HomeMy WebLinkAboutWQ0010062_Final Permit_20041026October 26, 2004
VERNON P. DAVIS
127 BIRNAMWOOD DRIVE
CHAPEL HILL, NORTH CAROLINA 27516
Dear Mr- Davis:
Michael F. Easley, Governor
William G. Russ Jr., Secretary
North Carolina Department of Environment and Natural Resources
Alan W. Klimek, P.E. Director
Division of Water Quality
Subject: Permit No. WQ0010062
Davis Subdivision — Lot 6
Single Family Residence
Surface Irrigation Facility
Chatham County
In accordance with your renewal request received December 8, 2004, we are forwarding herewith
Permit No. WQ0010062, dated October 26, 2004, to Vernon P. Davis for the construction and operation
of the subject single family wastewater treatment and surface irrigation facilities.
This permit shall be effective from the date of issuance until September 30, 2009, shall void
Permit No. WQ0010062 issued January 27, 1995, and shall be subject to the conditions and limitations as
specified therein. Please pay particular attention to the monitoring requirements in this permit. Failure to
establish an adequate system for collecting and maintaining the required operational information will
result in future compliance problems.
At least six (6) months prior to the expiration of this permit, an extension shall be requested.
Upon receipt of the request, the Commission will review the adequacy of the facility described therein,
and if warranted, will extend the permit for such period of time and under such conditions and limitations,
as it may deem appropriate.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of
this permit. This request must be in the form of a written petition, conforming to Chapter 150B of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service
Center, Raleigh, NC 27699-6714. Unless such demands are made this permit shall be final and binding -
If you need additional information concerning this matter, please contact Nathaniel Thornburg at
(919) 715 -6160 -
Sincerely,
lam.
115�f
/Alan W. Klimek, P. E.
cc: Chatham County Health Department
Raleigh Regional Office - Aquifer Protection Section
Technical Assistance and Certification Unit
APS Central Files (WQ0010062)
LAU Files One
No thCarolina
Ivaturalllf
Aquifer Protection Section 1636 Mail Service Center Raleigh, NC 27699-1636 Phone (919) 733-3221 Customer Service
Internet: httpalh2o.enr.state.nc.us 2728 Capital Boulevard Raleigh, NC 27604 Pax (919) 715-0588 1-877-623-6748
Fax (919)715-6048
An Equal OpportunitylAffirmative Adson Employer — 50% Recycled110% Post Consumer Paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
SINGLE FAMILY RESIDENCE SURFACE IRRIGATION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Vernon P. Davis
Chatham County
FOR THE
construction and operation of a 360 gallon per day (GPD) surface irrigation wastewater treatment and
disposal system consisting of a 1,000 gallon baffled septic tank, a 360 square foot (ftz) subsurface sand
filter, a tablet chlorinator, two (2) 1,200 gallon interconnected storage/pump tanks with audible and visual
high water alarms, and a 12,700 fO spray irrigation area and all associated piping and appurtenances to
serve the Davis Subdivision — Lot 6 residence with no discharge of wastes to the surface waters, pursuant
to the application received December 8, 2004, and in conformity with the project plan, specifications, and
other supporting data subsequently filed and approved by the Department of Environment and Natural
Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until September 30, 2009, shall void
Permit No. WQ0010062 issued January 27, 1995 and shall be subject to the following specified
conditions and limitations:
I. PERFORMANCE STANDARDS
Upon completion of construction and prior to operation of this permitted facility, a certification
must be received from a professional engineer certifying that the permitted facility has been
installed in accordance with this permit, the approved plans and specifications, and other
supporting materials. If this project is to be completed in phases and partials certified, yoq
shall retain the res onsibilit to track further construction approved under the same permit, and
shall provide a final certificate of completion once the entire project has been coin leted. Mail
the Certification to the Land Application Unit, 1636 Mail Service Center, Raleigh, NC 27699-
1636.
2. The Raleigh Regional Office, telephone number (919) 571-4700, shall be notified at least forty-
eight (48) hours in advance of operation of the installed facilities so that an in-place inspection
can be made. Such notification to the regional supervisor shall be made during the normal
office hours from 5:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State
Holidays.
3. The surface irrigation facilities shall be effectively maintained and operated at all times so that
there is no discharge to surface waters, nor any contamination of ground waters, which will
render them unsatisfactory for normal use. In the event that the facilities fail to perform
satisfactorily, including the creation of nuisance conditions or failure of the irrigation area to
adequately assimilate the wastewater, the Permittee shall take immediate corrective actions
including those actions that may be required by the Division of Water Quality, such as the
construction of additional or replacement wastewater treatment and disposal facilities.
4. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to
surface or ground waters resulting from the operation of this facility.
The sand media of the subsurface sand filter must comply with the Division's sand
specifications. The Engineer's Certification will serve as evidence that these specifications have
been met.
G. A leakage test shall be performed on the septic tank and storage/pump tank(s) to insure that any
exfiltration occurs at a rate, which does not exceed twenty (20) gallons per twenty-four (24)
hours per 1,000 gallons of tank capacity. The Engineer's Certification will serve as proof of
compliance with this condition.
7. If excavation into bedrock is required for the installation of the septic tank or sand filter, the pit
shall be lined with a 10-miI synthetic liner.
S. A sanitary tee and filter shall be installed on the effluent pipe of the septic tank. The Engineer's
Certification will serve as evidence that these specifications have been met.
9. The residuals generated from these treatment facilities must be disposed in accordance with
General Statute 143-215.1 and in a manner approved by the Division.
10. Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited.
11. The following buffers shall be maintained:
a. 400 feet between wetted area and any residence or places of public assembly under separate
ownership,
b. 150 feet between wetted area and property lines* ,
c. 100 feet between wetted area and wells,
d. 100 feet between wetted area and drainage ways or surface water bodies,
e. 50 feet between wetted area and public right of ways,
f. 100 feet between treatinent/storage units and any wells, and
g. 50 feet between treatment units and property lines.
* A 50 foot buffer to the common property line with the single family spray irrigation field
located at Davis Subdivision, Lot 14A will be allowed. This variance shall be recorded in
the Chatham County Register of deeds, shall be signed by all parties involved and
notarized.
Some of the buffers specified above may not have been included in previous permits for this
waste treatment and disposal system. These buffers are not intended to prohibit or prevent
modifications, which are required by the Division, to improve performance of the existing
treatment facility. These buffers do, however, apply to modifications of the treatment and
disposal facilities that are for the purpose of increasing the flow that is tributary to the facility.
These buffers do apply to any expansion or modification of the surface irrigation areas and
apply in instances in which the sale of property would cause any of the buffers now complied
with, for the treatment and disposal facilities, to be violated. The applicant is advised that any
modifications to the existing facilities will require a permit modification.
12. The pump tank(s) shall have functional audible and visual high water alarms that are external to
any structure.
2
13. The disposal system shall be connected to a rain or moisture sensor that shall indicate when
wastewater application is not appropriate in accordance with Condition 11(4).
II. OPERATION AND MAINTENANCE REQUIREMENTS
1. The facilities shall be properly maintained and operated at all times.
2. Upon classification of the wastewater treatment and surface irrigation facilities by the Water
Pollution Control System Operators Certification Commission (WPCSOCC), the Permittee
shall designate and employ a certified operator to be in responsible charge (ORC) and one or
more certified operator(s) to be back-up ORC(s) of the facilities in accordance with 15A NCAC
8G .0201. The ORC shall visit the facilities in accordance with 15A NCAC 8G.0204 or as
specified in this permit and shall comply with all other conditions specified in these rules.
3. A suitable year round vegetative cover shall be maintained.
4. hTigation shall not be performed during inclement weather or when the ground is in a condition
that will cause runoff.
5. Adequate measures shall be taken to prevent wastewater runoff from the irrigation field.
6. The application rate shall not exceed a cumulative loading of 21.34 inches over any twelve (12)
month period at an instantaneous application rate not to exceed 0.15 inches per hour.
7. The facilities shall be effectively maintained and operated as a non -discharge system to prevent
the discharge of any wastewater resulting from the operation of this facility.
8. No type of wastewater other than that from the Davis Subdivision — Lot 6 residence shall be
sprayed onto the irrigation area.
9. No traffic or equipment shall be allowed on the disposal area except while installation occurs or
while normal maintenance is being performed.
10. The irrigation field shall be fenced with at least a two -strand wire fence.
It. Wastewater treatment units open to the atmosphere shall have restricted access and pump
control panels shall be locked.
12. The Permittee is responsible for the operation and maintenance of the entire treatment and
disposal system including, but not limited to, the following items:
a. The septic tank shall be checked annually and pumped out as needed. The septic tank
effluent filter shall be checked and cleaned at the same frequency of the septic tank.
b. The tablet chlorinator shall be checked every week. Tablets shall be added to provide
proper chlorination.
c. The storage, pump, and alarm systems shall be inspected monthly. The scum layer shall be
removed at the same interval as the septic tank is cleaned out.
d. The system shall be inspected monthly to make certain of the proper operation of the spray
heads, that the vegetative growth allows a proper spray pattern, that the soil is assimilating
the disposed treated wastewater with no surface runoff, and that no objectionable odors are
being generated.
3
III. MONITORING AND REPORTING REQUIREMENTS
Any monitoring deemed necessary by the Division to insure surface and ground water
protection will be established and an acceptable sampling reporting schedule shall be followed.
2. The Permittee shall maintain records of all maintenance performed on the system and irrigation
area, as required in Condition 11(12) for a minimum of five years. This information shall be
provided to the Division upon request.
3. Noncompliance Notification:
The Permittee shall report by telephone to the Raleigh Regional Office, telephone, number (919)
571-4700, as soon as possible, but in no case more than 24 hours or on the next working day
following the occurrence or first knowledge of the occurrence of any of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility
incapable of adequate wastewater treatment, such as mechanical or electrical failures of
pumps, spray heads, etc.; or
b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to
receiving waters without treatment of all or any portion of the influent to such station or
facility.
Occurrences outside normal business hours may also be reported to the Division's Emergency
Response personnel at telephone number (800) 858-0368 or (919) 733-3300. Persons reporting
such occurrences by telephone shall also file a written report in letterform within five (5) days
following first knowledge of the occurrence. This report must outline the actions taken or
proposed to be taken to ensure that the problem does not recur.
IV. INSPECTIONS
1. Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to insure
proper operation of the subject facilities.
2. Any duty authorized officer, employee, or representative of the Division may, upon
presentation of credentials, enter and inspect any property, premises or place on or related to
the disposal site or facility at any reasonable time for the purpose of determining compliance
with this permit, may inspect or copy any records that must be maintained under the terms and
conditions of this permit, and may obtain samples of groundwater, surface water, or leachate.
V. GENERAL CONDITIONS
1. This permit shall become void unless the facilities are constructed in accordance with the
conditions of this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
3. This permit is not transferable. In the event there is a desire for the facilities to change
ownership, or there is a name change of the Permittee, a formal permit request must be
submitted to the Division accompanied by documentation from the parties involved, and other
supporting materials as may be appropriate. The approval of this request will be considered on
its merits and may or may not be approved.
F91
4. Upon the availability of a municipal or regional sewerage collection system, the subject
wastewater treatment facilities shall be abandoned and all wastewater discharged into the
municipal or regional sewerage system.
5. Failure to abide by the conditions and Iimitations contained in this permit may subject the
Permittee to an enforcement action by the Division in accordance with North Carolina General
Statute 143-215.6A to 143-215.6C.
6. The issuance of this permit does not preclude the Permittee from complying with any and all
statutes, rules, regulations, or ordinances, which may be imposed by other government agencies
(local, state, and federal), which have jurisdiction.
7. This permit may be revoked if the Permittee fails to abide by the conditions of the "Operation
and Maintenance Agreement" previously signed by the Permittee.
8. The Permittee shall retain a set of approved plans and specifications of the subject facility for
the life of the project.
9. The Permittee shall pay the annual administering and compliance fee within 30 days of being
billed by the Division. Failure to pay the fee accordingly may cause the Division to initiate
action to revoke this permit as specified by 15A NCAC 2H .0205 (c)(4).
10. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its
extension. Upon receipt of the request, the Commission will review the adequacy of the
facilities described therein, and if warranted, will extend the Permit for such period of time and
under such conditions and limitations, as it may deem appropriate.
Permit issued this the 26th day of October, 2004
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
-Alan W. Klimek, P.E., Director
Division of Water Quality 0
By Authority of the Environmental Management Comrrdssion
Permit Number WQ0010062
R
Permit No. WQ0010062
October 26, 2004
ENGINEER'S CERTIFICA'T'ION
Partial Final
I, , as a duly registered Professional Engineer in the State
of North Carolina, having been authorized to observe (periodically, weekly, full time) the construction of
the project,
Project Name
Location and County
for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the
observation of the construction such that the construction was observed to be built within substantial
compliance and intent of this permit, the approved plans and specifications, and other supporting
materials.
Signature
Date
Registration No.
E ANTERIOR,
JRVEY -
NH1T£ CROSS (N.C. 314 3.3 M1.
" 652 atas r
f 661 12'30 653 twhrrF cRrzOsNj
s� r
00
r + —
:�,pit
. i • � -:` % � I 500 1 I ' � I � � c r
1 / ` f \ "`[[L## III r i � ( "� � -.•� � (�`
} rO
rj�l11��,
A"k
UA
, ` r
.� j,'1 .fr ^Jt. +._ r � f�r�''f� •�G11� ''x 1 z + .,
IZ
01
� �),; 5rl� ' '.�k.^�i�� :..:. I M,, �.;�>ZI V'— �o-�� i tiAS4 ��;�� - .'• < `�L .�y F:'• -
OPERATION AND MAINTENANCE AGREEMENT
SINGLE FAMILY RESIDENCE WASTEWATER TREATMENT SYSTEM
DIVISION OF WATER QUALITY
Owner: Yelnv " A 0 •�;-
Address: f � 7_ .''r ►�%� 4.rfar �2, C i,,,r,,,� �... l
Disposal Method: l SPRAY IRRIGATION DRIP IRRIGATION (Circle One)
County:
Permit No. ec I U 6 6Z
ell
F41
4•,
I agree to operate and maintain the wastewater treatment system as follows: ,ij 's �
1) The Permittee is responsible for the operation and maintenance of the entire treatment and gSal
system including, but not limited to, the following items:,
a) The septic tank shall be checked annually and pumped out as needed. The effluent filter shall be
checked and cleaned at the same frequency of the septic tank.
b) [Open access sand filters only] The sand filter surface shall be raked and leveled every six (G)
months and any vegetative growth shall be removed by hand.
c) Check one:
The tablet chlorinator shall be checked every week. Tablets shall be added so as to provide
proper chlorination.
❑ The ultraviolet disinfection unit shall be checked every week. The lamp shall be cleaned
andlor replaced to ensure proper disinfection,
d) The storage, pump, and alarm systems shall be inspected monthly. The scum layer shall be
removed at the same time interval as the septic tank is pumped out.
e) The irrigation system shall be inspected monthly to make certain of proper operation, that
vegetative growth does not interfere with the system inspection or operation, that the soil is
assimilating the disposed treated wastewater with no surface runoff, and that no objectionable
odors are being generated.
2) Failure of the Permittee to properly operate this system is subject to a penalty up to $25,000 per day.
3) Failure to meet the permit conditions or violation of the State's surface or groundwater regulations
will require evacuating the dwelling and may void the permit.
I understand the above requirements and agree to these terms as part of the issued permit.
Owner Signature: L' z Date:
Notary Signature: Ci LC n .' Notary Seal:
Date: i - b -03 Conu ission Expiration:
SFR O&M 03103