Loading...
HomeMy WebLinkAboutWQ0007581_Final Permit_19930406State of North Carolina Department of Environment, Health and Natural Resources Division of Environmental Management 512 North Salisbury Street • Raleigh, North Carolina 27604 James B. Hunt, Jr., Governor Jonathan B. Howes, Secretary April 6, 1993 Mr. Harold Wagner, Owner 8701 N.C. 157W Rougemont, North Carolina 27572 Subject: Permit No. WQ0007581 Wagner Single Family Residence Spray Irrigation Facilities Orange County Dear Mr. Wagner: In accordance with your application received February 16, 1993, we are forwarding herewith Permit No. WQ0007581, dated April 6, 1993, to Mr. Harold Wagner for the construction and operation of the subject single family residence spray irrigation wastewater treatment and disposal facilities. This permit shall be effective from the date of issuance until March 31, 1998, shall void Permit No. 16085 issued April 28, 1988 and shall be subject to the conditions and limitations as specified therein. Please pay particular attention to the monitoring requirements in this permit. Failure to establish an adequate system for collecting and maintaining the required operational information will result in future compliance problems. If any parts, requirements, or limitations contained in this permit are unacceptable to you, you have the right to request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General Statutes, and filed with the Office of Administrative Hearings, PO. Drawer 27447, Raleigh, NC 27611-7447. Unless such demands are made this permit shall be final and binding. Regional Offices Asheville Fayetteville Mooresville Raleigh Washington Wilmington Winston-Salem 704/251-6208 919/486-1541 704/663-1699 919/5714700 919/946-6481 919/395-3900 919/761-2351 Pollution Prevention Pays PO Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-7015 An Equal Opportunity Affirmative Action Employer One set of approved plans and specifications is being forwarded to you. If you need additional information concerning this matter, please contactMx, Michael D. Alien at (919) 733-5083. Sincerely, 0 A. lest Howard, Jr., P.E. Director cc: Orange County Health Department Raleigh Regional Office Facilities Assessment Unit Training and Certification Unit NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION DEPARTMENT OF ENVIRONMENT, HEALTH AND NATURAL RESOURCES RALEIGH SINGLE FAMILY SPRAY IRRIGATION PERMIT In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations PERMISSION IS HEREBY GRANTED TO Mr. Harold Wagner Orange County FOR THE construction and operation of a 480 GPD spray irrigation wastewater treatment and disposal system consisting of a 1,000 gallon septic tank, a 450 ft2 subsurface sand filter, a tablet chlorinator, two (2) 1,200 gallon storage/pump tanks with high water alarm and a 16 GPM submersible pump and a 7,854 ftz spray irrigation area to serve the Wagner Residence, with no discharge of wastes to the surface waters, pursuant to the application received February 16, 1993, and in conformity with the project plan, specifications, and other supporting data subsequently filed and approved by the Department of Environment, Health and Natural Resources and considered a part of this permit. This permit shall be effective from the date of issuance until March 31, 1998, shall void Permit No. 16085 issued April 28, 1988 and shall be subject to the following specified conditions and limitations: I. PERFORMANCE STANDARDS 1. Upon completion of construction and prior to operation of this permitted facility, a certification must be received from a professional engineer certifying that the permitted facility has been installed in accordance with this permit and the approved plans and specifications. Mail the Certification to the Permits and Engineering Unit, PO. Box 29535, Raleigh, NC 27626-0535. 2. The Raleigh Regional Office, phone no. (919) 571-4700 shall be notified at least forty- eight (48) hours in advance of operation of the installed facilities so that an in-place inspection can be made. Such notification to the regional supervisor shall be made during the normal office hours from 8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State Holidays. 3. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to surface or groundwaters resulting from the operation of this facility. 4. The spray irrigation facilities shall be effectively maintained and operated at all times so that there is no discharge to the surface waters, nor any contamination of ground waters which will render them unsatisfactory for normal use. In the event that the facilities fail to perform satisfactorily, including the creation of nuisance conditions or failure of the irrigation area to adequately absorb the wastewater, the Permittee shall take immediate corrective action to correct the problem, including those as may be required by the Division of Environmental Management. 5. The sand media of the subsurface sand filter must comply with the Division's specifications. The engineer's certification will serve as proof of compliance with this condition. 6. A leakage test shall be performed on the septic tank and dosing tank to insure that any exfiltration occurs at a rate which does not exceed twenty (20) gallons per twenty-four (24) hours per 1,000 gallons of tank capacity. The engineer's certification will serve as proof of compliance with this condition. 7. If excavation into bedrock for the septic tank or sand filter installation is required, the pit shall be lined with a 10 mil synthetic liner. 8. The sludge generated from these treatment facilities must be disposed of in accordance with General Statute 143-215.1 and in a manner approved by the North Carolina Division of Environmental Management. 9. Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited. 10. The following buffers shall be maintained: a) 400 feet between wetted area and any residence or places of public assembly under separate ownership, b) 150 feet between wetted area and property lines, C) 100 feet between wetted area and wells, d) 100 feet between wetted area and drainageways or surface water bodies, e) 50 feet between wetted area and public right of ways, f) 100 feet between treatment/storage units and any wells, g) 50 feet between treatment units and property lines. Some of the buffers specified above may not have been included in previous permits for this waste treatment and disposal system. These buffers are not intended to prohibit or prevent modifications, which are required by the Division, to improve performance of the existing treatment facility. These buffers do, however, apply to modifications of the treatment and disposal facilities which are for the purpose of increasing the flow that is tributary to the facility. These buffers do apply to any expansion or modification of the spray irrigation areas and apply in instances in which the sale of property would cause any of the buffers now complied with, for the treatment and disposal facilities, to be violated. The applicant is advised that any modifications to the existing facilities will require a permit modification. 1. The facilities shall be properly maintained and operated at all times. 2. A suitable vegetative cover shall be maintained. 3. Irrigation shall not be performed during inclement weather or when the ground is in a condition that will cause runoff. 4. Adequate measures shall be taken to prevent wastewater runoff from the spray field. 5. The yearly application rate shall not exceed 35.0 inches at an instantaneous application rate not to exceed 0.25 inches per hour. 6. The facilities shall be effectively maintained and operated as a non -discharge system to prevent the discharge of any wastewater resulting from the operation of this facility. 7. No type of wastewater other than that from Wagner Residence shall be sprayed onto the irrigation area. 8. In the event that the sprinkler heads fail to achieve the design diameter due to obstructions, the obstructions shall be removed or the sprinkler heads shall be raised and supported to such height that the design diameter is achieved. 9. No traffic or equipment shall be allowed on the disposal area except while installation occurs or while normal maintenance is being performed. 10. The Permittee is responsible for the operation and maintenance of the entire treatment and disposal system including, but not limited to, the following items: a. The septic tank shall be checked annually and pumped out as needed. b. The tablet chlorinator shall be checked every week. Tablets shall be added so as to provide proper chlorination. C. The storage, pump, and alarm systems shall be inspected weekly. The scum layer shall be removed at the same interval as the septic tank is cleaned out. d. The spray system shall be inspected weekly to make certain of the sprayers proper operation, that the vegetative growth allows proper spray pattern, that the soil is absorbing the disposed treated wastewater with no surface runoff, and that no objectionable odors are being generated. Any monitoring deemed necessary by the Division of Environmental Management to insure surface and ground water protection will be established and an acceptable sampling reporting schedule shall be followed. 2. The Permittee shall maintain records of all maintenance performed on the system and irrigation area as required in Condition II.10 for a minimum of five years. This information shall be provided to the Division of Environmental Management upon request. 3. Noncompliance Notification: The Permittee shall report by telephone to the Raleigh Regional Office, telephone no. (919) 571-4700 as soon as possible, but in no case more than 24 hours or on the next working day following the occurrence or first knowledge of the occurrence of any of the following: a. Any process unit failure, due to known or unknown reasons, that render the facility incapable of adequate wastewater treatment such as mechanical or electrical failures of pumps, spray heads, etc. b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to receiving waters without treatment of all or any portion of the influent to such station or facility. Persons reporting such occurrences by telephone shall also file a written report in letter form within 15 days following first knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to ensure that the problem does not recur. affimel"I'mColo, 1. Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to insure proper operation of the subject facilities. 2. Any duly authorized officer, employee, or representative of the Division of Environmental Management may, upon presentation of credentials, enter and inspect any property, premises or place on or related to the disposal site and facility at any reasonable time for the purpose of determining compliance with this permit; may inspect or copy any records that must be kept under the terms and conditions of this permit; or may obtain samples of groundwater, surface water, or leachate. � KKWWM IKKOW I.T. 1. This permit shall become voidable unless the facilities are constructed in accordance with the conditions of this permit, the approved plans, specifications, and other supporting data. 2. This permit is effective only with respect to the nature and volume of wastes described in the application and other supporting data. 3. This permit is not transferable. In the event there is a desire for the facilities to change ownership, or there is a name change of the Permittee, a formal permit request must be submitted to the Division of Environmental Management accompanied by an application fee, documentation from the parties involved, and other supporting materials as may be appropriate. The approval of this request will be considered on its merits and may or may not be approved. 4. Upon the availability of a municipal or regional sewerage collection system, the subject wastewater treatment facilities shall be abandoned and all wastewater discharged into the municipal or regional sewerage system. 5. The spray irrigation field shall be fenced with at least a two strand wire fence. b. Failure to abide by the conditions and limitations contained in this permit may subject the Permittee to an enforcement action by the Division of Environmental Management in accordance with North Carolina General Statute 143-215.6A to 143-215.6C. 7. The issuance of this permit does not preclude the Permittee from complying with any and all statutes, rules, regulations, or ordinances which may be imposed by other government agencies (local, state, and federal) which have jurisdiction. 8. This permit may be revoked if the Permittee fails to abide by the conditions of the operation and maintenance agreement previously signed by the Permittee. 9. A set of approved plans and specifications for the subject project must be retained by the Permittee for the life of the project. 10. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its extension. Upon receipt of the request, the Commission will review the adequacy of the facilities described therein, and if warranted, will extend the Permit for such period of time and under such conditions and limitations as it may deem appropriate. 11. The proposed red tip photenia buffer and the existing tree line, as described on the approved plans, shall be maintained for the protection of adjacent property. In the event that the buffer fails to perform satisfactorily, including the prevention of nuisance conditions, the Permittee shall take such immediate corrective action as may be required by this Division, including the installation of additional buffers. Permit issued this the 6th day of April, 1993 NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION q-rc CJAll A. Preston oward, Jr., P. ., Director Division of Environmental Management By Authority of the Environmental Management Commission Pezmit Number WQ0007581 Permit No. WQ0007581 April b, 1993 Engineer's Certification 1, , as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe (periodically, weekly, full time) the construction of the project, Project Name Location for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance and intent of the approved plans and specifications. Signature Date Registration No. OPERATION AND MAINTENANCE AGREEMENT FOR THE DIVISION OF ENVIRONMENTAL MANAGEMENT Permit No. 16085 April 28, 1988 Mr. Harold Wagner Wagner Residence Wastewater Treatment System Final Disposal by Spray Irrigation Orange County rY . MAY 26 Jon 3 I, Harold Wagner, agree to operate and maintain the wastewater treatment system as follows: 1. The Permittee is responsible for the operation and maintenance of the entire treatment and disposal system, including but not limited to, the following items: a. The septic tank shall be checked every six (6) months and pumped out as required, but no less frequently than once per year. b. The tablet chlorinator shall be checked every week until the actual usage rate is established and thence on a monthly basis. Tablets shall be added so as to provide proper chlorination. C. The storage and pump system shall be inspected monthly. The scum layer shall be removed at the same interval as the septic tank is cleaned out. The alarm system shall be checked. The pump operation shall be checked. d. The spray system shall be inspected monthly to make certain of the sprayers' proper operation, that the vegetative growth allows proper spray patterns, that the soil is absorbing the disposed treated wastewater with no surface runoff, and that no objectionable odors are being generated. 2. Failuze of the Permittee to prcperly cpexatc this system is subject to a -penalty up to $10,000 per day. 3. Failing to meet permit cor_dit.inns or by violation of the Stare's surface or groundwater regulations will require cessation of oct.lipaucy of the residence. I understand that failure to comply with these conditions along with the permit conditions may result in voiding the permit. Mr. Harold Wagner '4Seg nd Signature /. l Y y .; IrYn�� State of North Carolina Department of Environment, Health and Natural Resources Division of Environmental Management 512 North Salisbury Street • Raleigh, North Carolina 27611 James B. Hunt, Jr., Governor A. Preston Howard, Jr., P.E. Jonathan B. Howes, Secretary Director MEMORANDUM To: Training and Certification From: Michael D. Allen, State Engineering Review Group Subject: Rating Sheet for Permit Number iniQOd07581 Date: Q 5-173 The subject permit is a renewal of Permit No. I (00135 , issued 4 - 28 - es therefore, a new rating sheet is not required. The existing rating is unchanged. Regional Offices Asheville Fayetteville Mooresville Raleigh Washington Wilmington Winston-Salem 7041251-6208 919/486-1541 704/663-1699 919/571-4700 919/946-6481 919/395-3900 919/896-7007 Pollution Prevention Pays P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-7015 An Equal Opportunity Affirmative Action Employer