HomeMy WebLinkAboutWQ0005247_Final Permit_20020123State of North Carolina
Department of Environment
and Natural Resources
Division of Water Quality
Michael F. Easley, Governor
William G. Ross Jr., Secretary
Gregory J. Thorpe, Ph.D., Acting Director
January 23, 2002
David C. Kellam, Superintendent
Rollingview State Recreation Area
NC DENR- Division of Parks and Recreation
13304 Creedmoor Rd
Wake Forest, NC 27587
Dear Mr. Kellam:
4 •
NCDENR
NORTH CAROLINA DEPARTMENT OF
ENVIRONMENT AND NATURAL RESOURCES
Subject: Permit No. WQ0005247
Rollingview State Recreation Area
Wastewater Spray Irrigation
Durham County
In accordance with your application received March 19, 2001, we are forwarding herewith Permit No.
WQ0005247, dated January 23, 2002, to NC DENR- Division of Parks and Recreation for the continued
operation of the subject wastewater treatment and spray irrigation facilities.
This permit shall be effective from the date of issuance untilDecember 31, 2006, shall void Permit No.
WQ0005247 issued August 9, 1996, and shall be subject to the conditions and limitations as specified therein.
Please pay particular attention to the monitoring requirements in this permit. Failure to establish an adequate
system for collecting and maintaining the required operational information will result in future compliance
problems.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to
request an adjudicatory hearing upon written request within thirty (30) days following receipt of this permit.
This request must be in the form of a written petition, conforming to Chapter I50B of the North Carolina
General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center,Raleigh, NC
27699-6714. Unless such demands are made this permit shall be final and binding.
If you need additional information concerning this matter, please co tact Sue Homewood at (919) 733-
5083 extension 502.
Since
..Gregory J. Thorpe, Ph.D.
cc: Durham County Health Department
Raleigh Regional Office, Water Quality Section
Raleigh Regional Office, Groundwater Section
Groundwater Section, Central Office
Technical Assistance and Certification Unit
Non -Discharge Compliance/Enforcement Unit
Water Quality Central Files
NDPU Files
1617 Mail Service Center, Raleigh, North Carolina 27699-1617 Telephone (919) 733-5083 Fax (919) 715-6048
An Equal Opportunity Affirmative Action Employer 50% recycled110% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
SPRAY IRRIGATION SYSTEM PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and
other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
NC DENR- Division of Parks and Recreation
Durham County
FOR THE
continued operation of a 10,500 GPD wastewater collection, spray irrigation treatment and disposal facility consisting
of approximately 345 linear feet of eight inch gravity sewer, approximately 225 linear feet of six inch gravity sewer, a
2 hp pump station with duplex pumps and high water alarms, eight, 5 hp pump stations each with duplex pumps and
high water alarms, two, 7.5 hp booster pump stations, each with duplex pumps and high water alarms, approximate
17,650 linear feet of 2,3, and 4 inch force main, .a 7 million gallon stabilization lagoon, a 5 million gallon storage
lagoon, a 3,200 gallon chlorine contact chamber with a gaseous chlorinator, a 150 GPM irrigation pump station with
dual submersible pumps, and two 3.55 acre irrigation zones, and wastewater collection facilities consisting of a septic
tank, a pump station with duplex 22 GPM effluent pumps and high water alarms, and approximately 500 linear feet of
two inch force main to discharge collected wastewater from the Superintendent's Residence to the existing wastewater
facilities to serve Rollingview State Recreation Area, with no discharge of wastes to the surface waters, pursuant to the
application received March 19, 2001, and in conformity with the project plan, specifications, and other supporting data
subsequently filed and approved by the Department of Environment and Natural Resources and considered a part of
this permit.
This permit shall be effective from the date of issuance until December 31, 2006, shall void Permit No.
WQ0005247 issued August 9, 1996, and shall be subject to the following specified conditions and limitations:
I. PERFORMANCE STANDARDS
The spray irrigation facilities shall be effectively maintained and operated at all times so that there is no
discharge to the surface waters, nor any contamination of ground waters which will render them
unsatisfactory for normal use. In the event that the facilities fail to perform satisfactorily, including the
creation of nuisance conditions or failure of the irrigation area to adequately assimilate the wastewater, the
Permittee shall take immediate corrective actions including those actions that may be required by the
Division of Water Quality (Division), such as the construction 'of additional or replacement wastewater
treatment and disposal facilities.
2. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to surface c
groundwaters resulting from the operation of this facility.
3. The residuals generated from these treatment facilities must be disposed in accordance with General
Statute 143-215.1 and in a manner approved by the Division.
4. Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited.
5. The following buffers shall be maintained:
a) 400 feet between wetted area and any residence or places of public assembly under separate
ownership,
b) 150 feet between wetted area and property lines,
c) 100 feet between wetted area and wells,
d) 100 feet between wetted area and drainageways or surface water bodies,
e) 50 feet between wetted area and public right of ways,
f) 100 feet between wastewater treatment units and wells, and
g) 50 feet between wastewater treatment units and property lines.
Some of the buffers specified above may not have been included in previous permits for this waste
treatment and disposal system_ These buffers are not intended to prohibit or prevent modifications, which
are required by the Division, to improve performance of the existing treatment facility. These buffers do,
however, apply to modifications of the treatment and disposal facilities which are for the purpose of
increasing the flow that is tributary to the facility. These buffers do apply to any expansion or
modification of the spray irrigation areas and apply in instances in which the sale of property would cause
any of the buffers now complied with, for the treatment and disposal facilities, to be violated. The
applicant is advised that any modifications to the existing facilities will require a permit modification.
II. OPERATION AND MAINTENANCE REQUIREMENTS
1. The facilities shall be properly maintained and operated at all times.
2. Upon classification of the facility by the Water Pollution Control System Operators Certification
Commission (WPCSOCC), the Permittee shall employ a certified wastewater treatment plant operator to
be in responsible charge (ORC) of the wastewater treatment facilities. The operator must hold a certificate
of the type and grade at least equivalent to or greater than the classification assigned to the wastewater
treatment facilities by the WPCSOCC. The Permittee must also employ a certified back-up operator of the
appropriate type and grade to comply with the conditions of 15A NCAC 8G .0202. The ORC of the
facility must visit each Class I facility at least weekly and each Class 11, III, and IV facility at Ieast daily,
excluding weekends and holidays, and must properly manage and document daily operation and
maintenance of the facility and must comply with all other conditions of 15A NCAC 8G .0202. Once the
facility is classified, the Permittee must submit a letter to the WPCSOCC which designates the operator in
responsible charge within thirty days after the wastewater treatment facilities are 50% complete.
A suitable year round vegetative cover shall be maintained.
4. Irrigation shall not be performed during inclement weather or when the ground is in a condition that will
cause runoff.
Adequate measures shall be taken to prevent wastewater runoff from the spray field.
6. The facilities shall be effectively maintained and operated as a non -discharge system to prevent the
discharge of any wastewater resulting from the operation of this facility.
7. The application rate shall not exceed a cumulative loading of 31.2 inches over any twelve (12) month
period at an instantaneous application rate not to exceed 0.2 inches per hour.
8. No type of wastewater other than that from Rollingview State Recreation Area shall be sprayed onto the
irrigation area.
9. No traffic or equipment shall be allowed on the disposal area except while installation occurs or w1
normal maintenance is being performed.
10. Public access to the land application sites shall be controlled during active site use. Such controls may
include the posting of signs showing the activities being conducted at each site.
11. Freeboard in the stabilization and storage lagoons shall not be less than two feet at any time.
12. The Permittee shall provide for the pump station and force main the following items:
a. Pump on/off elevations located so that 2-8 pumping cycles may be achieved per hour in
the pump station,
b. An air relief valve located at all high points along the force main,
c. A screened vent for the wet well,
d. Fillets located in the wet well at the intersection of the flooring and sidewalls,
e. Three feet of cover (minimum) over the force main or the use of ferrous material where
three feet cannot be maintained,
f. Sufficient devices which will protect the pump station from vandals, and
g. Flood protection if the pump station is located below the 100-year flood elevation.
III. MONITORING AND REPORTING REQUIREMENTS
Any monitoring (including groundwater, surface water, soil or plant tissue analyses) deemed necessary by
the Division to insure surface and ground water protection will be established and an acceptable sample
reporting schedule shall be followed.
2. Adequate records shall be maintained by the Permittee tracking the amount of wastewater disposed. These
records shall include, but are not necessarily limited to, the following information:
a. date of irrigation,
b. volume of wastewater irrigated,
c. field irrigated,
d. length of time field is irrigated,
e. continuous weekly, monthly, and year-to-date hydraulic (inches/acre) loadings for each field,
f. weather conditions, and
g. maintenance of cover crops.
Influent flow shall be continuously monitored and daily average flow values shall be reported on Form
NDMR. Flow may be estimated from water use records provided water use is metered. Daily average
values shall be calculated by dividing monthly flow volume by the number of days in the month.
4. The effluent from the subject facilities shall be monitored by the Permittee at the point prior to irrigation
every March, July, and November for the following parameters:
BOD$ TSS
Fecal Coliform pH
NH3 as N
5. Three (3) copies of all operation and disposal records (as specified in condition Ill 2) on Form NDAR-1
and three (3) copies of all effluent monitoring data (as specified in condition II1 3 and Ill 4) on Form
NDMR-1 shall be submitted on or before the last day of the following month. All information shall be
submitted to the following address:
NC Division of Water Quality
Water Quality Section
Non -Discharge Compliance/Enforcement Unit
I617 Mail Service Center
Raleigh, North Carolina 27699-1617
6. A representative annual soils analysis (Standard Soil Fertility Analysis) shall be conducted on each spray
field and the results maintained on file by the Permittee for a minimum of five years. The Standard Soil
Fertility Analysis shall include, but is not necessarily limited to, the following parameters:
Acidity Manganese Potassium
Calcium Percent Humic Matter Sodium
Copper pH Zinc
Magnesium Exchangeable Sodium Percentage Phosphorus
Cation Exchange Capacity Base Saturation (by calculation)
7. Noncompliance Notification:
The Permittee shall report by telephone to the Raleigh Regional Office, telephone number(919) 571-4700,
as soon as possible, but in no case more than 24 hours or on the next working day following the
occurrence or first knowledge of the occurrence of any of the following:
a. Any occurrence at the wastewater treatment facility which results in the treatment of significant
amounts of wastes which are abnormal in quantity or characteristic, such as the dumping of the
contents of a sludge digester; the known passage of a slug of hazardous substance through the facility;
or any other unusual circumstances.
b. Any process unit failure, due to known or unknown reasons, that render the facility incapable of
adequate wastewater treatment such as mechanical or electrical failures of pumps, aerators,
compressors, etc.
Any failure of a pumping station, sewer line, or treatment facility resulting in a by-pass directly to
receiving waters without treatment of all or any portion of the influent to such station or facility.
d. Any time that self -monitoring information indicates that the facility has gone out of compliance with
its permit limitations.
Persons reporting such occurrences by telephone shall also file a written report in letter form within five
(5) days following first knowledge of the occurrence. This report must outline the actions taken or
proposed to be taken to ensure that the problem does not recur.
IV. GROUNDWATER REQUIREMENTS
1. The COMPLIANCE BOUNDARY for the disposal system is specified by regulations in 15A NCAC 2L,
Groundwater CIassifications and Standards. The Compliance Boundary is for the disposal system
constructed after December 31, 1983 is established at either (1) 250 feet from the waste disposal area, or
(2) 50 feet within, the property boundary, whichever is closest to the waste disposal area. An exceedance
of Groundwater Quality Standards at or beyond the Compliance Boundary is subject to immediate
remediation action in addition to the penalty provisions applicable under General Statute 143-
215.6A(a)(1).
4
In accordance with 15A NCAC 2L, a REVIEW BOUNDARY is established around the disposal systems
midway between the Compliance Boundary and the perimeter of the waste disposal area. Any
exceedance of standards at the Review Boundary shall require remediation action on the part of the
perm ittee.
2. Any groundwater quality monitoring, as deemed necessary by the Division, shall be provided.
V. INSPECTIONS
1. Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to insure proper
operation of the subject facilities.
2. The Permittee or his designee shall inspect the wastewater treatment and disposal facilities to prevent
malfunctions and deterioration, operator errors and discharges which may cause or lead to the release of
wastes to the environment, a threat to human health, or a nuisance. ThePermittee shall keep an inspection
log or summary including at least the date and time of inspection, observations made, and any
maintenance, repairs, or corrective actions taken by the Permittee. This log of inspections shall be
maintained by the Permittee for a period of three years from the date of the inspection and shall be made
available upon request to the Division or other permitting authority.
Any duly authorized officer, employee, or representative of the Division may, upon presentation of
credentials, enter and inspect any property, premises or place on or related to the disposal site or facility at
any reasonable time for the purpose of determining compliance with this permit; may inspect or copy any
records that must be maintained under the terms and conditions of this permit, and may obtain samples of
CY
groundwater, surface water, or leachate.
VZ. GENERAL CONDITIONS
I. This permit shall become voidable unless the facilities are constructed in accordance with the conditions of
this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the application
and other supporting data.
This permit is not transferable. In the event there is a desire for the facilities to change ownership, or there
is a name change of the Permittee, a formal permit request must be submitted to the Division accompanied
by an application fee, documentation from the parties involved, and other supporting materials as may be
appropriate. The approval of this request will be considered on its merits and may or may not be
approved.
4. Failure to abide by the conditions and limitations contained in this permit may subject thePermittee to an
enforcement action by the Division in accordance with North Carolina General Statute 143-215.6A to 143-
2I5.6C.
The issuance of this permit does not exempt the Permittee from complying with any and all statutes, rules,
regulations, or ordinances which may be imposed by other government agencies (local, state, and federal)
which have jurisdiction, including but not limited to applicable river buffer rules in 15A NCAC 2B .0200,
erosion and sedimentation control requirements in 15A NCAC Ch. 4 and under the Division's General
Permit NCG0100000, and any requirements pertaining to wetlands under 15A NCAC 2B .0200 and 2H
.0500_
6. A set of approved plans and specifications for the subject project must be retained by thePennittee for the
life of the project.
7. The annual administering and compliance fee must be paid by the Permittee within thirty (30) days after
being billed by the Division. Failure to pay the fee accordingly may cause the Division to initiate action to
revoke this permit as specified by 15A NCAC 2H .0205 (c)(4).
The Permittee, at least six (6) months prior to the expiration of this permit, shall request its extension.
Upon receipt of the request, the Commission will review the adequacy of the facilities described therein,
and if warranted, will extend the permit for such period of time and under such conditions and limitations
as it may deem appropriate.
Permit issued this the 23d day of January, 2002
NORTH AROLINA YENVIRONMENTAL MANAGEMENT COMMISSION
f<Gregory J. Thorpe, Ph.D., Acting Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0005247
ll
16
2'30
^1.
3989
rq� Rec Arm Spey
39g W Q po0 S1Ll
�Ztq9L,�
36000`7-0 if
-790 Z:3r Lt3 "
5-NAY
szo o:
FEE
78.45'
1 J
70 7041 2 080 000 FEET I r705
Mapped, edited, and published by the Geological Survey
Control by USGS, NOS/NOAA, USCE, and North Carolina Geodetic Survey
Topography by photogrammetric methods from aerial photographs
A����
taken 1974. Field checked 1974
Projection and 10,000-foot grid ticks: North Carolina coordinate
system (Lambert conformal conic). 1000-meter Universal
Transverse Mercator grid ticks, zone 17, shown in blue. 1927
North American Datum: To place on the predicted North
American Datum 1983 move the projection lines 12 meters south
and 23 meters west as shown by dashed corner ticks
Fine red dashed lines indicate selected fence and field lines where
generally visible on aerial photographs. This information is unchecked
Revisions shown in purple and woodland compiled in cooperation
with North Carolina agencies from aerial photographs taken
1984 and other sources. This information not field checked
— ���. `� ' `• � •'•�� - sir;
.,rl', i� �� •.�ti;iv ram, -- _ ?`i
'7D6 42'30`r 1707 . ,
tihiz IOOC
GN E
124 MILS 1'22'
�24. MILS
UTM GRID AND 1987 MAGNETIC NORTH
DECLINAVON AT CENTER OF SHEET
Map photoinspected 1990 FOR SALE 6Y
No major culture or drainage changes observed A FO