HomeMy WebLinkAboutWQ0005790_Correction A_20120403el`
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Charles Wakiid, P.E.
Governor Director
Dee Freeman
Secretary
April 3, 2012 SCANNED
Jerry A. Walters. Town Manager
Town of Oak Island l 5
DATE:
4601 East Oak Island Drive
Oak Island, North Carolina 28465
Subject: Permit No. WQ0005790
Town of Oak Island
Wastewater Treatment, High
Rate Infiltration and
Conjunctive Reclaimed Water
Utilization System
Brunswick County
Dear Mr. Walters:
We are forwarding herewith a revised Attachment A for the permit issued on March 9, 2012 to
the Town of Oak Island. The corrections are as follows:
• Attachment A has been revised to indicate that the monthly average limit for Total Nitrate is
10 milligrams per liter (mgl). The permit issued on March 9, 2012 inadvertently omitted the
limit.
• Attachment A has been revised to indicate'that the daily minimum for pH is 6 standard units
(s. u.). The permit issued on March 9, 2012 inadvertently listed the limit as 6.9 s. u.
Please replace the Attachment A in the permit issued March 9, 2012 with the enclosed corrected
Attachment A.
If you need additional information concerning this matter, please contact Alice M. Wessner at
(919) 807-6425 or alice.wessner@ncdenr.gov.
Sincerely,
r
/harielWakild, P.E.
CC.' Brunswick County Health Department
Wilmington Regional Office, Aquifer Protection Section
G. Robert Graham, PE — George Finch/Roney and Associates, P.A., 309 N. Boylan Avenue,
Raleigh, NC 27603-1402
Permit File WQ0005790
Notebook File WQ0005790
AQUIFER PROTECTION SECTION
1636 Mail Service Center, Raleigh, North Carolina 27699.1636
Location: 511 N. Salisbury Si., Ralegh, North Carolina 27604 One Phone: 9IM07.6464 4 FAX: 919-807-6496 NOt"t�l Cd] O1l 1 F7 �
Internetwvuw ncwaten]ualitV.org .y ,������?����
Art Eqval Oppmunily 1 ANrmaiive Action Emplopel (/may/
ATTACHMENT A - LIMITATIONS AND MONITORING REQUIREMENTS
PPI 001— Effluent — Infiltration Pond and Reclaimed Water Utilization
Permit Number: WQ0005790
Version: 1.5
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORINGREQUIREMENTS
PCS
Code
Parameter Description
Monthly Average
Monthly Geometric
Mean
Daily Minimum
Daily Maximum
Measurement
Frequency
Sample
Type
00310
BOD, 5-Day (20 Deg. C)
10
mg/I
mg/I
mg/I
15
mg/I
2 x month'
Composite
00530
Solids, Total Suspended
5
mg/1
mg/l
mg/1
10
mg/I
2 x month'
Composite
00610
Nitrogen. Ammonia Total (as N)
4
mg/I
mg/1
mg/1
6
mg/1
2 x month'
Composite
00620
Nitrogen, Nitrate Total (as N)
10
mg/l
mg/1
mg/1
mg/l
2 x month'
Composite
00625
Nitrogen, Kjeldahl, Total (as N)
mg/l
mg/l
mg/1
mg/1
2 x month'
Composite
50060
Chlorine, Total Residual
mg/I
mg/1
mg/1
mg/I
Daily
Grab
00680
Carbon, Total Organic (TOC)
mg/I
mg/1
mg/I
mg/l
3 x yearn
Grab
00940
Chloride (as Cl)
mg/I
mg/1
mg/1
mg/I
3 x yearn
Grab
70295
Solids, Total Dissolved
mg/l
mg/1
mg/1
mg/I
3 x yearn
Grab
00400
pl-1
S.U.
S.U.
6
S.U.
9
s.u.
3 x year2
Grab
31616
Coliform, Fecal MF-FC Broth, 44.5C
14
#/100m1
#/100ml
#/100ml
25
#/100ml
2 x month'
Grab
00076
Turbidity, HCH Turbidimeter
ntu
Ntu
ntu
10
ntu
Continuous
Recorder
1. 2 x month monitoring frequency only during the months of April through October. During the remainder of the year, these parameters shall be monitored monthly.
2. 3 x year monitoring shall be conducted during February, June and October.
PPI 002 — WWTF Influent
INFLUENT CHARACTERISTICS
INFLUENT LIMITS
MONITORING
REQUIREMENTS
PCS
Parameter Description
Monthly Average
Monthly Geometric
Daily Minimum
Daily Maximum
Measurement
Sample
Code
Mean
Frequency
Type
50050
Flow, in conduit or thru treatment plant
400,000
gpd
Continuous
Recorder
THIS PAGE BLANK
J J-j - .. ,
ATTACHMENT A - LIMITATIONS AND MONITORING REQUIREMENTS (continued) Permit Number: WQ0005790 Version 1.5
PPI 003 —Effluent— from Conjunctive Reclaimed Water
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING
REQUIREMENTS
PCS
Code
Parameter Description
Monthly Average
Monthly Geometric
Daily Minimum
Daily Maximum
Measurement
Sample
Mean
Frequency
Type
50050
Flow, in conduit or thru treatment plant
225,951
gpd
Continuous
Recorder
PPI 004 — Effluent — Infiltration Pond
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING
REQUIREMENTS
PCS Code
Parameter
Monthly Average
Monthly Geometric
Daily Minimum
Daily Maximum
Measurement
Sample
Description
Mean
Frequency
Type
50050
Flow, in conduit or
180,000
gpd
—]—
Continuous
Recorder
thru treatment plant