Loading...
HomeMy WebLinkAboutWQ0022224_Final Permit_20080623June 23, 2008 The Honorable Jody L. McLeod - Mayor Town of Clayton Post Office Box 879 Clayton, North Carolina 27520-0879 Dear Mayor McLeod: Michael F. Easley, Governor William G. Ross Jr„ Secretary North Carolina Department of Environment and Natural Resources Coleen H. Sullins Director Division of Water Quality Subject: Permit No. WQ0022224 Town of Clayton Conjunctive Wastewater Generation and Reclaimed Water Utilization System Johnston County In accordance with your permit modification request received April 9, 2008, we are forwarding herewith Permit No. WQ0022224, dated June 23, 2008, to the Town of Clayton for the continued operation of the subject wastewater treatment and reclaimed water utilization facilities. This modification includes changes to the requirements of the maintenance log (Condition N.7). This permit shall be effective from the date of issuance until September 19, 2011, shall void Permit No. WQ0022224 issued September 20, 2006, and shall be subject to the conditions and limitations as specified therein. Please pay particular attention to the monitoring requirements in this permit. Failure to establish an adequate system for collecting and maintaining the required operational information will result in future compliance problems. Please note that effluent sampling parameters and frequencies have been changed (Attachment A). If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This request must be in the form of a written petition, conforming to Chapter 150B of the North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-6714. Unless such demands are made this permit shall be final and binding. If you need additional information concerning this matter, please contact Matthew Fleahman at (919) 715-6173 or matthew.fleahman@ncmail.net. Sincerely 4� — -'/—Coleen H. Sullins cc: Johnston County Health Department Raleigh Regional Office, Aquifer Protection Section Technical Assistance and Certification Unit (with rating sheet attached) APS Central Files LAU Files One NorthCarolina ,JUatura!!y Aquifer Protection Section 1636 Mail service Center Raleigh, NC 27699-1636 Telephone: (919) 733-3221 intemet: www.ncwaterguality.org Location: 2728 Capital Boulevard Raleigh. NC 27604 Fax 1: (919) 715-0588 Fax 2: (919) 715-6049 An Equal Opportunity/Affirmative Action Employer- 50% Recycled/10% Post Consumer Paper Customer Service: (877) 623-6748 NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES RALEIGH CONJUNCTIVE WASTEWATER TREATMENT AND RECLAIMED WATER UTILIZATION SYSTEM PERMIT In accordance with the provisions of .Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations PERMISSION IS HEREBY GRANTED TO Town of Clayton Johnston County FOR THE continued operation of a 237,840 gallon per day (GPD) wastewater generation and reclaimed water utilization facility consisting of. approximately 11,265 linear -feet of 6-inch reclaimed water main, 8,621 linear -feet of 8-inch reclaimed water main (including 875 feet of 10-inch HDPE directional drill), effluent transfer pump station with two 300 gallon per minute (gpm) pumps, a turbidity meter, chlorine feed equipment, associated appurtenances and piping to serve the Town of Clayton, with no discharge of wastes to the surface waters, pursuant to the application received April 9, 2008, and subsequent additional information received by the Division of Water Quality (Division), and in conformity with the project plan, specifications, and other supporting data subsequently filed and approved by the Department of Environment and Natural Resources and considered a part of this permit. This permit shall be effective from the date of issuance until September 19, 2011 shall void Permit No. WQ0022224 issued September 20, 2006, and shall be subject to the following specified conditions and limitations: I. SCHEDULES [please review the entire permit for reporting, monitoring, and other on -going activities] No later than six months prior to the expiration of this permit, the Permittee shall request renewal of this permit on official Division forms. Upon receipt of the request, the Division will review the adequacy of the facilities described therein, and if warranted, will extend the permit for such period of time and under such conditions and limitations as it may deem appropriate. Please note that Rule 15A NCAC 02T .0105(d) requires an updated site map to be submitted with the permit renewal application. WQ0022224 Version 1.1 Shell Version 070320 Page 1 of 7 11. PERFORMANCE STANDARDS I. The reclaimed water utilization facilities shall be effectively maintained and operated at all times so that there is no discharge to the surface waters, nor any contamination of ground waters, which will render them unsatisfactory for normal use. In the event that the facilities fail to perform satisfactorily, including the creation of nuisance conditions or failure of the utilization area to adequately assimilate the wastewater, the Permittee shall take immediate corrective actions including those actions that may be required by the Division of Water Quality (Division), such as the construction of additional or replacement wastewater treatment and disposal facilities. 2. The issuance of this permit shall not Telieve the Permittee of the responsibility for damages to ground or surface waters resulting from the operation of this facility. 3. Effluent limitations shall not exceed those specified in Attachment A. 4. The Town of Clayton is authorized to distribute its generated reclaimed water to the following facilities: Authorized Recipient Permit Number Annual Averaged Capacity allon!Lda ) Pine Hollow Golf Club WQ0024223 237,840 Total Authorized Capacity 237,840 5. The Permittee shall apply for a permit modification prior to any sale or transfer of property that affects a compliance boundary to establish a new compliance boundary. 6. In accordance with 15A NCAC 02L .0107(d), no wells, other than monitoring wells, shall be constructed within the compliance boundary except as provided by 15A NCAC 02L .0107(g). 7. The facilities permitted herein must be constructed according to the following setbacks: a. The setbacks for reclaimed utilization sites shall be as follows (all distances in feet): i. Surface waters not classified SA: 25 ii. Surface waters classified SA: 100 iii. Any well with exception to monitoring wells 100 b. The setbacks for treatment and storage units shall be as follows (all distances in feet): i. Any well with exception of monitoring wells: 100 ii. Any property line: 50 8. The following shall be requirements for the reclaimed water distribution, storage, and utilization facilities: a. All reclaimed water valves, storage facilities, and outlets shall be tagged or labeled to warn the public or employees that the water is not intended for drinking. Where appropriate, such warning shall inform the public or employees to avoid contact with the water. b. All reclaimed water piping, valves, outlets, and other appurtenances shall be color -coded, taped, or otherwise marked to identify the source of the water as being reclaimed water. i. All reclaimed water piping and appurtenances shall be either colored purple (i.e., Pantone 522) and embossed or integrally stamped or marked "CAUTION: RECLAIMED WATER — DO NOT DRINK" or be installed with a purple (i.e., Pantone 522) identification tape or WQ0022224 Version l .l Shell Version 070320 Page 2 of 7 polyethylene vinyl wrap. The warning shall be stamped on opposite sides of the pipe and repeated every three feet or less. ii. Identification tape shall be at least three inches wide and have white or black lettering on purple (i.e., Pantone 522) field stating "CAUTION: RECLAIMED WATER — DO NOT DRINK." Identification tape shall be installed on top of reclaimed water pipelines, fastened at least every 10 feet to each pipe length and ran continuously the entire length of the pipe. iii. Existing underground distribution systems retrofitted for the purpose of distributing reclaimed water shall be taped or otherwise identified as noted above. This identification need not extend the entire length of the distribution system, but shall be incorporated within 10 feet of crossing any potable water supply line or sanitary sewer4ine. c. All reclaimed water valves and outlets shall be of a type, or secured in a manner, that permits operation by authorized personnel only. d. Above -ground hose bibs (i.e., spigots or other hand -operated connections) shall not be present. Hose bibs shall be located in locked below -grade vaults that shall be clearly labeled as being of non -potable quality. As an alternative to the use of locked below -grade vaults with standard hose bibs services, hose bibs, which can only be operated by a special tool or connected to a special hose connection, may be placed in non -lockable underground services boxes clearly labeled as non -potable water. 9. The Permittee shall maintain an active cross -connection control program that shall have the following minimum requirements: a. No direct cross -connections shall be allowed between the reclaimed water and potable water systems. b. A reduced pressure principle backflow preventer, an approved air gap separation, or other device approved by the Division of Environmental Health shall be installed at the potable water service connection to the use area where both reclaimed water and potable water are supplied to a reclaimed water use area. The installation of the reduced pressure principle backflow prevention device shall allow proper testing. c. An air gap separation, approved and regularly inspected by the Permittee shall be provided between the potable water and reclaimed water systems where potable water is used to supplement a reclaimed water system. 10. Reclaimed water distribution lines shall be located 10 feet horizontally from and 18 inches below any water line where practicable. Where these separation distances cannot be met, the piping and integrity testing procedures shall meet water main standards in accordance with 15A NCAC 18C. 11. Reclaimed water distribution lines shall not be less than 100 feet from a well unless the piping and integrity testing procedures meet water main standards in accordance with 15A NCAC 18C, but no case shall they be less than 25 feet from a private well or 50 feet from a public well. 12. Reclaimed water distribution lines shall meet the separation distances to sewer lines in accordance with Rule .0305 of Subchapter 02T. M. OPERATION AND MAINTENANCE REQUIREMENTS The facilities shall be properly maintained and operated at all times. The facilities shall be effectively maintained and operated as a non -discharge system to prevent the discharge of any wastewater resulting from the operation of this facility. The Permittee shall maintain an Operation and Maintenance Plan pursuant to 15A NCAC 02T .0913 including operational functions, maintenance schedules, safety measures, and a spill response plan. WQ0022224 Version 1.1 Shell Version 070320 Page 3 of 7 Upon classification of the wastewater treatment and reclaimed utilization facilities by the Water Pollution Control System Operators Certification Commission (WPCSOCC), the Permittee shall designate and employ a certified operator to be in responsible charge (ORC) and one or more certified operator(s) to be back-up ORC(s) of the facilities in accordance with 15A NCAC 08G .0200. The ORC shall visit the facilities in accordance with 15A NCAC 08G .0200 or as specified in this permit and shall comply with all other conditions specified in these rules. 3. The residuals generated from these treatment facilities must be disposed / utilized in accordance with 15A NCAC 02T A 100. The Permittee shall maintain a residual management plan pursuant to 15A NCAC 02T .0914. 4. Should the limit for fecal coliform (daily maximum concentration of 25 per 100 ml) or turbidity (instantaneous maximum of 10 NTU) be exceeded, all wastewater shall be handled in one of three ways until the Ievels have stabilized below these maximum levels. The Permittee may further treat the wastewater to bring it into compliance with reclaimed water standards without returning the water to the facility's headworks, may reroute it to the headworks of the wastewater treatment facility for treatment to reuse standards, or may discharge it in strict accordance with the conditions of the facility's existing NPDES Permit No. NC0025453. IV. MONITORING AND REPORTING REQUIREMENTS 1. Any monitoring (including groundwater, surface water, soil or plant tissue analyses) deemed necessary by the Division to ensure surface and ground water protection will be established and an acceptable sampling reporting schedule shall be followed. 2. All laboratory analyses for effluent, ground waters, or surface waters shall be made by a laboratory certified by the Division for the required parameter(s) under 15A NCAC 02H .0800. 3. Flow through the treatment facility shall be continuously monitored and daily flow values shall be reported on Form NDMR, The Permittee shall maintain an appropriate flow measurement device consistent with approved engineering and scientific practices to ensure the accuracy and reliability of flow measurement. Flow measurement devices selected shall be capable of measuring flows with a maximum deviation of less than 10 percent from true flow, accurately calibrated at a minimum of once per year, and maintained to ensure that the accuracy of the measurements is consistent with the accepted capability of that type of device. The Permittee shall keep records of flow measurement device calibration on file for a period of at least three years. At a minimum, data to be included in this documentation shall be; a. Date of flow measurement device calibration, b. Name of person performing calibration, and c. Percent from true flow. 4. The effluent from the subject facilities shall be monitored by the Permittee at the frequency(ies) and location(s) for the parameter(s) specified in Attachment A. 5. Three copies of all monitoring data [as specified in Conditions W.3. and IVA] on Form NDMR for each point prior to irrigation (PPI) shall be submitted on or before the last day of the following month. If no activities occurred during the monitoring month, monitoring reports are still required documenting the absence of the activity. All information shall be submitted to the following address, Division of Water Quality Information Processing Unit 1617 Mail Service Center Raleigh, North Carolina 27699-1617 WQ0022�24 Version 1.1 Shell Version 070320 Page 4 of 7 6. A record shall be maintained of all residuals removed from this facility. This record shall include the name of the hauler, permit authorizing the disposal or a letter from a municipality agreeing to accept the residuals, date the residuals were hauled, and volume of residuals removed. 7. A maintenance log shall be maintained at this facility including but not limited to the following items: a. Visual observations of the plant and plant site. b. Record of preventative maintenance (changing of filters, adjusting belt tensions, alarm testing; diffuser inspections and cleanings, etc.). c. Date of calibration of flow measurement device. d. Date and results of power interruption testing on alternate power supply. 8. Noncompliance Notification: The Permittee shall report by telephone to the Raleigh Regional Office, telephone number (91.9) 791- 4200 as soon as possible, but in no case more than 24 hours or on the next working day following the occurrence or first knowledge of the occurrence of any of the following: a. Any occurrence at the wastewater treatment facility which results in the treatment of significant amounts of wastes which are abnormal in quantity or characteristic, such as the dumping of the contents of a sludge digester; the known passage of a slug of hazardous substance through the facility; or any other unusual circumstances including ponding in the reclaimed utilization area or runoff from the reclaimed utilization areas. b. Any process unit failure, due to known or unknown reasons, that render the facility incapable of adequate wastewater treatment such as mechanical or electrical failures of pumps, aerators, compressors, etc. c. Any failure of disposal system resulting in a by-pass directly to receiving waters. d. Any time that self -monitoring information indicates that the facility has gone out of compliance with its permit limitations including, but not limited to, freeboard measurements, effluent limitations, exceedances of groundwater standards, or overloading of any utilization area. For any emergency that requires immediate reporting (e.g., discharges to surface waters, imminent failure of a storage structure, etc.) outside normal business hours must be reported to the Division's Emergency Response personnel at telephone number (800) 662-7956, (800) 858-0368, or (919) 733- 3300. Persons reporting such occurrences by telephone shall also file a written report in letter form within five (5) days following first knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to ensure that the problem does not recur. V. INSPECTIONS 1. Adequate inspection and maintenance shall be provided by the Permittee to ensure proper operation of the subject facilities. 2. The Permittee or his designee shall inspect the wastewater treatment and disposal facilities to prevent malfunctions and deterioration, operator errors and discharges which may cause or lead to the release of wastes to the environment, a threat to human health, or a nuisance. The Permittee shall keep an inspection log or summary including at least the date and time of inspection, observations made, and any maintenance, repairs, or corrective actions taken by the Permittee. This log of inspections shall be maintained by the Permittee for a period of five years from the date of the inspection and shall be made available upon request to the Division or other permitting authority. WQ0022224 Version 1.1 Shell Version 070320 Page 5 of 7 3. Any duly authorized officer, employee, or representative of the Division may, upon presentation of credentials, enter and inspect any property, premises or place on or related to the disposal site or facility at any reasonable time for the purpose of determining compliance with this permit; may inspect or copy any records that must be maintained under the terms and conditions of this permit, and may obtain samples of groundwater, surface water, or leachate. VI. GENERAL CONDITIONS 1. Failure to abide by the conditions and limitations contained in this permit may subject the Permittee to an enforcement action by the Division in accordance with North Carolina General Statute 143- 215.6A to 143-215.6C. ` 2. This permit shall become voidable unless the facilities are constructed in accordance with the conditions of this permit, the approved plans and specifications, and other supporting data. 3. This permit is effective only with respect to the nature and volume of wastes described in the application and other supporting data. No variances to applicable rules governing the construction and / or operation of the permitted facilities are granted unless specifically requested and granted in this permit. 4. The issuance of this permit does not exempt the Permittee from complying with any and all statutes, rules, regulations, or ordinances, which may be imposed by other government agencies (local, state, and federal) that have jurisdiction. Of particular concern to the Division are applicable river buffer rules in 15A NCAC 02B .0200, erosion and sedimentation control requirements in 15A NCAC Chapter 4 and under the Division's General Permit NCGO10000, and any requirements pertaining to wetlands under 15A NCAC 02B .0200 and 02H .0500. 5. In the event there is a desire for the facilities to change ownership, or there is a name change of the Permittce, a formal permit request must be submitted to the Division on official Division forms, documentation from the parties involved, and other supporting materials as may be appropriate. The approval of this request will be considered on its merits and may or may not be approved. The Permittee of record shall remain fully responsible for compliance until a permit is issued to the new owner. 6. The Permittee shall retain a set of approved plans and specifications for the life of the facilities permitted herein. The Permittee shall maintain this permit until all permitted facilities herein are properly closed or permitted under another permit issued by the appropriate permitting authority. The Permittee must pay the annual fee within 30 days after being billed by the Division. Failure to pay the fee accordingly may cause the Division to initiate action to revoke this permit pursuant to 15A NCAC 02T .0105(e). 9. This permit in no way negates, precludes, or invalidates the most recent reissuance of NPDES Permit No. NC0025453, and the Permittee shall continue to comply with all conditions provided for therein. WQ0022224 Version 1.1 Shell Version 070320 Page 6 of 7 Permit issued this the 23rd day of June 2008 NORTH C OLINA E NMENTAL MANAGEMENT COMMISSION Coleen H. Sullins, Director Division of Water Quality By Authority of the Environmental Management Commission Permit Number WQ0022224 WQ0022224 Version 1.1 Shell Version 070320 Page 7 of 7 ATTACHMENT A - LIMITATIONS AND MONITORING REQUIREMENTS PPI 001 — WWTF Effluent Permit Number: WQ0022224 Version: 1A EFFLUENT CHARACTERISTICS EFFLUENT LIMITS MONITORINC REQUIREMENTS Parameter Description - PCS Code Monthly Average' Weekly Average Daily Maximum` Measurement Frequency Sample Type Nitrogen, Nitrate Total (as N) - 00620 2 X month Composite BOD, 5-Day (20 Deg. C) - 003I0 10 mg/l 15. mg/l 2 X month Composite Solids, Total Suspended - 00530 5 mg/l 10. mg/l 2 X month Composite Nitrogen, Ammonia Total (as N) - 00610 4 mg/l 6. mg/l 2 X month Composite Carbon, Tot Organic (TOC) - 00680 3 X years Grab pH - 00400 6.0 - 9.Oe su 9 su 5 X week Grab Chloride (as Cl) - 00940 3 X year" Grab Solids, Total Dissolved - 70295 3 X years Grab Chlorine, Total Residual - 50060 5 X week Grab Coliform, Fecal MF, M-FC Broth,44.5C - 31616 14' #I100ml 25_ #/100m1 2 X month Grab Flow, in conduit or thru treatment plant - 50050 237,840 gpd Continuous Recorder Turbidity, HCH Turbidimiter - 00076 10. ntu Continuous Recorder Monthly averages for all but fecal coliform shall be the arithmetic mean of all samples collected during the reporting period. b Monthly average for fecal coliform shall be the geometric mean of all samples collected during the reporting period. `Daily maximum shall be the maximum value of all samples collected during the reporting period. d3 X year sampling shall be conducted during March, July and November. eThe effluent pH shall not be less than 6.0 standard units nor greater than 9.0 standard units. WQ0022224 Version 1.1 Attachment A Page I of THIS PAGE BLANK WQ0022�- . Version 1.1 Attachment A ?age 2 of