HomeMy WebLinkAboutWQ0001664_Correspondence_20150310NCDENR
North Carolina Department of Environment and Natural Resources
Pat McCrory Donald R. van der Vaart
Governor Secretary
March 10, 2015
Martin Lashua — Vice President of Operations
Carolina Water Service, Inc. of NC
P.O. Box 240908
Charlotte, NC 28224-0908
Subject: Permit No. WQ0001664
Correction
Belvedere Plantation WWTF
High -Rate Infiltration and
Conjunctive Reclaimed Water
Utilization System
Pender County
Dear Mr. Lashua:
In accordance with a notification received March 4, 2015 from Eddie Baldwin, we are forwarding
Herewith corrected Attachment A of Permit No. WQOOO 1664 issued February 9, 2015.
The correction to the subject permit is as follows:
1. Add an additional PPI to allow different effluent monitoring requirements and limits for pre -
construction (PPI-001) and post -construction (PPI-002) of the WWTP conversion project.
Please replace Attachment A of Permit No. WQ0001664 issued February 9, 2015 with the
enclosed corrected Attachment A.
If you need additional information concerning this permit correction, please contact Chonticha
McDaniel at (919) 807-6337 or chonticha.mcdaniel@ncdenr.gov.
Sincerely,
{ S. Jay rmmerman, Director
Division of Water Resources
cc: Pender County Health Department (Electronic Copy)
Wilmington Regional Office, Water Quality Regional Operations Section (Electronic Copy)
Permit File WQ0001664
Notebook File WQOOOI664
Non -Discharge Permitting Unft
1617 Mail Service Center. Raleigh, North Carolina 27699-1617
Phone: 919-BG7-6464 4 I ntemet: hdPJ1Poftal. ncdenr.orglwebtwg
An Equal opportunity1 Affirmative Action Employer- Made in partw4h recycled paper
ATTACHMENT A — LIMITATIONS AND MONITORING REQUIREMENTS
PPI 001. — WVVTF Effluent (Prior to completion of plant conversion)
Permit Number: WQ0001664 Version: 4.0
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING REQUIREMENTS
PCS
Code
Parameter Description
Units of
Measure
Monthly
Average
Monthly
Geometric Mean
Daily Minimum
Daily Maximum
Measurement
Frequency
Sample
Type
00310
BOD, 5-Day (20 *C)
mg/l
I0
15
2 x Month'
Composite
00940
Chloride (as Cl)
mg/I
3 x Year t
Grab
50060
Chlorine, Total Residual
mg/l
5 x Week
Grab
31616
Coliforrn, Fecal MF, M-FC Broth, 44-5'C
#/100 till
14
25
2 x Month'
Grab
50050
Flow, in Conduit or thru Treatment plant
gpd
216A00
Continuous
Recorder
00610
Nitrogen, Ammonia Total (as N)
mgd
4
6
2 x Month'
3 x Year t
Composite
Grab
00620
Nitrogen, Nitrate Total (as N)
mg/I
00400
pH
so
3 x Year
Grab
70300
Solids, Total Dissolved — 180 °C
cng/I
3 x Year
Grab
00530
Solids, Total Suspended
mg/I
5
10
2 x Month'
Composite
00076
Turbidity, HCH Turbidimeter
ntu
10
Continuous
Recorder
3xYear monitoring shall be conducted in January, June, and October.
2 x Month sampling frequency only during the months of April through October, during the remainder of the year, these parameters shall be monitored monthly.
Conlinued on n Cl pag
WQ0001664 Version 4.0 Attachment A Pagel of 2
ATTACHMENT A — LIMITATIONS AND MONITORING REQUIREMENTS
PPI 002 — WWTF Effluent (After completion of plant conversion)
Permit Number: WQ0001664 Version: 4.0
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING REQUIREMENTS
PCS
Code
Parameter Description
Units of
Measure
Monthly
Average
Monthly
Geometric Mean
Daily Minimum
Daily Maximum
Measurement
Frequency
Sample
Type
00310
BOD, 5-Day (20 "C)
mg/l
10
15
2 x Week
Composite
00940
Chloride (as Cl)
mg/l
3 x Year
Composite
50060
Chlorine, Total Residual
mg/l
5 x Week
Grab
31616
Coliform, Fecal MF, M-FC Broth, 44.5 °C
#/100 ml
14
25
2 x Week
Grab
50050
Flow, in Conduit or thru Treatment plant
gpd
300,000
Continuous
Recorder
00610
Nitrogen, Ammonia Total (as N)
mg/1
4
6
2 x Week
Composite
00625
Nitrogen, Kjeldahl, Total (as N)
mgil
2 x Week
Composite
00620
Nitrogen, Nitrate Total (as N)
mgil
2 x Week
Composite
00600
Nitrogen, Total (as N)
mgll
7
2 x Week
Composite
00400
pH
su
6
9
5 x Week
Grab
00665
Phosphorus, Total (as P)
mg/l
3
2 x Week
Composite
70300
Solids, Total Dissolved — 180 °C
mg/1
i
3 x Year
Composite
00530
Solids, Total Suspended
mg/l
5
10
2 x Week
Composite
00076
Turbidity, HCH Turbidimeter
ntu
I
10
Continuous
Recorder
WQ01
Flow, Reclaimed Water Distributed'
gallons
Monthly
Estimated
3xYcar monitoring shall be conducted in March, July, and November
The application rates on the conjunctive reclaimed water utilization site shall not exceed the following:
a. Fairways I (with Baymeade, Autryville, or Pactolus soils) through 7 and 15 through 18, maximum cumulative loading rates over any twelve month period of 96.7 inches-
b. Fairways I (with Foreston or Leon Soils) and fairways 8 through 14, maximum cumulative loading rates over any twelve month period of 32.2 inches.
C. Maximum instantaneous application rate for all areas is 0.40 inches per hour.
WQ0001664 Version 4.0 Attachment A Page 2 of 2