HomeMy WebLinkAboutWQ0001280_Final Permit_19990308State of North Carolina
Department of Environment
and Natural Resources
Division of Water Quality
James B. Hunt, Jr., Governor
Wayne McDevitt, Secretary
A. Preston Howard, Jr., P.E., Director
March 8, 1999
Mr. Mark D. Hockney
403 Upchurch Farm Road
Durham, NC 27713
Dear Mr. Hockney-
4 IT r
Ilk
•
NCDENR
NORTH CAROLINA DEPARTMENT OF
ENVIRONMENT AND NATURAL RESOURCES
Subject: Permit No. WQ0001280
Hockney Residence
Single Family Wastewater
Spray Irrigation Facility
Durham County
In accordance with your application received December 4, 1998, we are forwarding herewith Permit
No. WQ0001280, dated March 8, 1999, to Mark D. Hockney for continued operation of the subject single
family wastewater treatment and spray irrigation facilities.
This permit shall be effective from the date of issuance until February 28, 2004, shall void Permit No.
WQ0001280 issued May 18, 1993, and shall be subject to the conditions and limitations as specified therein.
Please pay particular attention to the monitoring requirements in this permit. Failure to establish an adequate
system for collecting and maintaining the required operational information will result in future compliance
problems.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right
to request an adjudicatory hearing upon written request within thirty (30) days following receipt of this permit.
This request must be in the form of a written petition, conforming to Chapter 150B of the North Carolina
General Statutes, and filed with the Office of Administrative Hearings, P.O. Drawer 27447, Raleigh, NC
27611-7447. Unless such demands are made this permit shall be final and binding.
If you need additional information concerning this matter, please contact Joe Pearce at (919) 733-5083
extension 544. /`
�ZSincer,
A. Preston Howard, Jr., P.E.
cc: Durham County Health Department
Raleigh Regional Office, Water Quality Section
Technical Assistance and Certification Unit
Non -Discharge Compliance/Enforcement Unit
PO Box 29535, Raleigh, forth Carolina 27626-0535 Telephone (919) 733-5083 Fax (919) 733-0719
An Equal Opportunity Affirmative Action Employer 50% recycled/10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
SINGLE FAMILY SPRAY IRRIGATION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Mr. Mark A Hockney
Durham County
FOR THE
continued operation of a 360 GPD spray irrigation wastewater treatment and disposal system consisting of a
1000 gallon baffled septic tank, a distribution box, dual 150 square foot subsurface sand filter, a tablet
chlorinator, a 2400 gallon storage/pump tank, a 23.5 GPM irrigation pump with automatic pump controls, a
0.34 square foot spray irrigation area , 2-inch diameter force main piping, 6 sprinklers, valves and all
associated appurtenances to serve the Hockney Residence, with no discharge of wastes to the surface waters,
pursuant to the application received December 4, 1999, and in confonnity with the project plan, specifications,
and other supporting data subsequently filed and approved by the Department of Environment and Natural
Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until February 28, 2004, shall void Permit No.
WQ0001280 issued May 19, 1993, and shall be subject to the following specified conditions and limitations:
I. PERFORMANCE STANDARDS
The spray irrigation facilities shall be effectively maintained and operated at all times so that there
is no discharge to the surface waters, nor any contamination of ground waters which will render
them unsatisfactory for normal use. In the event that the facilities fail to perform satisfactorily,
including the creation of nuisance conditions or failure of the irrigation area to adequately
assimilate the wastewater, the Permittee shall take immediate corrective actions including those
actions that may be required by the Division of Water Quality (Division), such as the construction
of additional or replacement wastewater treatment and disposal facilities.
2. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to
surface or groundwaters resulting from the operation of this facility.
The residuals generated from these treatment facilities must be disposed in accordance with
General Statute 143-215.1 and in a manner approved by the Division.
4. Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited.
The following buffers shall be maintained:
a) 400 feet between wetted area and any residence or places of public assembly under separate
ownership,
b) 150 feet between wetted area and property lines,
c) 100 feet between wetted area and wells,
d) 100 feet between wetted area and drainageways or surface water bodies,
e) 50 feet between wetted area and public right of ways,
f) 100 feet between treatment/storage units and any wells, and
g) 50 feet between treatment units and property lines.
Some of the buffers specified above may not have been included in previous permits for this waste
treatment and disposal system. These buffers are not intended to prohibit or prevent
modifications, which are required by the Division, to improve performance of the existing
treatment facility. These buffers do, however, apply to modifications of the treatment and disposal
facilities which are for the purpose of increasing the flow that is tributary to the facility. These
buffers do apply to any expansion or modification of the spray irrigation areas and apply in
instances in which the sale of property would cause any of the buffers now complied with, for the
treatment and disposal facilities, to be violated. The applicant is advised that any modifications to
the existing facilities will require a permit modification.
H. OPERATION AND MAINTENANCE REQUIREMENTS
The facilities shall be properly maintained and operated at all times.
2. Upon classification of the facility by the Water Pollution Control System Operators Certification
Commission (WPCSOCC), the Permittee shall employ a certified wastewater treatment plant
operator to be in responsible charge (ORC) of the wastewater treatment facilities. The operator
must hold a certificate of the type and grade at least equivalent to or greater than the classification
assigned to the wastewater treatment facilities by the WPCSOCC. The Permittee must also
employ a certified back-up operator of the appropriate type and grade to comply with the
conditions of 15A NCAC 8A .0202. The ORC of the facility must visit each Class I facility at
least weekly and each Class II, III, and IV facility at least daily, excluding weekends and holidays,
and must properly manage and document daily operation and maintenance of the facility and must
comply withal] other conditions of 15A NCAC 8A .0202.
A suitable year round vegetative cover shall be maintained.
4. Irrigation shall not be performed during inclement weather or when the ground is in a condition
that will cause runoff.
5. Adequate measures shall be taken to prevent wastewater runoff from the spray field.
6. The application rate shall not exceed a cumulative loading of 10.4 inches per acre over anytwelve
(12) month period.
7. The facilities shall be effectively maintained and operated as a non -discharge system to prevent
the discharge of any wastewater resulting from the operation of this facility.
8. No type of wastewater other than that from the Hockney Residence shall be sprayed onto the
irrigation area.
9. In the event that the sprinkler heads fail to achieve the design diameter due to obstructions, the
obstructions shall be removed or the sprinkler heads shall be raised and supported to such height
that the design diameter is achieved.
10. No traffic or equipment shall be allowed on the disposal area except while installation occurs or
while normal maintenance is being performed.
11. The spray irrigation field shall be fenced with at least a two strand wire fence.
12. The Permittee is responsible for the operation and maintenance of the entire treatment and disposal
system including, but not limited to, the following items:
a. The septic tank shall be checked annually and pumped out as needed.
b. The tablet chlorinator shall be checked every week. Tablets shall be added so as to provide
proper chlorination.
c. The storage, pump, and alarm systems shall be inspected weekly. The scum layer shall be
removed at the same interval as the septic tank is cleaned out.
d. The spray system shall be inspected weekly to make certain of the sprayers proper operation,
that the vegetative growth allows a proper spray pattern, that the soil is assimilating the
disposed treated wastewater with no surface runoff, and that no objectionable odors are being
generated.
III. MONITORING AND REPORTING REOUIREMENTS
Any monitoring deemed necessary by the Division to insure surface and ground water protection
will be established and an acceptable sampling reporting schedule shall be followed.
2. The Permittee shall maintain records of all maintenance performed on the system and irrigation
area, as required in Condition II 12 for a minimum of five years. This information shall be
provided to the Division upon request.
3. Noncompliance Notification:
The Permittee shall report by telephone to the Raleigh Regional Office, telephone number
(919)571-4700, as soon as possible, but in no case more than 24 hours or on the next working day
following the occurrence or first knowledge of the occurrence of any of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable
of adequate wastewater treatment, such as mechanical or electrical failures of pumps, spray
heads, etc.; or
b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to
receiving waters without treatment of all or any portion of the influent to such station or
facility.
Persons reporting such occurrences by telephone shall also file a written report in letter form
within five (5) days following first knowledge of the occurrence. This report must outline the
actions taken or proposed to be taken to ensure that the problem does not recur.
3
IV. INSPECTIONS
Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to insure
proper operation of the subject facilities.
2. Any duly authorized officer, employee, or representative of the Division may, upon presentation
of credentials, enter and inspect any property, premises or place on or related to the disposal site or
facility at any reasonable time for the purpose of determining compliance with this permit, may
inspect or copy any records that roust be maintained under the terms and conditions of this permit,
and may obtain samples of groundwater, surface water, or Ieachate.
V. GENERAL CONDITIONS
This permit shall become voidable unless the facilities are constructed in accordance with the
conditions of this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
3. This permit is not transferable. In the event there is a desire for the facilities to change ownership,
or there is a name change of the Permittee, a formal permit request must be submitted to the
Division accompanied by an application fee, documentation from the parties involved, and other
supporting materials as may be appropriate. The approval of this request will be considered on its
merits and may or may not be approved.
4. Upon the availability of a municipal or regional sewerage collection system, the subject
wastewater treatment facilities shall be abandoned and all wastewater discharged into the
municipal or regional sewerage system.
5. Failure to abide by the conditions and limitations contained in this permit may subject the
Permittee to an enforcement action by the Division in accordance with North Carolina General
Statute 143-215.6A to 143-215.6C.
6. The issuance of this permit does not preclude the Permittee from complying with any and all
statutes, rules, regulations, or ordinances which may be imposed by other government agencies
(local, state, and federal) which have jurisdiction.
7. This permit may be revoked if the Permittec fails to abide by the conditions of the "Operation and
Maintenance Agreement" previously signed by the Permittee.
8. A set of approved plans and specifications for the subject project must be retained by the Permittee
for the life of the project.
4
9. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its
extension. Upon receipt of the request, the Commission will review the adequacy of the facilities
described therein, and if warranted, will extend the Permit for such period of time and under such
conditions and limitations as it may deem appropriate.
Permit issued this the Eighth day of March, 1999
NORTH CAMLINA ENVUeONMEXTAL MANAGEMENT COMMISSION
A. Preston Howard, Jr., P.E., Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0001280
itAl
OEpa RrMENr ofi t C FORTH CA ROLINA
t NA-r 1RAL
6B4 gip„ RAZE! NORThO ECONOMIC RESOURCES
...
CAQOLINA
�' _ TourNwFsr nu tia
687
057
Cem • '�o (eflya Ch
,-
J - _ T_RP�� //!O /� v� •�` Q� •l VSL] 1�^ \'11�, — ..
LU27.
ri
248
_�,-��o !-`�y •' i. Tit-'- _ r � �- � �" _ _ �.
i ell,---:
Cclm
,cp, _� rho �.: I • _ , ,- ' � � � /
OPERATION AND MAINTENANCE AGREEMENT FOR THE
DIVISION OF WATER QUALITY RECEIVED
WATER QUALITY SECTION
Name:
Addres
City: -- ) 46 v+!N State: li ZIP:
Single Family Residence Wastewater Treatment System
Final Disposal by Spray Irrigation
Permit No. Wl4 nin law
County
I agree to operate and maintain the wastewater treatment system as follows:
A-))i3
1. The Permittee is responsible for the operation and maintenance of the entire treatment and
disposal system including, but not limited to, the following items:
a. The septic tank shall be checked every six (6) months and pumped out as required.
b. The tablet chlorinator shall be checked every week until the actual usage rate is established
and thence on a monthly basis. Tablets shall be added so as to provide proper chlorination.
c. The storage system, pump system, and alarm system shall be inspected monthly. The
scum layer shall be removed at the same interval as the septic tank is cleaned out.
d. The spray system shall be inspected monthly to make certain of the sprayers proper
operation, that the vegetative growth allows proper spray patterns, that the soil is absorbing
the disposed treated wastewater with no surface runoff, and that no objectionable odors are
being generated.
2. Failure of the Permittee to properly operate this system is subject to a penalty up to 510.000 per
day.
3. Failure to meet permit conditions or violation of the State's surface or groundwater regulations
will require cessation of occupancy of the residence.
I understand that failure to comply with these conditions along with the permit conditions may result in
voiding the perVd.
S ignature:
Notary Sew
Date:
Notary Signature: Date: l oT 119