering and scientific
practices. Selected flow measurement devices shall be capable of measuring flows with a maximum
deviation of less than ten percent from true flow; accurately calibrated at a minimum of once per year;
and maintained to ensure the accuracy of measurements is consistent with the selected device's
accepted capability. The Permittee shall maintain records of flow measurement device calibration on
file for a period of at least five years. At a minimum, documentation shall include:
a. Date of flow measurement device calibration,
b. Name of person performing calibration, and
c. Percent from true flow.
WQ0036766 Version 1.0 Shell Version 131016 Page 6 of 10
4. The Permittee shall monitor the effluent from the subject facilities at the frequencies and locations for
the parameters specified in Attachment A.
5. The Permittee shall maintain adequate records tracking the amount of effluent infiltrated. At a
minimum, these records shall include the following information for each infiltration site listed in
Attachment B:
a. Date of infiltration;
b. Volume of effluent infiltrated;
c. Loading rates to each infiltration site listed in Attachment B;
d. Weather conditions; and
6. Freeboard (i.e., waste level to the lowest embankment elevation) in the five day upset pond shall be
measured to the nearest inch or tenth of a foot, and recorded weekly. Weekly freeboard records shall
be maintained at the facility for a period of no less than five years, and shall be made available to the
Division upon request.
T Three copies of all monitoring data (as specified in Conditions IV.3. and IVA.) on Form NDMR for
each PPI and three copies of all operation and disposal records (as specified in Conditions IV -5. and
IV.6) on Form NDAR-2 for every site in Attachment B shall be submitted on or before the last day of
the following month. If no activities occurred during the monitoring mouth, monitoring reports are
still required documenting the absence of the activity. All information shall be submitted to the
following address:
Division of Water Resources
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
A record shall be maintained of all residuals removed from this facility. This record shall be
maintained at the facility for a period of no less than five years, and shall be made available to the
Division upon request. At a minimum, this record shall include:
a. Name of the residuals hauler;
b. Non -Discharge permit number authorizing the residuals disposal, or a letter from a municipality
agreeing to accept the residuals,
c. Date the residuals were hauled; and
d. Volume of residuals removed.
9_ A maintenance log shall be maintained at this facility. This log shall be maintained at the facility for
a period of no less than five years, and shall be made available to the Division upon request. At a
minimum, this log shall include:
a. Date and results of power interruption testing on alternate power supply;
b. Date of calibration of flow measurement device;
c. Visual observations of the plant and plant site; and
d. Record of preventative maintenance (e.g., changing of equipment, adjustments, testing,
inspections and cleanings, etc.).
10. Monitoring wells shall be sampled after construction and within 3 months prior to initiating non -
discharge disposal operations. Monitoring wells shall be sampled thereafter at the frequencies and for
the parameters specified in Attachment C. All mapping, well construction forms, well abandonment
forms and monitoring data shall refer to the permit number and the well nomenclature as provided
Attaclurnent C and Figure 2.
WQ0036766 Version 1.0 Shell Version 131016 Page 7 of 10
11. For initial sampling of monitoring wells, the Permittee shall submit a Compliance Monitoring Forni
(GW -59) and a Well Construction Record Fonn (GW -1) listing this permit number and the
appropriate monitoring well identification number. Initial Compliance Monitoring Forms (GW -59)
without copies of the Well Construction Record Forms (GW -1) are deemed incomplete, and may be
returned to the Permittee without being processed.
12. Two copies of the monitoring well sampling and analysis results shall be submitted on a Compliance
Monitoring Form (GW -59), along with attached copies of laboratory analyses, on or before the last
working day of the month following the sampling month. The Compliance Monitoring Form (GW -
59) shall include this permit number, the appropriate well identification number, and one GW -59a
certification form shall be submitted with each set of sampling results. All information shall be
submitted to the following address:
Division of Water Resources
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
13. Noncompliance Notification;
The Permittee shall report by telephone to the Wilmington Regional Office, telephone number (9 10)
796-7215, as soon as possible, but in no case more than 24 hours, or on the next working day
following the occurrence or first knowledge of the occurrence of any of the following:
a. Any occurrence at the facility resulting in the treatment of significant amounts of wastes that is
abnormal in quantity or characteristic, including the known passage of a hazardous substance.
b. Any process unit failure (e.g., mechanical, electrical, etc.), due to known or unknown reasons,
rendering the facility incapable of adequate wastewater treatment.
c. Any facility failure resulting in a by-pass directly to receiving surface waters.
d. Any time self-monitoring indicates the facility has gone out of compliance with its permit
limitations.
e. Effluent breakout from the infiltration basin(s).
Any emergency requiring immediate reporting (e.g., discharges to surface waters, imminent failure of
a storage structure, etc.) outside normal business hours shall be reported to the Division's Emergency
Response personnel at telephone number (800) 662-7956, (800) 858-0368, or (919) 733-3300.
Persons reporting such occurrences by telephone shall also file a written report in letter form within
five days following first knowledge of the occurrence. This report shall outline the actions taken or
proposed to be taken to ensure the problem does not recur.
V. INSPECTIONS
1. The Permittee shall provide adequate inspection and maintenance to ensure proper operation of the
wastewater treatment and infiltration facilities.
2. The Pcrmittee or their designee shall inspect the wastewater treatment and infiltration facilities to
prevent malfunctions, facility deterioration and operator errors resulting in discharges, which may
cause the release of wastes to the environment, a threat to human health or a public nuisance. The
Permittee shall maintain an inspection log that includes, at a minimum, the date and time of
inspection, observations made, and any maintenance, repairs, or corrective actions taken. The
Permittee shall maintain this inspection log for a period of five years from the date of the inspection,
and this log shall be made available to the Division upon request.
WQ0036766 Version 1.0 Shell Version 131016 Page 8 of 10
I Any duly authorized Division representative may, upon presentation of credentials, enter and inspect
any property, premises or place on or related to the wastewater treatment and infiltration facilities
permitted herein at any reasonable time for the purpose of determining compliance with this permit;
may inspect or copy any records required to be maintained under the terms and conditions of this
permit, and may collect groundwater, surface water or leachate samples.
VI. GENERAL CONDITIONS
1. Failure to comply with'the conditions and limitations contained herein may subject the Permittee to
an enforcement action by the Division in accordance with North Carolina General Statutes 143-
215.6A to 143-215.6C.
2. This permit shall become voidable if the permitted facilities are not constructed in accordance with
the conditions of this permit, the Division approved plans and specifications, and other supporting
documentation.
3. This permit is effective only with respect to the nature and volume of wastes described in the permit
application, Division approved plans and specifications, and other supporting documentation. No
variances to applicable rules governing the construction or operation of the permitted facilities are
granted, unless specifically requested and approved in this permit pursuant to 15A NCAC 02T
.0105(n).
4. The issuance of this permit does not exempt the Permittee from complying with any'and all statutes,
rules, regulations, or ordinances, which may be imposed by other jurisdictional government agencies
(e.g., local, state, and federal). Of particular concern to the Division are applicable river buffer rules
in 15A NCAC 02B .0200; erosion and sedimentation control requirements in 15A NCAC Chapter 4
and under the Division's General Permit NCG010000; any requirements pertaining to wetlands under
15A NCAC 02B .0200 and 02H .0500; and documentation of compliance with Article 21 Part 6 of
Chapter 143 of the General Statutes.
5. In the event the permitted facilities change ownership or the Permittee changes their name, a formal
permit modification request shall be submitted to the Division. This request shall be made on official
Division forms, and shall include appropriate property ownership documentation and other supporting
documentation as necessary. The Permittee of record shall remain fully responsible for maintaining
and operating the facilities permitted herein until a permit is issued to the new owner.
6. The Permittee shall retain a set of Division approved plans and specifications for the life of the
facilities permitted herein.
7. The Permittee shall maintain this permit until all permitted facilities herein are properly closed or
permitted under another permit issued by the appropriate permitting authority pursuant to 15A NCAC
02T.01056).
8. This permit is subject to revocation or unilateral modification upon 60 days notice from the Division
Director, in whole or part for the requirements listed in 15A NCAC 02T.0 I 10,
9. Unless the Division Director grants a variance, expansion of the permitted facilities contained herein
shall not be granted if the Permittee exemplifies any of the criteria in 15A NCAC 02T.0 I 20(b).
10. The Permittee shall pay the annual fee within 30 days after being billed by the Division. Failure to
pay the annual fee accordingly shall be cause for the Division to revolve this permit pursuant to 15A
NCAC 02T .0105(e)(3).
WQ0036766 Version 1.0 Shell Version 131016 Page 9 of 10
Permit issued this the 10"' day of January 2014
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
Jvr ho s A. Reeder, Director
Di sion of Water Resources
By Authority of the Environmental Management Commission
Permit Number WQ0036766