HomeMy WebLinkAboutWQ0000088_Correction_19940311State of North Carolina
Department of Environment,
Health and Natural Resources
)ivision of Environmental Management
James B. Hunt, Jr., Governor
Jonathan B. Howes, Secretary
A. Preston Howard, Jr., P.E., Director
March 11, 1994
William J. Brinn, Jr., Vice President
Governors Club Development Corporation
Post Office Box 2615
Chapel Hill, North Carolina 27515
RE: Governors Club Development Corporation
Governors Club
Chatham County
Dear Mr. Brinn:
&R4 J
�EHNFi
On February 25, 1994, the Division received your flow reduction request and support
documentation concerning flows associated with present residences in Governors Club. Your letter
requested the Division allow the use of a flow rate of 240 gallons per day per residence rather that the 120
GPD per bedroom required by the North Carolina Administrative Code. In support of your request,
documentation and flow data was supplied from Crayton Utility Company's Bellefem Wastewater
Treatment Facility, Permit No. 15166, and the Governors Club Limited Partnership Wastewater Treatment
7�acility, WQ0000088.
An evaluation was made using the flow data supplied for the Governors Club Wastewater
Treatment Facility which includes 12 months of data starting from February, 1993. In accordance with
15A NCAC .0219(1)(3), the peak month was found to be December, 1993, and a flow rate was
determined by averaging the three (3) peak days of that month. A flow rate of 222 GPD was calculated.
The Crayton Utility flow data for December, 1993 and January, 1993 was used to confirm the flow rate
found with the Governors Club flow data.
In view of the information submitted, the Division of Environmental Management will allow the
use of 240 GPD per residence on all applicable non -discharge permit applications for future wastewater
collection extensions in Governors Club which are made tributary to the Governors Club Limited
Partnership Wastewater Treatment Facility, WQ0000088. This consideration applies to any applicable
future projects submitted to this Division as well as any projects which are presently under review. This
letter must be submitted with future wastewater collection extensions applications. All wastewater
collection systems previously approved will require a $400.00 fee to amend each permit to account for the
change in flow made tributary to the Governors Club Wastewater Treatment Facility.
If you have any questions or comments regarding this matter, please contact Mr. Michael D. Allen
at (919) 733-5083.
Sincerely,
,
cc: Raleigh Regional Office, Water Quality Creston Hj�Jr., P.E.
W. Lee Fleming, Jr.
State Engineering Review Group
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-7015 FAX 919-733-2496