HomeMy WebLinkAboutWQ0033406_Correction_20110518HCDEN
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Coieen H. Sullins
Governor Director
May 18, 2011
DR. MATTHEW GARRETT - PRESIDENT
CHATHAM COUNTY AND CENTRAL CAROLINA COMMUNITY COLLEGE
POST OFFICE BOX 1809
PITTSEORO, NORTH CAROLINA 27312
Dear Dr. Garrett:
Doe Freeman
Secretary
Subject: Permit No. WQ0033406
Correction
Central Carolina Community College
Conjunctive Reclaimed Water System
Chatham County
In accordance with a written request received on May 18, 2011 from Matthew Fleahman of the Raleigh
Regional Office's Aquifer Protection Section, we are forwarding herewith a corrected Attachment A for
Permit No. WQ0033406, issued May 26, 2009.
The following corrections have been made to the permit:
1. The requirement to monitor parameters Total Dissolved Solids (70300) and Chloride (00940) has
been removed,
2. All previous sample types listed as "Composite" have been changed to "Grab."
3. The requirement to continuously monitor and record effluent flows has been changed to a monthly
estimate.
4. The measurement frequency for pH has been reduced from "5 x Week" to "Weekly."
Please replace Attachment A with the corrected Attachment A into Permit No. WQ0033406, issued
May 26, 2009.
If you have any questions regarding this request, please do not hesitate to contact Nathaniel D. Thornburg
at (919) 715-6160. Thank you for your cooperation.
Sincerely,
Qr oleen H. Sullins
cc: Raleigh Regional Office, Aquifer Protection Section
Permit File WQ0033406
Notebook File WQ0033406
r,C—FER PRCTECT"Y SECTIO
1--- Pail SerJice Cer-e-, Raleigh.'Jorth C'^rc.na 27'99-103'
' -ccat:c,,. 2...
Ph -L%' 19-7133.322;'iFk 1:919 -?':i -05c : A`;?:91 71C-E'A8 C_ ...�•' S n c_.1•.';•02: 7a��11 t ..
nternet: www.ncwaterauaiitv.org E]""t� . 1 e! I IIi
%il ��rr �r � f • lc• r�Jk r r
'31 f fl✓L t•%'ai 6n►4 r
ATI'ACIIMENT A - LIMITATIONS AND MONITORING REQUIREMENTS
PPI 001— Reuse Tank Effluent (Prior to Landscape Utilization)
Permit Number: WQ0033406 Version: lA
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING
REQUIREMENTS
PCS
Code
Parameter Description
1ltontlrfy Average
Monthly Geometric
Nlean
Daily Minimum
Daily Maximum
Measurement
Measurement
Sample
Type
00310
BOD, 5 -Day (20'C)
10
ing/L
15
mg/L
4 x Year I
Grab
31616
Coliform, Fecal MF, M -FC Broth, 44.5 °C
14
#/100 mL
25
#1100 mL
4 x Year"
Grab
50050
Flow, in Conduit or thru Treatment Plant
GPD
Monthly
Estimate
00610
Nitrogen, Ammonia Total (as N)
4
mglL
6
mg/L
4 x Year
Grab
00620
Nitrogen, Nitrate Total (as N)
5
tng/L
10
mg/L
4 x Year
Grab
00400
pll
6
su
9
su
Weekly
Grab
00530
Solids, Total Suspended
5
mg/L
10
mg/L
4 x Year
Grab
00076
Turbidity, HCfI Turbidimeter
10
NTU
Continuous
Recorder
1. 4 x Year sampling shall be conducted in February, May, August and November.
2. Monthly average for Fecal Coliforn shall be a geometric mean.
PPI 002 — Mechanical Room Suffer Tank Effluent (Prior to Toilet Flush and Cooling Water Utilization.)
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING
REQUIREMENTS
PCS
Code
Parameter Description
Monthly Average
Monthly Geometric
dean
Daily Minimum
Daily Maximum
Measurement
Frequency
Sample
Type
00310
BOD, 5 -Day (20'C)
10
mg/L
15
rng/L
4 x Year
Grab
31616
Coliform, Fecal MF, M -FC Broth, 44.5C
14
#/100 mL
25
#1100 mL
4 x Year ix
Grab
50050
Flow, in Conduit or thru Treatment Plant
GPD
Monthly
Estimate
00610
Nitrogen, Ammonia Total (as N)
4
mg/L
6
mg/L
4 x Year'
Grab
(H)530
Solids, Total Suspended
5
mglL
10
mg/L
4 x Year
Grab
1. 4 x Year sampling shall be conducted in February, May, August and November.
2. Monthly average for Fecal Coliform shall be a geometric mean.
WQ0033406 Version 1.0 Attachment A Page 1 of 2
THIS PAGE BLANK