HomeMy WebLinkAboutWQ0013749_Final Permit_19970512State of North Carolina
Department of Environment,
Health and Natural Resources
Ai
Division of Water Quality�Al
James B.Governor
B. H
Jonathan B. Howes, Secretary
A. Preston Howard, Jr., P.E., Director
May 12, 1997
Mr. Jack M. Rhodes
51 Sawmill Road
Horseshoe, NC 28742
Subject: Permit Number WQ0013749
Mountain Laurel Resort and Campground
Pump and Haul Operation
Henderson County
Dear Mr. Rhodes:„, n
In accordance with your application received April 14, 1997, aji—A
supporting materials subsequently received, we are forwarding herewith M
Permit No. WQ0013749, dated May 12, 1997, to Jack M. Rhodes for the=c r�-)3r�i
construction and operation of a pump and haul facility to serve Mou4aiH'C�
Laurel Resort and Campground. o
This permit shall be effective from the date of issuance
until November 11, 1997, and shall be subject to the conditions and
limitations as specified therein. Please pay particular attention to the
monitoring requirements in this permit. Failure to establish an adequate
system for collecting and maintaining the required operational
information will result in future compliance problems.
If any parts, requirements, or limitations contained in
this permit are unacceptable to you, you have the right to request an
adjudicatory hearing upon written request within 30 days following
receipt of this permit. The request must be in the form of a written
petition, conforming to Chapter 150B of North Carolina General Statutes,
and filed with the Office of Administrative Hearings, P. O. Box 27447,
Raleigh, N. C. 27611-7447. Unless such requests are made, this permit
shall be final and binding.
One set of approved plans and specifications is being
forwarded to you. If you need additional information concerning this
matter, please contact Paul White at 704/251-6208.
Lncerell.y,
—fXQ��
C .
A. Preston Howard, Jr., P.E.
Enclosure
xc: Henderson County ealth Department
Coleen Sullins
P.O. Box 29535, �� FAX 919-733-2496
Raleigh, North Carolina 27626-0535 NwfC An Equal Opportunity/Affirmative Action Employer
Telephone 919-733-7015 50% recycles/ 10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPAR'T'MENT OF ENVIRONMENT, HEALTH, AND NATURAL RESOURCES
RALEIGH
PUMP AND HAUL PERMIT WQ0013749
In accordance with the provisions of Article 21 of Chapter 143,
General Statutes of North Carolina as amended, and other applicable Laws,
Rules, and Regulations
PERMISSION IS HERESY GRAN'T'ED TO
Jack M. Rhodes
Henderson County
FOR THE
construction and operation of a pump and haul facility to serve Mountain
Laurel Resort and Campground with no discharge of wastes to the surface
waters, pursuant to the application received April 14, 1997, and in
conformity with the project plan, specifications, and other supporting
data subsequently filed and approved by the Department of Environment,
Health, and Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until
November 11, 1997, and shall be subject to the following specified
conditions and limitations:
1. This permit shall become voidable unless the subject pump and haul
activities are carried out in a manner which has been approved by
this Division.
2. This permit is effective only with respect to the nature and volume
of wastes described in the application and other supporting data.
3. The facility shall be properly maintained and operated at all times.
4. This permit is not transferable. If -the facilities change
ownership, or if there is a name change of the Permittee, a formal
permit request must be submitted to the Division of Water Quality
accompanied by an application fee, documentation from the parties
involved, and other supporting materials as may be appropriate. The
approval of this request will be considered on its merits and may or
may not be approved.
5. No type of wastewater other than that from Mountain Laurel Resort
and Campground shall be included in the pump and haul activities.
6. The permit shall become voidable unless the agreement between Jack
M. Rhodes, AAA Septic Tank Service, and the City of Brevard for the
collection, transportation, and ultimate disposal of the wastewater
is in full force and effect.
7. If the facilities fail to perform satisfactorily, including the
creation of nuisance conditions, the Permittee shall cease operation
of all pump and haul activities and take such immediate corrective
action as may be required by this Division.
8. This pump and haul permit shall not be renewed.
9. The sewage and wastewater collected by this system shall be treated
in the City of Brevard Wastewater Treatment Facility prior to being
discharged into the receiving stream.
10. The Asheville Regional Office, telephone number 704/251-6208, shall
be notified at least forty-eight (48) hours in advance of operation
of the pump and haul activities so that an in-place inspection can
be made. Such notification to the regional supervisor shall be made
during the normal office hours from 8:00 a.m. until 5:00 p.m. on
Monday through Friday, excluding State Holidays.
11. The Permittee is liable for any damages caused by a spill or failure
of the pump and haul operations.
12. Adequate inspection, maintenance, and cleaning shall be provided by
the Permittee to insure proper operation of the subject facilities.
13. The Permittee or his designee shall inspect the wastewater
collection facilities to prevent malfunctions and deterioration,
operator errors and discharges which may cause or lead to the
release of wastes to the environment, a threat to human health, or a
nuisance. The Permittee shall keep an inspection log or summary
including at least the date and time of inspection, observations
made, and any maintenance, repairs, or corrective actions taken by
the Permittee. This log of inspections shall be maintained by the
Permittee for as long as the pump and haul activities are being
conducted and shall be made available upon request to the Division
of Water Quality or other permitting authority.
14. Any duly authorized officer, employee, or representative of the
Division of Water Quality may, upon presentation of credentials,
enter and inspect any property, premises or place on or related to
the wastewater collection facilities at any reasonable time for the
purpose of determining compliance with this permit; may inspect or
copy any records that must be kept under the terms and conditions of
this permit; and may obtain samples.
15. An accurate record of the monthly pump and haul activities must be
maintained by the Permittee, indicating:
a) date wastewater is removed from the facility,
b) name of facility from which wastewater is removed,
c) name of facility receiving wastewater,
d) volume of wastewater removed, and
e) status of permanent disposal option.
These records shall be submitted to the Asheville Regional Office on
or before the fifteenth (15) day of the following month.
16. Failure to abide by the conditions and limitations contained in this
permit may subject the Permittee to an enforcement action by the
Division of Water Quality in accordance with North Carolina General
Statute 143-215.6.
17. The issuance of this permit does not preclude the Permittee from
complying with any and all statutes, rules, regulations, or
ordinances which may be imposed by other government agencies (local,
state and federal) which have jurisdiction.
18. The Permittee shall provide for the installation and maintenance of
an audible and visual high water alarm.
19.- A leakage test shall be performed on the septic tank and other tanks
to insure that any exfiltration occurs at a rate which does not
exceed twenty (20) gallons per twenty-four (24) hour per 1,000
gallons of tank capacity. The engineer's certification will serve
as proof of compliance with this condition.
20. A copy of the approved plans and specifications shall be maintained
on file by the Permittee for the life of the project.
21. Non -Compliance Notification:
The Permittee shall report by telephone to the Asheville Regional
Office, at telephone number 704/251-6208, as soon as possible, but
in no case more than 24 hours or on the next working day following
the occurrence or first knowledge of the occurrence of any of the
following:
a. Any process unit failure, due to known or unknown reasons, that
render the facility incapable of adequate wastewater treatment
such as mechanical or electrical failure of pumps. aerators,
compressors, etc.
b. Any failure of a pumping station, sewer line, etc. resulting in
a by-pass directly to receiving waters without treatment of all
or any portion of the influent to such station or facility.
Persons reporting such occurrences by telephone shall also file a
written report in letter form within 15 days following first
knowledge of the occurrence. This report must outline the actions
taken or proposed to be taken to ensure that the problem does not
recur.
22. Upon completion of construction and prior to operation of the pump
and haul activities, certification must be received from a
professional engineer certifying that the permitted facilities have
been installed in accordance with this permit, the approved plans
and specifications. Mail the certification to the Permits and
Engineering Unit, Post Office Box 29535, Raleigh, NC 27626-0535.
23. The annual administering and compliance fee must be paid by the
Permittee within thirty (30) days after being billed by the
Division. Failure to pay the.fee accordingly may cause the Division
to initiate action to revoke this permit as s ecified b 15 NCAC
2H.0205 (c) (4) . Permit issued this the /,-),t1--- day of , 1997.
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
A. Preston Howard, Jr., P.E.
Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0013749
, 1997
Engineer's Certification
I,
as a duly registered
Professional Engineer in the State of North Carolina, having been
authorized to observe (periodically/weekly/full time) the construction
of the project,
for
(Project) (Name of Location)
the Permittee hereby state that, to the best of my abilities, due
care and diligence was used in the observation of the construction
such that the construction was observed to be built within substantial
compliance and intent of the approved plans and specifications.
Signature
Date
Registration No.
NUTEL;;
1. The A4 -1-1N4 alarm requires 1, 115 volt, 15 amp circuit at tank.
2. The alarm is to be mounted 2 feet above ground level on steel
angle brackets attached to the riser and the alarm.
3. The float is set in the tank to signal at 18 inches below the top
of the tanks. A PVC gray conduit 1" diameter is used to access from
the inside of the riser to the alarm (the float wire is threaded
through the conduit and sealed at both ends with silicone rubber or
other approved sealer.
n P
A2-3
Specifications `qw'
■ Unit rating: 10 amps at 120
or 240 Vac. 15 foot SJO
neoprene cord 13 amps
maximum. .
Rr�-ss
L= �l �-
A2-3
Features
B Mercury switch
permanently sealed in
polyurethane resin.
■ Adjustable weight position.
■ Normally open design
mercury fluid contacts.
■ Can be used in liquid up to A4 -1N4
140°F (60°C), i
—/`'v' - " Zp , E - �vU - ST'UZ V, =yrs~ --��.J _ �4/>
� 2-3
%Dodgy GdULb /�
T -r- "IL
j fro 0 rev+ • r9-ti.47L. R-"' -_ �
rim �•s
HIGH LIQUID LEVEL ALARM PANELS
t4-9) o o—,o 7-4-x IC
J34ra 04Z L
A4-1, A4 -1N4 provides
warning of high liquid level
di
conditions:
1. Hach tank -to have its' own
I
■ V, single phase, 60 Hz.
riser. The' pump and haul is
■Available i NEMA
in (A4-1}
n 1
from the last tank. The alarm
and NEMA 4 (A4-1 ).
i is set on the middle tank. Do
:alarm
■ Includes: alarm bell or
bund
,not pump from tank with the
(NEred
buzzer(NEhtorredflashing
alarm unless necessary. The
indicator li
Circuit could be damaged during
light (NEMA 4X), power on
pumping.
light, off-onlreset switch,
:2. The alarm and float are
terminal block for wiring
available from Gould. Local
connections.
source is Louis Williams,
■ UL and CSA listed.
Henderso l le, N, C.
�_0A
■ Does not control pump
�.�''CAR�f'''�,
operation.
_,� ;.� OQ.,...... .,.•Li '•,:
m Alarm bell and red indicator
o Cy•.,�
light will stay on until reset.
: QQ' ��•
r SEAT. i
■ Requires additional liquid
= G7 : 5543 Ito
levef switch, one A2-3 or A2-7.
% r" ,: -. �,
m Operates even if pump
•�'� rNtr `
�''�' •
circuit fails (when properly
��•`�
installed on separate branch
circuit).
Sr�r l�--f-c�S '^ � � �D1�,rG Ti�>Y�S `�� � r`'-'�•*��-r �2t vC�r�
1. 2 sres,cr r!�rdl� Yk�n r �-.�e.ti., A/vL,o,,V � 5
- ��� E Si'�vr�!-� � T�rY.0 o�4 D i / ��ir,.r /2�v�•c,•c
�� lit ✓�� - t
i
Sc
SO
13
. . �•r��....�=ma=y.. ,
i
ca Roy
.2• � 'FESS/�' � 9 'r . _.. -- - -- �•/�+ .. .� 1
iQ. SEAL
6548
ILANp�,•'
"Ali
r 1
�- rr._� � mow...._. w�._'iY�+� �. ~-�rl� yy•� • � ' ��, `
c2,7 ficoc