HomeMy WebLinkAboutWQ0020814_Final Permit_20020511SOF W A��9Q Michael F. Easley, Governor
pWilliam G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
p Gregory J. Thorpe, Ph.D., Acting Director
Division of Water Quality
May 11, 2002
PATRICK O'NEAL
CHATHAM DEVELOPMENT CORPORATION
211 CHANCELLORS RIDGE DRIVE
DURHAM, NC 27713
Subject: Permit No. WQ0020814
Hills of Rosemont — Lot 22
Wastewater Treatment & Drip Irrigation Facility
Chatham County
Dear Mr. O'Neal:
In accordance with your request received December 11, 2001 and additional information received April
18, 2002, we are forwarding herewith Permit No. WQ0020814, dated May 11, 2002, to Chatham Development
Corporation for the construction and operation of the subject single family wastewater treatment and drip
irrigation facilities.
This permit shall be effective from the date of issuance until April 30, 2007, and shall be subject to the
conditions and limitations as specified therein. Please pay particular attention to the monitoring requirements in
this permit. Failure to establish an adequate system for collecting and maintaining the required operational
information will result in future compliance problems. Upon completion of the transfer of the property to another
party, a name change request shall be submitted to the Division of Water Quality accompanied by an application
fee, documentation from the parties involved, and other supporting materials as may be appropriate.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to
request an adjudicatory hearing upon written request within thirty (30) days following receipt of this permit. This
request must be in the form of a written petition, conforming to Chapter 150B of the North Carolina General
Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-
6714. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this matter, please contact Nathaniel Thornburg at (919) 733-5083 extension 533.
Sincerer,
a! 1 1_71
Gregory J. Thorpe, Ph.D.
cc: Chatham County Health Department
Raleigh Regional Office, Water Quality Section
Jerry T. Dalton -- Dalton Engineering & Associates, PA
Technical Assistance and Certification Unit
Non -Discharge Compliance/Enforcement Unit
Water Quality Central Files
NDPU Files
Non -Discharge Permitting Unit
1617 Mail Service Center, Raleigh, NC 27699-1617
DENR Customer Service Center
An Equal opportunity Action Employer
Internet http://h2o.ear.state.nc.us/ndpu
Telephone (919) 733-5083 Fax (919)715-6M
Telephone 1 800 623-7748
50% mcycled/I0% post -consumer paper
Alhk
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
SINGLE FAMILY DRIP IRRIGATION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended,
and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Chatham Development Corporation
Chatham County
FOR THE
construction and operation of a 600 gallon per day (GPD) drip irrigation wastewater treatment and disposal
system consisting of a 1,500 gallon baffled septic tank with effluent filter, two (2) 72 square foot (ft2)
recirculating sand filters with a 4.17 gpd/ft2 surface loading rate, a 12 gallon per minute (gpm) Ultraviolet
disinfection unit (Sanitron Model S37B), a 4,000 gallon recirculation/storage/pump tank with a 24.5 gpm pump
operating at 115.5 ft of TDH, audio and visual high water alarms, rain sensor, and a 16,203 ft2 drip irrigation area
with approximately 5,401 linear feet of drip line containing 2,701 emitters to serve Hills of Rosemont — Lot 22,
with no discharge of wastes to the surface waters, pursuant to the application received December 11, 2001, and in
conformity with the project plan, specifications, and other supporting data subsequently filed and approved by the
Department of Environment and Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until April 30, 2007, and shall be subject to the
following specified conditions and limitations.-
1.
imitations:
I. PERFORMANCE STANDARDS
Upon completion of construction and prior to operation of this permitted facility, a certification must
be received from a professional engineer certifying that the permitted facility has been installed in
accordance with this permit, the approved plans and specifications, and other supporting materials. If
this project is to be completed in phases and partially certified, you shall retain the responsibility to
track further construction approved under the same permit, and shall provide a final certificate of
completion once the entire project has been com leted. Mail the Certification to the Non -Discharge
Permitting Unit, .1617 Mail Service Center, Raleigh, NC 27699-1617.
2. The Raleigh Regional Office, telephone number (919) 571-4700, shall be notified at least forty-eight
(48) hours in advance of operation of the installed facilities so that an in-place inspection can be
made. Such notification to the regional supervisor shall be made during the normal office hours from
8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State Holidays.
The drip irrigation facilities shall be effectively maintained and operated at all tinges so that there is
no discharge to the surface waters, nor any contamination of ground waters which will render them
unsatisfactory for normal use. In the event that the facilities fail to perform satisfactorily, including
the creation of nuisance conditions or failure of the irrigation area to adequately assimilate the
wastewater, the Permittee shall take immediate corrective actions including those actions that may be
required by the Division of Water Quality (Division), such as the construction of additional or
replacement wastewater treatment -and disposal facilities. -E
4. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to surface
or groundwaters resulting from the operation of this facility.
The sand media of the recirculating sand filter must comply with the Division's sand specifications.
The engineer's certification will serve as evidence that these specifications have been met.
A leakage test shall be performed on the septic tank and dosing tank to insure that any exfiltration
occurs at a rate which does not exceed twenty (20) gallons per twenty-four (24) hours per 1,000
gallons of tank capacity. The engineer's certification will serve as proof of compliance with this
condition.
If excavation into bedrock is required for the installation of the septic tank or sand filter, the pit shall
be lined with a 10 -mil synthetic liner.
A sanitary tee shall be installed on the effluent pipe of the septic tank. The engineer's certification
will serve as evidence that these specifications have been met.
The residuals generated from these treatment facilities must be disposed in accordance with General
Statute 143-215.1 and in a manner approved by the Division.
10. Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited.
11. The following buffers shall be maintained:
a) 100 feet between wetted area and any residence or places of public assembly under separate
ownership,
b) 50 feet between wetted area and property lines,
c) 100 feet between wetted area and wells,
d) 50 feet between wetted area and drainageways or surface water bodies,
e) 50 feet between wetted area and public right of ways,
f) 100 feet between treatment/storage units and any wells, and
g) 50 feet between treatment units and property lines.
2
I. OPERATION AND MAINTENANCE REQUIREMENTS
The facilities shall be properly maintained and operated at all times.
2. Upon classification of the facility by the Water Pollution Control System Operators Certification
Commission (WPCSOCC), the Permittee shall employ a certified wastewater treatment plant operator
to be in responsible charge (ORG} of the. wastewater treatment -facilities. -The operator must hold a
certificate of the type and grade at least equivalent to or greater than the classification assigned to the
wastewater treatment facilities by the WPCSOCC. The Permittee must also employ a certified back-
up operator of the appropriate type and grade to comply with the conditions of 15A NCAC 8G .0202.
The ORC of the facility must visit each Class I facility at least weekly and each Class 11, III, and IV
facility at Ieast daily, excluding weekends and holidays, and must properly manage and document
daily operation and maintenance of the facility and must comply with all other conditions of 15A
NCAC 8G .0202. Once the facility is classified, the Permittee must submit a letter to the WPCSOCC
which designates the operator in responsible charge within thirty days after the wastewater treatment
facilities are 50% complete.
3. A suitable year round vegetative cover shall be maintained.
4. Irrigation shall not be performed during inclement weather or when the ground is in a condition that
will cause runoff.
Adequate measures shall be taken to prevent wastewater runoff from the drip field.
6. The application rate shall not exceed a cumulative loading of 21.85 inches over any twelve (12)
month period at an instantaneous application rate not to exceed 0.49 inches per hour.
7. The facilities shall be effectively maintained and operated as a non -discharge system to prevent the
discharge of any wastewater resulting from the operation of this facility.
8. No type of wastewater other than that from the Hills of Rosemont — Lot 22 shall be dripped onto the
irrigation area.
9. No traffic or equipment shall be allowed on the disposal area except while installation occurs or while
normal maintenance is being performed.
10. The drip irrigation field shall be fenced with at least a two -strand wire fence.
11. The Permittee is responsible for the operation and maintenance of the entire treatment and disposal
system including, but not limited to, the following items:
a. The septic tank shall be checked annually and pumped out as needed.
b. The ultraviolet disinfection unit shall be checked every week. The lamp shall be cleaned and/or
replaced to ensure proper disinfection.
The storage, pump, and alarm systems shall be inspected monthly. The scum layer shall be
removed at the same interval as the septic tank is cleaned out.
d. The drip irrigation system shall be inspected monthly to make certain of the emitters proper
operation, that the soil is assimilating the disposed treated wastewater with no surface runoff, and
that no objectionable odors are being generated.
III. MONITORING ANDREPORTING-REQUIREMENTS
Any monitoring deemed necessary by the Division to insure surface and ground water protection will
be established and an acceptable sampling reporting schedule shall be followed.
2. The. Permittee shall maintain records of all maintenance performed on the system and irrigation area,
as required in Condition II 11 for a -minimum of five years. This information shall be provided to the
Division upon request.
3. Noncompliance Notification:
The Permittee shall report by telephone to the Raleigh Regional Office, telephone number (919) 571-
4700, as soon as possible, but in no case more than 24 hours or on the next working day following the
occurrence or first knowledge of the occurrence of any of the following:
a_ Any process unit failure, due to known or unknown reasons, that renders the facility incapable of
adequate wastewater treatment, such as mechanical or electrical failures of pumps, emitters, etc.;
or
b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to receiving
waters without treatment of all or any portion of the influent to such station or facility.
Persons reporting such occurrences by telephone shall also file a written report in letter form within
five (5) days following first knowledge of the occurrence. This report must outline the actions taken
or proposed to be taken to ensure that the problem does not recur.
IV. INSPECTIONS
Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to insure proper
operation of the subject facilities.
2. Any duly authorized officer, employee, or representative of the Division may, upon presentation of
credentials, enter and inspect any property, premises or place on or related to the disposal site or
facility at any reasonable time for the purpose of determining compliance with this permit, may
inspect or copy any records that must be maintained under the terms and conditions of this permit,
and may obtain samples of groundwater, surface water, or leachate.
V. GENERAL CONDITIONS
1. This permit shall become voidable unless the facilities are constructed in accordance with the
conditions of this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
This permit is not transferable. In the event there is a desire for the facilities to change ownership, or
there is a name change of the Permittee, a formal permit request trust be submitted to the Division
accompanied by an application fee, documentation from the parties involved, and other supporting
materials as may be appropriate_ The approval of this request will be. considered on its merits and
may or may not be approved.
4. Upon the availability of a municipal or regional sewerage collection system, the subject wastewater
treatment facilities shall be abandoned and all wastewater discharged into the municipal or regional
sewerage system.
4
5. Failure to abide by the conditions and limitations contained in this permit may subject the Permittee
to an enforcement action by the Division in accordance with North Carolina General Statute 143-
215.6A to 143-215.6C.
6. The issuance of this permit does not exempt the Permittee from complying with any and all statutes,
rules, regulations, or ordinances which may be imposed by other government agencies (local, state,
and federal) which have jurisdiction, including but not Iimited to.applicable river buffer rules in 15A
NCAC 2B.0200, erosion and sedimentation control requirements in 15A NCAC Chapter 4 and under
the Division's General Permit NCG010000, and any requirements pertaining to wetlands under 15A
NCAC 2B .0200 and 2H .0500.
7. This permit may be revoked if the Permittee fails to -abide by the conditions of the "Operation and
Maintenance Agreement" previously signed by the Permittee.
8. A set of approved plans and specifications for the subject project must be retained by the Permittee
for the life of the project.
The annual administering and compliance fee must be paid by the Permittee within 30 days after
being billed by the Division_ Failure to pay the fee accordingly may cause the Division to initiate
action to revoke this permit as specified by 15A NCAC 2H .0205 (c)(4).
10. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its extension.
Upon receipt of the request, the Commission will review the adequacy of the facilities described
therein, and if warranted, will extend the Permit for such period of time and under such conditions
and Iimitations as it may deem appropriate.
Permit issued this tke I Ph day of May, 2002.
NORTH AROLINA E rRONMENTAL MANAGEMENT COMMISSION
—/-Gregory J. Thorpe, Ph -D., Acting Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0020814
Permif No. WQ0020814
May 11, 2002
ENGINEER'S CERTIFICA'T'ION
Partial Final
1, , as a duly registered Professional Engineer in the State of North
Carolina, having been authorized to observe (periodically, weekly, full time) -the construction of the project,
Project Name
Location and County
for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the
construction such that the construction was observed to be built within substantial compliance and intent of this permit,
the approved plans and specifications, and other supporting materials.
Signature
Date
R
Registration No.
rec-,
STATE OF NORTH CAROLINA
DEPARTMENT OF NATURAL AND ECONOMIC RESOURCES
RALE10H, NORTH CAROLINA
525;S IV NW '
r'80% DUPeA M 10 M1, (SOUTHWEST687 55' 689
DURHAM) 2 030 000 FE
'7 7
3
00
B
u station
13
r
0 co
p
37MelpCb
70 --------
- 0
IIV
31
--------- �:R
...........
7
-----------
7 7-
- - ----------
hmE�F § --------
N,
m
1
v
----- - ------ 71
WWV
I a
(r
--,J, fdF
HFA�Ija
ilk
-- --- ---- -------- -----
------------
----------
---------- ------
7z
IC6,
- -----------------
------------
------------- --------
-------------- -----------
. L
Zo
Zlj u
. Q
40 0.-
OPERATIOti AND MAINTENANCE AGREEMENT
SINGLE FAMILY RESIDENCE WASTEWATER TREATMENT SYSTEM
DIVISION OF WATER QUALITY
Owner: A / N� ,� Lort a�
Address: a// C%sa�✓ cad/a�� R� da{ -D
Disposal Method: SPRAY IRRIGATION
County: ChPAP-m
Permit No. c .)1j?002091-1
DRIP IRRIGATION (Circle One)
I agree to operate and maintain the wastewater treatment system as follows:
I ) The Permittee is responsible for the operation and maintenance of the entire treatment and disposal
system. including, but not limited to, the following items:
a) The septic tank shall be checked annually and pumped out as needed. The effluent filter shall be
checked and cleaned at the same frequency of the septic tank.
b1 Check one:
[ The tablet chlorinator shall be checked every week. Tablets shall be added so as to provide
proper chlorination.
The ultraviolet disinfection unit shall be checked every week. The lamp shall be cleaned
and/or replaced to ensure proper disinfection.
c) The storage, pump, and alarm systems shall be inspected monthly. The scum laver shall be
removed at the same time interval as the septic tank is pumped out.
d 1 The irrigation system shall be inspected monthly to make certain of proper operation, that
caetative aroxti7h does not interfere with the system inspection or operation, that the soil is
assimilating the disposed treated wastewater with no surface runoff, and that no objectionable
odors are beim generated.
'_) Failure of the Permittee to properly operate this system is subject to a penalty up to 525,000 per day.
3) Failure to meet the permit conditions or violation of the State's surface or groundwater regulations
will require evacuating the dwelling and may void the permit.
I understand the above require ents and agree t terms as part of the issued pertnit.
Owner Signature: Date: / 7 1
Votan Si;nature: L4 ON, Notary Seal: K. Ho�o��
Date: Ja p f Commission Expiration: all ra
NOTARY
y PUBLIC
SFR 0&!M 04/01
013
WATER POLLUTION CONTROL SYSTEM OPERATORS
CERTIFICATION COMMISSION
CLASSIFICATION
RATING SHEET FOR WATER POLLUTION coisrrROLL-SYSTEMS
FACILITY INFORMATION:
NAME OF FACILITY: Chatham Developrnent Corp., Hills of Rosemont -Lot Z
MAILING ADDRESS: 211 Chancellors Ridge Dr., Durham, NC 27713
COUNTY: Chatham
CONTACT PERSON: Patrick O'Neal
PERMIT NO.: WQ0020814- Check One: NC
14)X41
TELEPHONE: 9191$06-3262
WQ ✓
TELEPHONE:
HEALTH DP
RATING INFORMATION: (Before completing this section, please refer to pages 2-4)
PERMITTED FLOW: &ov GPD BNR? YES NO
CHECK CLASSIFICATION: WASTEWATER: 1 2 3 4
DRIP IRRIGATION .l
PHYSICAL/CHEMICAL
COLLECTION: 1
SUBSURFACE
2 3 4
LAND APPLICATION
GRADEII
RATED BY: Randv Jones REGION. RRO DATE: 3128/02
REGIONAL OFFICE TELEPHONE NUMBER: 9191571-4700
Permit No.: WQ002081 4 -
Page 1
EXT: 249
Classification of Drip Irrigation Water Pollution Control Systems:
Systems which utilize drip irrigation for the reuse or disposal of wastewater.
These systems include: septic tanks, sand filter, oil/water separators, lagoons,
storage basins, screening, sedimentation. Systems other than those listed above
shall be subject to additional classification.
Classification of Land APPlication of Residuals Systems:
Systems permitted and dedicated for the land application of residuals that are produced by
a water pollution control system or contaminated soils.
Classification of Phvsical/Chemical Water Pollution Control Treatment Systems:
Grade I Physical/Chemical: Any water pollution control system that utilizes a primarily
physical process to treat wastewater. This classification includes groundwater remediation
systems **
Grade II Physical/Chemical: Any water pollution control system that utilizes a primarily
chemical process to treat wastewater. This classification includes reverse osmosis,
electrodialysis, and ultrafiltration systems. **
* * Any water pollution control system that utilizes a physical/chemical process to enhance an
activated sludge or fixed growth process, shall not be subject to additional classification
Classification of Subsurface Water Pollution Control Systems:
Systems which utilize the soil for subsurface treatment and disposal of wastewater
And/or are required to have a certified operator under 15A NCAC 18A.1961. ***
* ** Any subsurface system that has as part of its treatment process a water pollution control
system that may be classified under Rules .0302 through .0307 of this section shall be
subject to additional classification.
Permit No.: WQ00208
Page 3