HomeMy WebLinkAboutWQ0007144_Final Permit_20160419Water Resources
ENVIRONMENTAL QUALITY
PAT MCCRORY
Gowcrnor
DONALD R. VAN DER VAART
Secretary
S. JAY ZIMMERMAN
Director
April 19, 2016
MIKE ASKEW — DIRECTOR OF FACILITIES
THE YOUNG MEN'S CHRIsTIAN ASSOCIATION OF THE TRIANGLE AREA, INC.
801 CORPORATE CENTER— SUITE 200
RALEIGH, NORTH CAROLINA 27607
Dear Mr. Askew:
Subject: Permit No. WQ0007144
Camp Seafarer WWTF
Wastewater Irrigation System
Pamlico County
In accordance with your permit renewal request received January 20, 2016, we are forwarding
herewith Permit No. WQ0007144 dated April 19, 2016, to The Young Men's Christian Association of the
Triangle Area, Inc. for the continued operation of the subject wastewater treatment and irrigation facilities.
Please note that this renewed permit shall become effective on July 1, 2016 (i.e. the day after the expiration
date of the existing permit).
Please note the Permittee has been changed from The Capital Area YMCA to The Young Men's
Christian Association of the Triangle Area, Inc.
This permit shall be effective from July 1, 2016 until June 30, 2021, shall void Permit No.
WQ0007143 issued July 27, 2007, and shall be subject to the conditions and limitations as specified therein.
Please pay particular attention to the monitoring requirements listed in Attachments A, B and C for they
may differ from the previous permit issuance. Failure to establish an adequate system for collecting and
maintaining the required operational information shall result in future compliance problems.
Please note the following permit conditions have been removed since the last permit issuance
dated July 27, 2007:
➢ Old Condition I.2. — This condition has been removed as it is not a requirement of this facility.
➢ Old Condition IV.8. — This condition has been removed because the wells have been
constructed.
Please note the following permit conditions are new since the last permit issuance dated July
27, 2007:
➢ Condition II.11. — This condition requires that any Iandowner who owns land within the
compliance boundary that is not the Permittee record an easement in the County Register of
Deeds.
➢ Condition VI.8. — States the Division Director's authority to unilaterally modify or revoke a
permit should circumstances warrant such action.
State of North Carolina I Environmental Quality I Water Resources I Water Quality Permitting I Non -Discharge Permitting
1617 Mail Service Center j Raleigh, North Carolina 27699-1617
919 807 6464
Mr. Mike Askew
April 19, 2016
Page 2 of 2
➢ Condition VI.9. -- States the limitations placed on the Permittee with respect to facility
expansion along with the authority granted to the Division Director relative to expansion.
If any parts, requirements or limitations contained in this permit are unacceptable, the Permittee
has the right to request an adjudicatory hearing upon written request within 30 days following receipt of
this permit. This request shall be in the form of a written petition, conforming to Chapter 150B of the North
Carolina General Statutes, and filed with the Office of Administrative Hearings at 6714 Mail Service
Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and binding.
If you need additional information concerning this permit, please contact David Schlobohm at (919)
807-6384 or david.schlobohnigncdenngov.
Sincerely,
S. Jay Zimmerman, P.G., Directo
Division of Water Resources
cc: Pamlico County Health Department (Electronic Copy)
Washington Regional Office, Water Quality Regional Operations Section (Electronic Copy)
Digital Permit Archive (Electronic Copy)
Central Files
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENTAL QUALITY
RALEIGH
WASTEWATER IRRIGATION SYSTEM PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules and Regulations
PERMISSION IS HEREBY GRANTED TO
The Young Men's Christian Association of the
Triangle Area, Inc®
Pamlico County
FOR THE
continued operation of a 55,000 gallon per day (GPD) wastewater treatment and irrigation facility
consisting of:
approximately 6,000 linear feet (LF) of wastewater collection system; a sewer lift station; a 2.5 acre and a
2.25 acre stabilization/holding lagoon with a total capacity of 11.498 million gallons (MG); a removable
bar screen; a baffled chlorine contact tank with liquid chlorine mixing and pumping facilities including a
chlorine diffuser; a 234 gallon per minute (GPM) pump station with dual pumps; approximately 1,713 LF
of 8-inch below ground force main, with above ground force main consisting of approximately 362 LF of
8-inch, approximately 325 LF of 6-inch, approximately 125 LF of 4-inch, approximately 62 LF of 3-inch
and approximately 100 LF of 2-inch (all above ground force main having self -draining pipe gaskets); three
spray irrigation fields with Field 2 (5.8 wetted acres / 14.1 gross acres) and Field 3 (6.4 wetted acres 18.7
gross acres) as the primary fields and Field 1 (5.8 wetted acres / 19.8 gross acres) as secondary stand-by
field; and all associated piping, valves, controls and appurtenances
to serve Camp Seafarer, with no discharge of wastes to surface waters, pursuant to the application received
January 20, 2016, and in conformity with the project plans, specifications, and other supporting data
subsequently filed and approved by the Department of Environmental Quality and considered a part of this
permit.
This permit shall be effective from July 1, 2016 until June 30, 2021, shall void Permit No. WQ0007144
issued July 27, 2007, and shall be subject to the following specified conditions and limitations:
WQ0007144 Version 4.0 Shell Version 151201 Page 1 of 9
1. SCHEDULES
1. The Washington Regional Office, telephone number (252) 946-6481, shall be notified at least 48 hours
in advance (excluding weekends and holidays) of operation of the 5.8 acre secondary irrigation field
(i.e., Field 1) such that an in -place inspection can be made. Notification to the regional supervisor shall
be made from 8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State Holidays. [15A
NCAC 02T .0108(b)(2)]
2. The 5.8 acre secondary irrigation field (i.e., Field 1) shall be fenced prior to becoming operational.
[ 15A NCAC 02T .0108(b)(2)]
No later than six months prior to the expiration of this permit, the Permittee shall request renewal of
this permit on official .Division forms. Upon receipt of the request, the Division will review the
adequacy of the facilities described therein, and if warranted, will renew the permit for such period of
time and under such conditions and limitations as it may deem appropriate. Please note Rule 15A
NCAC 02T .0105(d) requires an updated site map to be submitted with the permit renewal application.
[15A NCAC 02T .0105(d), 02T .0106, 02T .0109, 02T .0115(c)]
ii. PERFORMANCE STANDARDS
The subject non -discharge facilities shall be effectively maintained and operated at all titres so there is
no discharge to surface waters, nor any contravention of groundwater or surface water standards. In
the event the facilities fail to perform satisfactorily, including the creation of nuisance conditions due
to improper operation and maintenance, or failure of the irrigation areas to adequately assimilate the
effluent, the Permittee shall take immediate corrective actions including Division required actions, such
as the construction of additional or replacement wastewater treatment or irrigation facilities. [G.S. 143-
215.1, 143-213.3(a)]
2. This permit shall not relieve the Permittee of their responsibility for damages to groundwater or surface
water resulting from the operation of this facility. [ 15A NCAC 02B .0200, 02L .0100]
3. All wells constructed for purposes of groundwater monitoring shall be constructed in accordance with
15A NCAC 02C .0 10 8 (Standards of Construction for Wells Other than Water Supply), and any other
jurisdictional laws and regulations pertaining to well construction. [I5A NCAC 02C .0108]
4. The wastewater collection facilities shall be properly maintained and operated at all times. The
Permittee shall maintain compliance with an individual system -wide collection system permit for the
operation and maintenance of these facilities in accordance with 15A NCAC 02T .0400. If an
individual permit is not required, the following performance criteria shall be met:
a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to
land or surface waters, and any contravention of groundwater or surface water standards.
b. A map of the sewer system shall be developed and actively maintained
c. An operation and maintenance plan shall be developed, implemented and maintained.
d. Pump stations not connected to a telemetry system shall be inspected every day (i.e., 365 days per
year). Pump stations connected to a telemetry system shall be inspected at least once per week.
e. High -priority sewers shall be inspected at least once every six months.
f. A general observation of the entire sewer system shall be conducted at least once per year.
g. Overflows and bypasses shall be reported to the Washington Regional Office in accordance with
15A NCAC 02B .0506(a), and public notice shall be provided as required per North Carolina
General Statute §143-215.1C.
h. A grease control program shall be developed, implemented and maintained.
i. Right-of-ways and easements shall be maintained.
WQ0007144 Version 4.0 Shell Version 151201
Page 2 of 9
j. Inspection and maintenance records for Conditions IIA.a. through 11.4.i. shall be maintained for a
period of at least three years, except for Conditions 11A.b. and II.4.c., which shall be maintained
for the life of the system.
[15A NCAC 02T .0403]
5. Effluent quality shall not exceed the limitations specified in Attachment A. [15A NCAC 02T
.0108(b)(1), 02T .0505(b)]
6. Application rates, whether hydraulic, nutrient or other pollutant, shall not exceed those specified in
Attachment B. [15A NCAC 02T .0505(c), 02T .0505(n)]
This disposal system was individually permitted on or after December 30, 1983; therefore, the
compliance boundary is established at either 250 feet from the effluent disposal area, or 50 feet within
the property boundary, whichever is closest to the effluent disposal area. An exceedance of
groundwater standards at or beyond the compliance boundary is subject to remediation action according
to 15A NCAC 02L .0106(d)(2) as well as enforcement actions in accordance with North Carolina
General Statute 143-215.6A through 143-215.6C. [15A NCAC 02L .0106(d)(2), 02L .0107(b)]
8. In accordance with 15A NCAC 02L .0108, the review boundary is established midway between the
compliance boundary and the effluent disposal area. Any exceedance of groundwater standards at the
review boundary shall require action in accordance with 15A NCAC 02L .0106. [15A NCAC 02L
.0106, 02L .0108]
9. The Permittee shall apply for a permit modification to establish a new compliance boundary prior to
any sale or transfer of property affecting a compliance boundary. [15A NCAC 02L .0107(c)]
10. In accordance with 15A NCAC 02L .0107(d), no wells, excluding Division approved monitoring wells,
shall be constructed within the compliance boundary except as provided for in 15A NCAC 02L
.0107(g). [ 15A NCAC 02L .0107]
11. Except as provided for in 15A NCAC 02L .0107(g), the Permittee shall ensure any landowner who is
not the Permittee and owns land within the compliance boundary shall execute and file with the
Pamlico County Register of Deeds an easement running with the land containing the following items:
a. A notice of the permit and number or other description as allowed in 15A NCAC 02L .0107(f)(1);
b. Prohibits construction and operation of water supply wells within the compliance boundary; and
c. Reserves the right of the Permittee or the State to enter the property within the compliance boundary
for purposes related to the permit.
The Director may terminate the easement when its purpose has been fulfilled or is no longer needed.
[ 15A NCAC 02L .0107(f)]
WQ0007144 Version 4.0 Shell Version 151201 Page 3 of 9
12. The facilities permitted herein shall be constructed according to the following setbacks:
a. The setbacks for irrigation sites permitted under 15A NCAC 02H .0200 shall be as follows (all
distances in feet):
i. Any habitable residence or place of public assembly under separate ownership: 400
ii. Surface waters: 100
iii. Groundwater lowering ditches: 100
iv. Any well with exception of monitoring wells: 100
v. Any property line: 150
[ 15A NCAC 02H .0219(k)]
b. The setbacks for storage and treatment units permitted under 15A NCAC 02H .0200 shall be as
follows (all distances in feet):
i. Any well with exception of monitoring wells: 100
ii. Any property line: 50
[15A NCAC 02H .0219(k)]
III. OPERATION AND MAINTENANCE REQUIREMENTS
1. The facilities shall be properly maintained and operated at all times. The facilities shall be effectively
maintained and operated as a non -discharge system to prevent the discharge of any wastewater resulting
from the operation of this facility. The Permittee shall maintain an Operation and Maintenance Plan,
which at a minimum shall include operational functions, maintenance schedules, safety measures and
a spill response plan. [15A NCAC 02T .0507]
2. Upon the Water Pollution Control System Operators Certification Commission's (WPCSOCC)
classification of the subject non -discharge facilities, in accordance with 15A NCAC 08G .0200 the
Permittee shall designate and employ a certified operator in responsible charge (ORC) and one or more
certified operator(s) as back-up ORC(s). The ORC or their back-up shall visit the facilities in
accordance with 15A NCAC 08G .0200, and shall comply with all other conditions specified in the
previously cited rules. [ 15A NCAC 02T .0117]
3. A suitable year round vegetative cover shall be maintained at all times, such that crop health is
optimized, allows for even distribution of effluent and allows inspection of the irrigation system. [15A
NCAC 02T .0108(b)(1)]
4. Adequate measures shall be taken to prevent effluent ponding in or runoff from the irrigation sites listed
in Attachment B. [15A NCAC 02T .0108(b)(1)]
5. Irrigation shall not be performed during inclement weather or when the ground is in a condition that
will cause ponding or runoff. [15A NCAC 02T .0108(b)(1)]
6. All irrigation equipment shall be tested and calibrated at least once per permit cycle. Calibration records
shall be maintained at the facility for a period of no less than five years, and shall be made available to
the Division upon request. [15A NCAC 02T .0108(b)(1)]
7. Only effluent from Camp Seafarer WWTF shall be irrigated on the sites listed in Attachment B. [G.S.
143-215.1]
8. No automobiles or machinery shall be allowed on the irrigation sites except during equipment
installation or while maintenance is being performed. [15A NCAC 02T .0108(b)(1)]
9. Public access to the irrigation sites and wastewater treatment facilities shall be prohibited. [ 15A NCAC
02T .0505(q)]
WQ0007144 Version 4.0 Shell Version 151201 Page 4 of 9
10. The residuals generated from the wastewater treatment facilities shall be disposed or utilized in
accordance with 15A NCAC 02T .I 100. The Permittee shall maintain a residual management plan
pursuant to 15A NCAC 02T .0508 [15A NCAC 02T .0508 02T. 1100]
11. Diversion or bypassing of untreated or partially treated wastewater from the treatment facilities is
prohibited. [15ANCAC 02T .05050)]
12. Freeboard in the stabilization/holding lagoons shall not be less than two feet at any time. [I5A NCAC
02T .0505(d)]
13. Gauges to monitor waste levels in the stabilization/holding lagoons shall be provided. These gauges
shall have readily visible permanent markings, at inch or tenth of a foot increments, indicating the
following elevations: maximum liquid level at the top of the temporary liquid storage volume;
minimum liquid level at the bottom of the temporary liquid storage volume; and the lowest point on
top of the dam. [15A NCAC 02T .0108(b)(1)]
14. A protective vegetative cover shall be established and maintained on all earthen embankments (i.e.,
outside toe of embankment to maximum allowable temporary storage elevation on the inside of the
embankment), berms, pipe runs, erosion control areas, and surface water diversions. Trees, shrubs, and
other woody vegetation shall not be allowed to grow on the earthen dikes or embankments. Earthen
embankment areas shall be kept mowed or otherwise controlled and accessible. [15A NCAC 02T
.0108(b)(1)]
IV. MONITORING AND REPORTING REQUIREMENTS
1. Any Division required monitoring (including groundwater, plant tissue, soil and surface water analyses)
necessary to ensure groundwater and surface water protection shall be established, and an acceptable
sampling reporting schedule shall be followed. [15A NCAC 02T .0108(c)]
2. A Division certified laboratory shall conduct all laboratory analyses for the required effluent,
groundwater or surface water parameters. [ 15A NCAC 02H .0800]
3. Flow through the treatment facility shall be continuously monitored, and daily flow values shall be
reported on Form NDMR.
The Permittee shall install and maintain an appropriate flow measurement device to ensure the accuracy
and reliability of flow measurement consistent with accepted engineering and scientific practices.
Selected flow measurement devices shall be capable of measuring flows with a maximum deviation of
less than ten percent from true flow; accurately calibrated at a minimum of once per year; and
maintained to ensure the accuracy of measurements is consistent with the selected device's accepted
capability. The Permittee shall maintain records of flow measurement device calibration on file for a
period of at least five years. At a minimum, documentation shall include:
a. Date of flow measurement device calibration,
b. Name of person performing calibration, and
c. Percent from true flow.
[ 15A NCAC 02T A 105(k)]
4. The Permittee shall monitor the effluent from the subject facilities at the frequencies and locations for
the parameters specified in Attachment A. [15A NCAC 02T .0108(c)]
WQ0007144 Version 4,0 Shell Version 151201 Page 5 of 9
5. The Permittee shall maintain adequate records tracking the amount of effluent irrigated. At a minimum,
these records shall include the following information for each irrigation site listed in Attachment B:
a. Date of irrigation;
b. Volume of effluent irrigated;
c. Site irrigated;
d. Length of time site is irrigated;
e. Continuous weekly, monthly, and year-to-date hydraulic (inches/acre) loadings;
f. Continuous monthly and year-to-date loadings for any non -hydraulic parameter specifically
limited in Attachment B;
g. Weather conditions; and
h. Maintenance of cover crops.
[15A NCAC 02T .0I08(c)]
6. Freeboard (i.e., waste level to the lowest embankment elevation) in the stabilization/holding lagoon
shall be measured to the nearest inch or tenth of a foot, and recorded weekly. Weekly freeboard records
shall be maintained at the facility for a period of no less than five years, and shall be made available to
the Division upon request. [15A NCAC 02T .0108(c)]
7. Three copies of all monitoring data (as specified in Conditions IV.3. and IVA.) on Form NDMR for
each PPI and three copies of all operation and disposal records (as specified in Conditions IV.5, and
IV.6.) on Form NDAR-1 for every site in Attachment B shall be submitted on or before the last day of
the following month. If no activities occurred during the monitoring month, monitoring reports are still
required documenting the absence of the activity. All information shall be submitted to the following
address:
Division of Water Resources
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
[15A NCAC 02T A105(1)]
8. A record shall be maintained of all residuals removed from this facility. This record shall be maintained
at the facility for a period of no less than five years, and shall be made available to the Division upon
request. At a minimum, this record shall include:
a. Name of the residuals hauler;
b. Non -Discharge permit number authorizing the residuals disposal, or a letter from a municipality
agreeing to accept the residuals;
c. Date the residuals were hauled; and
d. Volume of residuals removed.
[15A NCAC 02T .0108(b)(1)]
9. A maintenance log shall be maintained at this facility. This log shall be maintained at the facility for a
period of no less than five years, and shall be made available to the Division upon request. At a
minimum, this log shall include:
a. Date of calibration of flow measurement device;
b. Visual observations of the plant and plant site; and
c. Record of preventative maintenance (e.g., changing of equipment, adjustments, testing, inspections
and cleanings, etc.).
[15A NCAC 02T .0108(b)(1)]
10. Monitoring wells shall be sampled at the frequencies and for the parameters specified in Attachment
C. All mapping, well construction forms, well abandonment forms and monitoring data shall refer to
the permit number and the well nomenclature as provided in Attachment C and Figures 2 and 3. [15A
NCAC 02T ,0105(m)]
WQ0007144 Version. 4.0 Shell Version 151201 Page 6 of 9
11. Two copies of the monitoring well sampling and analysis results shall be submitted on a Compliance
Monitoring Form (GW-59), along with attached copies of laboratory analyses, on or before the last
working day of the month following the sampling month. The Compliance Monitoring Form (GW-59)
shall include this permit number, the appropriate well identification number, and one GW-59a
certification form shall be submitted with each set of sampling results. All information shall be
submitted to the following address:
Division of Water Resources
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
[I 5A NCAC 02T .0105(m)]
12. An annual representative soils analysis (i.e., Standard Soil Fertility Analysis) shall be conducted on
each irrigation site listed in Attachment B. These results shall be maintained at the facility for a period
of no less than five years, and shall be made available to the Division upon request. At a minimum, the
Standard Soil Fertility Analysis shall include the following parameters:
Acidity
Exchangeable Sodium Percentage
Phosphorus
Base Saturation (by calculation)
Magnesium
Potassium
Calcium
Manganese
Sodium
Cation Exchange Capacity
Percent Humic Matter
Zinc
Copper
pH
[15A NCAC 02T .0108(c)]
13. Noncompliance Notification:
The Permittee shall report by telephone to the Washington Regional Office, telephone number (252)
946-6481, as soon as possible, but in no case more than 24 hours, or on the next working day following
the occurrence or first knowledge of the occurrence of any of the following:
a. Treatment of wastes abnormal in quantity or characteristic, including the known passage of a
hazardous substance.
b. Any process unit failure (e.g., mechanical, electrical, etc.), due to known or unknown reasons,
rendering the facility incapable of adequate wastewater treatment.
c. Any facility failure resulting in a by-pass directly to receiving surface waters.
d. Any time self -monitoring indicates the facility has gone out of compliance with its permit
limitations.
e. Ponding in or runoff from the irrigation sites.
Any emergency requiring immediate reporting (e.g., discharges to surface waters, imminent failure of
a storage structure, etc.) outside normal business hours shall be reported to the Division's Emergency
Response personnel at telephone number (800) 662-7956, (800) 858-0368, or (919) 733-3300. Persons
reporting such occurrences by telephone shall also file a written report in letter form within five days
following first knowledge of the occurrence. This report shall outline the actions taken or proposed to
betaken to ensure the problem does not recur. [15A NCAC 02T .0105(1), 02T .0108(b)(1)]
WQ0007144 Version 4.0 Shell Version 151201 Page 7 of 9
V.
1. The Permittee shall provide adequate inspection and maintenance to ensure proper operation of the
wastewater treatment and irrigation facilities. [15A NCAC 02T .0108(b)]
2. The Permittee or their designee shall inspect the wastewater treatment and irrigation facilities to prevent
malfunctions, facility deterioration and operator errors resulting in discharges, which may cause the
release of wastes to the environment, a threat to human health or a public nuisance. The Permittee shall
maintain an inspection Iog that includes, at a minimum, the date and time of inspection, observations
made, and any maintenance, repairs, or corrective actions taken. The Permittee shall maintain this
inspection log for a period of five years from the date of the inspection, and this log shall be made
available to the Division upon request. [15A NCAC 02T .0108(b)]
3. Any duly authorized Division representative may, upon presentation of credentials, enter and inspect
any property, premises or place on or related to the wastewater treatment and irrigation facilities
permitted herein at any reasonable time for the purpose of determining compliance with this permit;
may inspect or copy any records required to be maintained under the terms and conditions of this permit,
and may collect groundwater, surface water or leachate samples. [G.S. 143-21.5.3(a)(2)]
VI. GENERAL CONDITIONS
1. Failure to comply with the conditions and limitations contained herein may subject the Permittee to an
enforcement action by the Division in accordance with North Carolina General Statutes 143-215.6A to
143-215.6C. [G.S. 143-215.6A to 143-215.6C]
2. This permit shall become voidable if the permitted facilities are not constructed in accordance with the
conditions of this permit, the Division approved plans and specifications, and other supporting
documentation. [15ANCAC 02T .0110]
3. This permit is effective only with respect to the nature and volume of wastes described in the permit
application, Division approved plans and specifications, and other supporting documentation. No
variances to applicable rules governing the construction or operation of the permitted facilities are
granted, unless specifically requested and approved in this permit pursuant to 15A NCAC 02T .0105(n).
[G.S. 143-21.5.11
4. The issuance of this permit does not exempt the Permittee from complying with any and all statutes,
rules, regulations, or ordinances, which may be imposed by other jurisdictional government agencies
(e.g., local, state, and federal). Of particular concern to the Division are applicable river buffer rules in
15A NCAC 02B .0200; erosion and sedimentation control requirements in 15A NCAC Chapter 4 and
under General Permit NCG010000; any requirements pertaining to wetlands under 15A NCAC 02B
.0200 and 02H .0500; and documentation of compliance with Article 21 Part 6 of Chapter 143 of the
General Statutes. [15A NCAC 02T .0105(c)(6)]
5. In the event the permitted facilities change ownership or the Permittee changes their name, a formal
permit modification request shall be submitted to the Division. This request shall be made on official
Division forms, and shall include appropriate property ownership documentation and other supporting
documentation as necessary. The Permittee of record shall remain fully responsible for maintaining
and operating the facilities permitted herein until a permit is issued to the new owner. [ 15A NCAC
02T .0104]
6. The Permittee shall retain a set of Division approved plans and specifications for the life of the facilities
permitted herein. [15A NCAC 02T .0108(b)(1)]
7. The Permittee shall maintain this permit until all permitted facilities herein are properly closed or
permitted under another permit issued by the appropriate permitting authority. [15A NCAC 02T
.01050)]
WQ0007144 Version 4.0 Shell Version 151201 Page 8 of 9
8. This permit is subject to revocation or unilateral modification upon 60 days notice from the Division
Director, in whole or part for the requirements listed in 15A NCAC 02T .0110. [ 15A NCAC 02T .0110]
9. Unless the Division Director grants a variance, expansion of the permitted facilities contained herein
shall not be granted if the Permittee exemplifies any of the criteria in 15A NCAC 02T .0120(b). [15A
NCAC 02T .0120]
10. The Permittee shall pay the annual fee within 30 days after being billed by the Division. Failure to pay
the annual fee accordingly shall be cause for the Division to revoke this permit. [15A NCAC 02T
.0105(e)(3)]
Permit issued this the 190' day of April 2016
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
Jay Zimmerman, P.G., Director
Division of Water Resources
By Authority of the Environmental Management Commission
Permit Number WQ0007144
WQ0007144 Version 4.0 SheIl Version 151201 Page 9 of 9
THIS PAGE BLANK
ATTACHMENT A — LIMITATIONS AND MONITORING REQUIREMENTS
PPI 001 — WWTF Effluent
Permit Number: WQ0007144 Version: 4.0
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING REQUIREMENTS
PCS
Code
Parameter Description
Units of
Measure
Monthly
Average
Monthly
Geometric Mean
Daily Minimum
Daily Maximum
Measurement
Frequency
9 Y
Sample
YP
Type
00310
BOD, 5-Day (20 °C)
mg/L
4 x Year
Grab
00940
Chloride (as Cl)
mg/L
3 x Year 2
Grab
50060
Chlorine, Total Residual
mg/L
Per Event 3
Grab
31616
Coliform, Fecal MF, M-FC Broth, 44.5 °C
9/100 mL
4 x Year
Grab
50050
Flow, in Conduit or thru Treatment Plant
GPD
55,000
Continuous
Recorder
00610
Nitrogen, Ammonia Total (as N)
mg/L
4 x Year I
Grab
00625
Nitrogen, Kjeldahl, Total (as N)
mg/L
4 x Year 1
Grab
00620
Nitrogen, Nitrate Total (as N)
mg/L
4 x Year t
Grab
00600
Nitrogen, Total (as N)
mg/L
4 x Year I
Grab
00400
pH
su
Per Events
Grab
00665
Phosphorus, Total (as P)
mg/L
4 x Year I
Grab
70300
Solids, Total Dissolved — 180°C
mg/L
3 x Year 2
Grab
00530
Solids, Total Suspended
mg/L
4 x Year 1
Grab
1. 4 x Year monitoring shall be conducted in January, March, July, and November.
2. 3 x Year monitoring shall be conducted in March, July, and November.
3, Per Event sampling shall be conducted per irrigation event.
WQ0007144 Version 4.0 Attachment A Page 1 of 1
THIS PAGE BLANK
ATTACHMENT B - APPROVED LAND APPLICATION SITES AND LIMITATIONS
The Young Men's Christian Association of the Triangle Area, Inc. — Camp Seafarer WWTF
Permit Number: WQ0007144 Version: 4.0
IRRIGATION AREA INFORMATION
APPLICATION LIMITATIONS
Field
Owner
County
Latitude
Longitude
Net
Dominant
Parameter
Hourly
Yearly
Units
Acreage
Soil Series
Rate
Max
I
The Young Men's Christian Association of the
Triangle Area, Inc.
Pamlico
35.005°
-76.8487'
5.80
01284 — Non -Discharge Application Rate
NIA
54
inches
2
The Young Men's Christian Association of the
Triangle Area, Inc.
Pamlico
35.0014'
-76,85040
5.80
01284 — Non -Discharge Application Rate
NIA
83.2
inches
3
The Young Men's Christian Association of the
Triangle Area, Inc.
Pamlico
35.0078°
-76.84890
6.40
01284 — Non -Discharge Application Rate
NIA
69.4
inches
Totals
i
I
1
1 18.00
WQ0007144 Version 4.0 Attachment B Page 1 of 1
THIS PAGE BLANK
ATTACHMENT C — GROUNDWATER MONITORING AND LIMITATIONS
Monitoring wells: MW-2, MW-5, MW-6, Mid'-7 & MW-8
Permit Number: WQ0007144 Version: 4.0
GROUNDWATER CHARACTERISTICS
GROUNDWATER STANDARDS
MONITORING REQUIREMENTS
PCS Code
Parameter Description
Daily Maximum
Frequency Measurement
Sample Type
Footnotes
00940
Chloride (as CI)
250
mg/L
3 x Year
Grab
1
31616
Coliform, Fecal MF, M-FC Broth, 44.5 °C
#/100 mL
3 x Year
Grab
1
00610
Nitrogen, Ammonia Total (as N)
1.5
mg/L
3 x Year
Grab
1
00620
Nitrogen, Nitrate Total (as N)
10
mg/L
3 x Year
Grab
1
00400
pH
6.5-8.5
su
3 x Year
Grab
1,2
00665
Phosphorus; Total (as P)
mg/L
3 x Year
Grab
1
70300
Solids, Total Dissolved -180 °C
500
mg/L
3 x Year
Grab
1
82546
Water Level, Distance from measuring point
feet
3 x Year
Calculated
1, 2, 3
I. 3 x Year monitoring shall be conducted in March, July & November; Annual monitoring shall be conducted every November.
2. The measurement of water levels shall be made prior to purging the wells. The depth to water in each well shall be measured from the surveyed point on the top of the casing. The measurement of
pH shall be made after purging and prior to sampling for the remaining parameters.
3. The measuring points (top of well casing) of all monitoring wells shall be surveyed to provide the relative elevation of the measuring point for each monitoring well. The measuring points (top of
casing) of all monitoring wells shall be surveyed relative to a common datum.
4. Monitoring wells shall be reported consistent with the nomenclature and location information provided in Figure 2 and this attachment.
WQ0007144 Version 4.0 Attachment C Page 1 of 1
Print Map - TopoZone
Page I of I
Lower Duck Creek Topo Map in Pamlico County North Carolina
SCALE IN FEET RI
3/4 INCH = 1000'�C����'s���t1D�
Map provided by TopoZone.com JAIN 2 0 2W6
Non-Uisch rge
Pemtittin0
httn://www,tonozone.com/mat)-Drint/?lat=35.0251603&Ion=-76.9016077&title=Lower Du... 1/14/2016
Print Map - TopoZone
Page I of I
Lower Duck Creek Topo Map in Pamlico County North Carolina
SPRAY FIELD
A
SPRAY FIELD LAGOONS
4
J
4..
fj
0A
CAMP SEAFARER
PERMIT NO. WQ0007144
NORTH
G6 01e.
SCALE IN FEET
3/4 INCH = 1000'
Map provided by TopoZonexorn
16
200 M
n. 7
L
jAN 2 0 "016
Non-D'Ischsrge
pemiting U-11ft