HomeMy WebLinkAboutWQ0022883_Final Permit_20031222A r�QG
Michael F. Easley, Governor
CQ William G. Ross Jr., Secretary
�- North Carolina Department of Environment and Natural Resources
0 �
Alan W. Klimek, P. E.., Director
Division of Water Quality
December 22, 2003
ANN ARADER, OWNER
305 N. WEST STREET
CARY, NC 27513
Dear Ms. Arader:
Subject: Permit No. WQ0022883
Single Family Residence
Surface Irrigation Facility
Chatham County
In accordance with your permit application request received July 24, 2003 and additional
information received December 1, 2003, we are forwarding herewith Permit No. WQ0022883, dated
December 22, 2003, to Ann Arader for the construction and continued operation of the subject single family
wastewater treatment and surface irrigation facilities.
This permit shall be effective to the date of issuance until November 30, 2008, and shall be subject
to the conditions and limitations as specified therein. Please pay particular attention to the monitoring
requirements in this permit. Failure to establish ran adequate system for collecting and maintaining the
required operational information will result in future compliance problems. Please pay special attention. to
Conditions V (3) and V (10).
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of this
permit. This request must be in the form of a written petition, conforming to Chapter 150B of the North
Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center,
Raleigh, NC 27699-6714. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this matter, please contact Toni Wyche at (919) 733-5083 extension 546.
Sincerely,
r
j4e
Alan W. Klimek, P. E.
cc: Chatham County Health Department
Raleigh Regional Office, Water Quality Section
Technical Assistance and Certification Unit
Bryan Staley, PE, Duane K. Stewart & Associates, Inc.
Water Quality Central Files
NDPU Files
Non -Discharge Permitting Unit Internet http://h2o.enr.state.nc.us/ndpu�+
1617 Mail Service Center, Raleigh, NC 27699-1617 Telephone (919) 733-5083 Fax (919) 715-6048
DENR Customer Service Center Telephone 1 800 623-7748
An Equal Opportunity Action Employer 50% recycled/10%a post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
SINGLE FAMILY RESIDENCE SURFACE RRIGA TION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended,
and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Ann Arader
Chatham County
FOR THE
construction and continued operation of a 360 gallon per day (GPD) surface spray irrigation wastewater treatment
and disposal system consisting of a 1,250 gallon baffled septic tank with effluent filter, two 168 square foot
primary sand filters, a tablet chlorinator disinfection unit, a 1,578 gallon storage tank, a 2,440 gallon pump tank, a
12 GPM pump, audio and visual high water alarms, rain sensor, 8,494.2 square feet of irrigation area with four
spray nozzles, and all associated piping and appurtenances to serve the Arader Residence, with no discharge of
wastes to the surface waters, pursuant to the application received July 24, 2003, and in conformity with the project
plan, specifications, and other supporting data subsequently filed and approved by the Department of
Environment and Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until November 30, 2008, and shall be subject to the
following specified conditions and limitations:
I. PERFORMANCE STANDARDS
I. Upon completion of construction and prior to operation of this permitted facility, a certification must
be received from a professional engineer certifying that the permitted facility has been installed in
accordance with this permit, the approved plans and specifications, and other supporting materials. If
this. project is to be completed in phases and partials certified, you shall retain the responsibility to
track further construction approved under the same permit, and shall provide a final certificate of
completion once the entire project has been completed. Mail the Certification to the Non -Discharge
Permitting Unit, 1617 Mail Service Center, Raleigh, NC 27699-1617.
2. The Raleigh Regional Office, telephone number (919) 571-4700, shall be notified at least forty-eight
(48) hours in advance of operation of the installed facilities so that an in -place inspection can be
made. Such notification to the regional supervisor shall be made during the normal office hours from
8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State Holidays.
The surface irrigation facilities shall be effectively maintained and operated at all times so that there
is no discharge to surface waters, nor any contamination of ground waters which will render them
unsatisfactory for normal use. In the event that the facilities fail to perform satisfactorily, including
the creation of nuisance conditions or failure of the irrigation area to adequately assimilate the
wastewater, the Pernttee shall take immediate corrective actions including those actions that may be
required by the Division of Water Quality (Division), such as the construction of additional or
replacement wastewater treatment and disposal facilities.
4. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to surface
or ground waters resulting from the operation of this facility.
The sand media of the subsurfacesand filter must comply with the Division's sand specifications. The
Engineer's Certification will serve as evidence that these specifications have been met.
b. A leakage test shall be performed on the septic tank and storage/pump tank(s) to insure that any
exfiltration occurs at a rate which does not exceed twenty (20) gallons per twenty-four (24) hours per
1,000 gallons of tank capacity. The Engineer's Certification will serve as proof of compliance with
this condition.
7. If excavation into bedrock is required for the installation of the septic tank or sand filter, the pit shall
be lined with a 10-mil synthetic liner.
8. A sanitary tee and filter shall be installed on the effluent pipe of the septic tank. The Engineer's
- - Certification will serve as evidence that these specifications have been met.
9. The residuals generated from these treatment facilities must be disposed in accordance with General
Statute 143-215.1 and in a manner approved by the Division.
10. Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited.
11. The following buffers shall be maintained:
a. 400 feet between wetted area and any residence or places of public assembly under separate
ownership,
b. 150 feet between wetted area and property lines,
c. 100 feet between wetted area and wells,
d. 100 feet between wetted area and drainage ways or surface water bodies,
e. 50 feet between wetted area and public right of ways,
f. 100 feet between treatment/storage units and any wells, and
g. 50 feet between treatment units and property lines.
12. The pump tank(s) shall have functional audible and visual high water alarms that are external to any
structure.
13. The disposal system shall be connected to a rain or moisture sensor that shall indicate when
wastewater application is not appropriate in accordance with Condition II(4).
11. OPERATION AND MAINTENANCE REQUIREMENTS
The facilities shall be properly maintained and operated at all times.
2. Upon classification of the wastewater treatment and surface irrigation facilities by the Water Pollution
Control System Operators Certification Commission (WPCSOCC), the Permittee shall designate and
employ a certified operator to be in responsible charge (ORC) and one or more certified operator(s) to
be back-up ORC(s) of the facilities in accordance with 15A NCAC 8G .0201. The ORC shall visit
the facilities in accordance with 15A NCAC 8G .0204 or as specified in this permit and shall comply
with all other conditions specified in these rules.
3. A suitable year round vegetative cover shall be maintained.
4. Irrigation shall not be performed during inclement weather or when the ground is in a condition that
will cause runoff.
5. Adequate measures shall be taken to prevent wastewater runoff from the irrigation field.
6. The application rate shall not exceed a cumulative loading of 26.7 inches over any twelve (12) month
period at an instantaneous application rate not to exceed 0.30 inches per hour.
The facilities shall be effectively maintained and operated as a non -discharge system to prevent the
discharge of any wastewater resulting from the operation of this facility.
No type of wastewater other than that from the Ann Arader Residence shall be sprayed onto the
irrigation area.
9. -- No traffic or equipment shall be allowed on the disposal area except while installation occurs or while
normal maintenance is being performed.
10. The irrigation field shall be fenced with at least a two -strand wire fence.
11. Wastewater treatment units open to the atmosphere shall have restricted access and pump control
panels shall be locked.
12. The Permittee is responsible for the operation and maintenance of the entire treatment and disposal
system including, but not limited to, the following items:
a. The septic tank shall be checked annually and pumped out as needed. The septic tank effluent
filter shall be checked and cleaned at the same frequency of the septic tank.
b. The tablet chlorinator shall be checked every week. Tablets shall be added to provide proper
chlorination.
c. The storage, pump, and alarm systems shall be inspected monthly. The scum layer shall be
removed at the same interval as the septic tank is cleaned out.
d. The system shall be inspected monthly to make certain of the proper operation of the spray
head(s), that the vegetative growth allows a proper spray pattern, that the soil is assimilating the
disposed treated wastewater with no surface runoff, and that no objectionable odors are being
generated.
III. MONITORING AND REPORTING REQUIREMENTS
Any monitoring deemed necessary by the Division to insure surface and ground water protection will
be established and an acceptable sampling reporting schedule shall be followed.
2. The Permittee shall maintain records of all maintenance performed on the system and irrigation area,
as required in Condition II(12) for a minimum of five years. This information shall be provided to the
Division upon request.
3. Noncompliance Notification:
The Permittee shall report by telephone to the Raleigh Regional Office, telephone number (919) 571-
} 4700, as soon as possible, but in no case more than 24 hours or on the next working day following the
occurrence or first knowledge of the occurrence of any of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of
adequate wastewater treatment, such as mechanical or electrical failures of pumps, spray heads,
etc.; or
b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to receiving
waters without treatment of all or any portion of the influent to such station or facility.
Occurrences outside normal business hours may also be reported to the Division's Emergency
Response personnel at telephone number (800) 858-0368 or (919) 733-3300. Persons reporting such
occurrences by telephone shall also file a written report in letterform within five (5) days following
first knowledge of the occurrence. This report must outline the actions taken or proposed to be taken
to ensure that the problem does not recur.
IV. INSPECTIONS
1. Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to insure proper
operation of the subject facilities.
2. Any duly authorized officer, employee, or representative of the Division may, upon presentation of
credentials, enter and inspect any property, premises or place on or related to the disposal site or
facility at any reasonable time for the purpose of determining compliance with this permit, may
inspect or copy any records that must be maintained under the terms and conditions of this permit,
and may obtain samples of groundwater, surface water, or leachate.
V. GENERAL CONDITIONS
1. This permit shall become void unless the facilities are constructed in accordance with the conditions
of this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
3. This permit is not transferable. In the event there is a desire for the facilities to change ownership, or
there is a name change of the Permittee, a formal permit request must be submitted to the Division
accompanied by documentation from the parties involved, and other supporting materials as may be
appropriate. The approval of this request will be considered on its merits and may or may not be
approved.
4. Upon the availability of a municipal or regional sewerage collection system, the subject wastewater
treatment facilities shall be abandoned and all wastewater discharged into the municipal or regional
sewerage system.
5. Failure to abide by the conditions and limitations contained in this permit may subject the Permittee
to an enforcement action by the Division in accordance with North Carolina General Statute 143-
215.6A to 143-215.6C.
6. The issuance of this permit does not preclude the Permittee from complying with any and all statutes,
rules, regulations, or ordinances which may be imposed by other government agencies (local, state,
and federal) which have jurisdiction.
4
This permit may be revoked if the Permittee fails to abide by the conditions of the "Operation and
Maintenance Agreement" previously signed by the Permittee.
A set of approved plans, specifications and operation and maintenance manual for the subject project
must be retained by the Permittee for the life of the project.
9. The annual administering and compliance fee must be paid by the Permittee within 30 days after
being billed by the Division. Failure to pay the fee accordingly may cause the Division to initiate
action to revoke this permit as specified by 15A NCAC 2H .0205 (c)(4).
10. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its extension.
Upon receipt of the request, the Come-fAssion will review the adequacy of the facilities described
therein, and if warranted, will extend the Permit for such period of time and under such conditions
and limitations, as it may deem appropriate.
Permit issued this the 22"' day of December, 2003
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
Alan W. Klimek P-E:, Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0022883
Permit No. WQ0022883
December 22, 2003
ENGINEER'S CERTIFICATION
Partial Final
I, , as a duly registered Professional Engineer in the State of North
Carolina, having been authorized to observe (periodically, weekly, full time) the construction of the project,
Project Name
Location and County
for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the
construction such that the construction was observed to be built within substantial compliance and intent of this permit,
the approved plans and specifications, and other supporting materials.
Signature
Date
Registration No.
r,
V
_� �' .(`�, N� �� � ...t�'- - �__� � !i zee a ��J ++ �✓� � (y tl j
+ � �(
eM
. , a-_ - -- � !I 5F'�,•�Q_y Q- _-=-�tY `; i� r Il- , D,.F
L t
v
it
Site Location
Ann Arader SFR ` \
�•� ;r -��; .: WQ0022883 }� , }
Chatham County • az3 1, 1, 7aa41
/ j r
o\ _ , 1*\ . 1 I j//� \��\ //ram- � r •' 'S 11 � „C _
� , , .1 �._ it ti , i ,, II t ,�<�; • � �., •'� --
r
- 'n
1P
71
�.!'J• , L I,'F l �f (z °;_ c _ �' !�/, / � ! lit "_ �'F'', , it { r �'I.
+��. �- 5 r, ' � � J: ,1 = f i ��1� ll � ;' .. f, r 1 � AF J �$ I L� � .ti"��. � •�.��
�23S`„r
_ Imo\ r'- \ - i{ `'.;, ,�&/f;lil`.a�.:;IF 1'I 1� I • ' �� "'� j -}� �;
in
C
OPERATION AND MAINTENANCE AGREEMENT
SINGLE FAMILY RESIDENCE WASTEWATER TREATMENT SYSTEM
DIVISION OF WATER QUALITY
Ms: Ann Arader
305 N. West St.
Cary, NC 27513
,v
Disposal Method: SPRAY IRRIGATION
County: Chatham Permit No.
I agree to operate and maintain the wastewater treatment system as follows:
1) The Permittee is responsible for the operation and maintenance of the entire treatment and disposal system
including, but not limited to, the following items:
a) The septic tank shall be checked annually and pumped out as needed. The effluent filter shall be checked
and cleaned at the same frequency of the septic tank.
b) Check one:
• The tablet chlorinator shall be checked every week. Tablets shall be added so as to provide proper
chlorination.
o The ultraviolet disinfection unit shall be checked every week. The lamp shall be cleaned and/or
replaced to ensure proper disinfection.
c) The storage, pump, and alarm systems shall be inspected monthly. The scum layer shall be removed at the
same time interval as the septic tank is pumped out.
d) The irrigation system shall be inspected monthly to make certain of proper operation, that vegetative
growth does not interfere with the system inspection or operation, that the soil is assimilating the disposed
treated wastewater with no surface runoff, and that no objectionable odors are being generated.
2) Failure of the Permittee to property operate this system is subject to a penalty up to $25,000 per day.
3) Failure to meet the permit conditions or violation of the State's surface or groundwater regulations will require
evacuating the dwelling and may void the permit.
I understand the above requirements and agree to these terms as part of the issued permit.
Date: d ZU
y Commission Expires: my � l e