Subject: Compliance Evaluation Inspection
Single Family Wastewater Treatment System
Permit No.NCG551054
Orange County
Dear Permittee:
On September 24,2018,Jeremiah Dow and Zachary Thomas from the Raleigh Regional Office visited
your single-family residence(SFR)wastewater treatment system to evaluate compliance with the above
permit to discharge wastewater. The checked boxes below show what conditions were noted at your
facility:
n In compliance: You are reminded to regularly maintain the chlorine disinfection and
dechlorination systems,have the effluent sampled once a year, and have the septic tank pumped
out every 3 to 5 years. Your good record of operation and meeting the permit requirements is
highly commended.
n Your home is improperly plumbed: Some of the wastewater discharges are going directly to
the environment without first passing through the treatment system. This must be corrected
immediately. Please submit a schedule to this office within 20 days of receipt of this letter that
states your plan for correcting this deficiency. The work is to be completed within the next 3
months.
n !Disinfection: Your system is lacking disinfection, either chlorine tablets or a UV light system.
New rules put into place on August 1,2007 require all SFR systems to have a means of
disinfection(and dechlorination when chlorine tablets are used to disinfect, if the system was
installed since that date). Since your system had no disinfection,the installation is to include a
chlorine tablet dispenser, a contact chamber capable of providing a minimum 30 minute contact
i „. i-F-7-E7---:'1
y t1J1b1 NLL`l I. S
North Carolina Department of Environmental Quality I Division of Water Resources Quality I Raleigh Regional Office
1628 Mail Service Center I Raleigh,North Carolina 27699-1628
919 7914200
time, and another tablet dispenser that will hold dechlorination tablets. Please submit a schedule
to this office within 20 calendar days of receipt of this letter that states your plan for correcting
this deficiency.
® Treatment tablets missing or are wrong kind: You are responsible for always having
chlorine tablets and dechlorination tablets (if a required part of your system) in place. They must
be the kind for wastewater treatment and not for swimming pools.
nleclilorinnatiosn:Your system was installed after August 1;2007,so must have a means of
dechlorination_located downstream of the chlorinator and its contact chamber. See Disinfection
paragraph above. Please submit a schedule to this office within 20 calendar days of receipt of this
letter stating your plan for correcting this deficiency.
®'Pumping the septic tank: The septic tank should be pumped out every 3 to 5 years. A
pumping company can check the status periodically and determine when pumping is required.
/1 Failure to analyze the effluent: The effluent that is discharged from your system must be
analyzed once each year. See Part I(A) of your permit about his requirement. Please make
arrangements for sampling to be carried out within the next 3 months, and submit results to this
office within 3 weeks after the sampling has been done.
® Locations of treatment units are unknown: The effluent discharge pipe could not be
located at the time of the inspection. Determine the location and report to this office within 30
days of receipt of this letter with a sketch or map.
❑ Other:
If you have questions or comments about this inspection or the requirements to take corrective action,
please contact Jeremiah Dow at 919-791-4200. Licensed plumbers should be used to make plumbing
changes within your home. Contractors for installing disinfection or other equipment may be found in the
Yellow Pages under Environmental Consultants.
Sincerely
Yr-
S.Daniel Smith, Supervisor
Water Quality Regional Supervisor
Raleigh Regional Office
Attachments: Inspection Reports
cc: RRO/SWP Files
Charles Weaver,NPDES Permitting Unit
North Carolina Department of Environmental Quality I Division of Water Resources,Quality I Raleigh Regional Office
1628 Mail Service Center I Raleigh,North Carolina 27699-1628
919.791.4200
United States Environmental Protection Agency
Form Approved.
EPA
Washington,D C 20460 OMB No 2040-0057
Water Compliance Inspection Report, Approval expires 8-31-98
Section A National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 ILI 2 I5 I 3 I NCG551054 111 12 I 18/09/24 117 18 C 19 {J 20 Li
211111111111IIIIIIIIIIIIIII111111 IIIIIIIIIII r6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA — Reserved
67I I 70I I 71 I I 72 LJ LI 731 1 174 751 1 1 1 1 1 1 180
Section B Facility Data -
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number)
12 OOPM 18/09/24 07/08/01
1515 Indian Camp Road
1515 Indian Camp Rd Exit Time/Date Permit Expiration Date
Chapel Hill NC 27516 12.15PM 18/09/24 12/07/31
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Diane Farrington,1515 Indian Comp Rd Chapel Hill NC 27516//919-968-2523/
No
Section C Areas Evaluated Dunng Inspection(Check only those areas evaluated)
® Operations&Maintenance Ell Self-Monitoring Program Facility Site Review Effluent/Receiving Waters
Section D.Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Jeremiah J Dow Division of Water Quality//919-791-4248/
...----. 7 .
ign ture of Manag ment Q�A Re ie r Agency/Office/Phone and Fax Numbers Da e
a a v . 7/Y21 : l b/g/ / ( '1 27/c-Itt2VV 2� ,/3-7-fr.-/
EPA Form 35/0-3(Rev 9-94)Previous editions 4 e obsolete.
Page# 1
l
NPDES yr/mo/day Inspection Type 1
31 NCG551054 I11 121 18/09/24 117 18 I I
Section D.Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
•
Page# 2 ' -
Permit: NCG551054 Owner-Facility: 1515 Indian Camp Road
Inspection Date: 09/24/2018 Inspection Type. Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping'? Ci ❑ ❑ ❑
Does the facility analyze process control parameters, for ex. MLSS, MCRT, Settleable ❑ ❑ ® ❑
Solids, pH, DO, Sludge Judge, and other that are applicable'?
Comment.
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained'? ❑ E ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris'? ❑ ❑ ® ❑
If effluent (diffuser pipes are required) are they operating properly'? ❑ ❑ J ❑
Comment: Effluent pipe could not be located. Found what is believed
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational'? ❑ 0 ® ❑
Is septic tank pumped on a schedule'? ❑ ❑ ❑ ;,
Are pumps or syphons operating properly? 00110
Are high and low water alarms operating properly? ❑ ❑ ® ❑
Comment: Unknown if septic has been pumped
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? 01500
Are the tablets the proper size and type? ❑ ❑ ® ❑
Number of tubes in use'? 0
Is the level of chlorine residual acceptable? 0000
Is the contact chamber free of growth, or sludge buildup'? UNDO
Is there chlorine residual prior to de-chlorination'? ❑ ❑ i ❑
Comment- No tablets in chlorinator and base or chlorinator tube had some build up of black solids.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ ® ❑
Is sample collected below all treatment units'? ❑ ❑ ❑
Is proper volume collected'? ❑ ❑ , ❑
Is the tubing clean? ❑ ❑ r. ❑
#Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees ❑ ❑ ® ❑
Celsius)?
Page# 3
Permit: NCG551054
Owner-Facility: 1515 Indian Camp Road
Inspection Date: 09/24/2018
Inspection Type: Compliance Evaluation
Effluent Sarnplinc8 Yes No NA NE
Is the facility sampling performed as required by the permit(frequency,sampling type 1 ® 0 0
representative)?
Comment: Home owner could not answer questions at the time of the inspection and has not called,
therefore no lab results were received
Page# 4