HomeMy WebLinkAboutWQ0004367_Final Permit_19951031State of North Carolina
Department of Environment,
Health and Natural Resources
Division of Environmental Management
James B. Hunt, Jr., Governor
Jonathan B. Howes, Secretary
A. Preston Howard, Jr., P.E., Director
October 31, 1995
Mr. Richard Pasin, President
Leland Resin Corporation
P.O. Box 1080
Leland, NC 28451
A
LT!MA,
••
1 EFE F1
Subject: Permit No. WQ0004367
Leland Resin Corporation
Wastewater Spray Irrigation
Brunswick County
Dear Mr. Pasin:
In accordance with your renewal request received July 3, 1995, we are forwarding herewith Permit
No. WQ0004367, dated October 31, 1995, to Leland Resin Corporation for the continued operation of the
subject wastewater spray irrigation facilities.
This permit shall be effective from the date of issuance until September 30, 2000, shall void Permit
No. WQ0004367 issued August 19, 1992, and shall be subject to the conditions and limitations as
specified therein. Please pay particular attention to the monitoring requirements in this permit. Failure to
establish an adequate system for collecting and maintaining the required operational information will result
in future compliance problems.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of
this permit. This request must be in the form of a written petition, conforming to Chapter 150B& of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings, P.O. Drawer
27447, Raleigh, NC 27611-7447. Unless such demands are made this permit shall be final and binding.
If you need additional information concerning this matter, please contact Mr. Ray Cox at (919)
733-5083, extension 549.
Sincerely,
A. PrestA Howard, r., P.E.
cc: Brunswick County Health Department
Wilmington Regional Office, Water Quality Section
Wilmington Regional Office, Groundwater Section
Bob Cheek, Groundwater Section, Central Office
Training and Certification Unit (no revised rating)
Facilities Assessment Unit
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-5083 FAX 919-733-9919
An Equal Opportunity Affirmative Action Employer 50% recycled/ 10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT, HEALTH AND NATURAL RESOURCES
RALEIGH
SPRAY IRRIGATION SYSTEM PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Ireland Resin Corporation
Brunswick County
FOR THE
continued operation of a 9,060 GPD (weekly average) spray irrigation 'disposal facility consisting of a
2,500 gallon storage tank, a 190 GPM pump station with high water alarms, approximately 850 linear feet
of 3-inch force main, four spray irrigation heads mounted on 30-inch risers which spray at a radius of 90
feet, with a total application area of 2.34 acres, to serve Leland Resin Corporation, with no discharge of
wastes to the surface waters, pursuant to the renewal request received July 3, 1995, and in conformity
with the project plan, specifications, and other supporting data subsequently filed and approved by the
Department of Environment, Health and Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until September 30, 2000, shall void Permit
No. WQ0004367 issued August 19, 1992, and shall be subject to the following specified conditions and
limitations:
I. PERFORMANCE STANDARDS
1. The spray irrigation facilities shall be effectively maintained and operated at all times so that
there is no discharge to the surface waters, nor any contamination of ground waters which
will render them unsatisfactory for normal use. In the event that the facilities fail to
perform satisfactorily, including the creation of nuisance conditions or failure of the
irrigation area to adequately assimilate the wastewater, the Permittee shall take immediate
corrective actions including those actions that may be required by the Division of
Environmental Management, such as the construction of additional or replacement
wastewater treatment and disposal facilities.
2. The issuance of this permit shall not relieve the Permittee of the responsibility for damages
to surface or groundwaters resulting from the operation of this facility.
3. Any residuals generated from these facilities must be disposed in accordance with General
Statute 143-215.1 and in a manner approved by the North Carolina Division of
Environmental Management.
4. The following buffers shall be maintained:
a) 400 feet between wetted area and any residence or places of public assembly under
separate ownership,
b) 150 feet between wetted area and property lines,
c) 100 feet between wetted area and wells,
d) 100 feet between wetted area and drainageways or surface water bodies,
e) 50 feet between wetted area and public right of ways,
f) 100 feet between wastewater treatment units and wells, and
g) 50 feet between wastewater treatment units and property lines.
Some of the buffers specified above may not have been included in previous permits for
this waste disposal system. These buffers are not intended to prohibit or prevent
modifications, which are required by the Division, to improve performance of the existing
facility. These buffers do, however, apply to modifications of the disposal facilities which
are for the purpose of increasing the flow that is tributary to the facility. These buffers do
apply to any expansion or modification of the spray irrigation areas and apply in instances
in which the sale of property would cause any of the buffers now complied with, for the
disposal facilities, to be violated. The applicant is advised that any modifications to the
existing facilities will require a permit modification.
II. OPERATION AND -MAINTENANCE -REQUIREMENTS
I . The facilities shall be properly maintained and operated at all tunes.
2. Upon classification of the facility by the Certification Commission, the Permittee shall
employ a certified wastewater treatment plant operator to be in responsible charge (ORC) of
the wastewater treatment facilities. The operator must hold a certificate of the type and
grade at least equivalent to or greater than the classification assigned to the wastewater
treatment facilities by the Certification Commission, The Permittee must also employ a
certified back-up operator of the appropriate type and grade to comply with the conditions
of Title 15A, Chapter 8A, .0202. The ORC of the facility must visit each Class I facility at
least weekly and each Class II, III, and N facility at least daily, excluding weekends and
holidays, and must properly manage and document daily operation and maintenance of the
facility and must comply with all other conditions of Title 15A, Chapter 8A, .0202.
3. A suitable vegetative cover shall be maintained.
4. Irrigation shall not be performed during inclement weather or when the ground is in a
condition that will cause runoff.
5. Adequate measures shall be taken to prevent wastewater runoff from the spray field.
6. The facilities shall be effectively maintained and operated as a non -discharge system to
prevent the discharge of any wastewater resulting from the operation of this facility.
7. The application rate shall not exceed a cumulative loading of 52.0 inches over any twelve
(12) month period at an instantaneous application rate that will not cause ponding or runoff.
8. No type of wastewater other than that from Leland Resin Corporation's once -through, non -
contact cooling water (for the chemical reactors) and the boiler blowdown water shall be
sprayed onto the irrigation area.
9. No traffic or equipment shall be allowed on the disposal area except while installation
occurs or while normal maintenance is being performed.
Oj
10. Public access to the land application sites shall be controlled during active site use. Such
controls may include the posting of signs showing the activities being conducted at each
site.
III. MONITORING AND REPORTING REQUIREMENTS
1. Any monitoring (including groundwater, surface water, soil or plant tissue analyses)
deemed necessary by the Division of Environmental Management to insure surface and
ground water protection will be established and an acceptable sampling reporting schedule
shall be followed.
2. Adequate records shall be maintained by the Permittee tracking the amount of wastewater
disposed. These records shall include, but are not necessarily limited to, the following
information:
a. date of irrigation,
b . volume of wastewater irrigated,
c. field irrigated,
d . length of time field is irrigated,
e. continuous weekly, monthly, and year-to-date hydraulic (inches/acre) loadings for each
field,
f. weather conditions, and
g . maintenance of cover crops.
3. Three (3) copies of all operation and disposal records (as specified in condition III 2), on
Form NDAR-1, shall be submitted on or before the last day of the following month to the
following address:
NC Division of Environmental Management
Water Quality Section
Facility Assessment Unit
PO Box 29535
Raleigh, NC 27626-0535
4. Noncompliance Notification:
The Permittee shall report by telephone to the Wilmington Regional Office, telephone
number (910) 395-3900, as soon as possible, but in no case more than 24 hours or on the
next working day following the occurrence or first knowledge of the occurrence of any of
the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility
incapable of adequate wastewater treatment, such as mechanical or electrical failures of
pumps, aerators, compressors, etc.;
b. Any failure of the pumping station, irrigation line, or other facility resulting in a by-
pass directly to receiving waters; or
c. Any time that self -monitoring information indicates that the facility has gone out of
compliance with its permit limitations.
Persons reporting such occurrences by telephone shall also file a written report in letter
form within 15 days following first knowledge of the occurrence. This report must outline
the actions taken or proposed to be taken to ensure that the problem does not recur.
IV. GROUNDWATER REQUIREMENTS
The three monitor wells MW-1, MW-2 and MW-3 shall be sampled every February, June
and October for the following parameters:
NO3 Total Phosphorus
TDS TOC
pH Water Levels
The measurement of water levels must be made prior to sampling for the remaining
parameters. The depth to water in each well shall be measured from the surveyed point on
the top of the casing.
The measuring points (top of well casing) of all monitoring wells shall be surveyed to
provide the relative elevation of the measuring point for each monitoring well.
If TOC concentrations greater than 10 mg/l are detected in any downgradient monitoring
well, additional sampling and analysis must be conducted to identify the individual
constituents comprising this TOC concentration. If the TOC concentration as measured in
the background monitor well exceeds 10 mg/l, this concentration will be taken to represent
the naturally occurring TOC concentration. Any exceedances of this naturally occurring
TOC concentration in the downgradient wells shall be subject to the additional sampling
and analysis as described above.
The results of the sampling and analysis shall be sent to the Groundwater Section, Permits
and Compliance Unit, P.O. Box 29578 Raleigh, N.C. 27626-0578 on Form GW-59
[Compliance Monitoring Report Form] every March, July and November.
2. Any additional groundwater quality monitoring, as deemed necessary by the Division, shall
be provided.
3. The COMPLIANCE BOUNDARY for the disposal system is specified by regulations in
15A NCAC 2L, Groundwater Classifications and Standards. The Compliance Boundary is
for the disposal system constructed after December 31, 1983 is established at either (1) 250
feet from the waste disposal area, or (2) 50 feet within the property boundary, whichever is
closest to the waste disposal area. An exceedance of Groundwater Quality Standards at or
beyond the Compliance Boundary is subject to immediate remediation action in addition to
the penalty provisions applicable under General Statute 143-215.6A(a)(1).
In accordance with 15A NCAC 2L, a REVIEW BOUNDARY is established around the
disposal systems midway between the Compliance Boundary and the perimeter of the
waste disposal area. Any exceedance of standards at the Review Boundary shall require
remediation action on the part of the permittee.
V . INSPECTIONS
1. Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to
insure proper operation of the subject facilities.
2. The Permittee or his designee shall inspect the wastewater treatment and disposal facilities
to prevent malfunctions and deterioration, operator errors and discharges which may cause
or lead to the release of wastes to the environment, a threat to human health, or a nuisance.
The Permittee shall keep an inspection log or summary including at least the date and time
of inspection, observations made, and any maintenance, repairs, or corrective actions taken
by the Permittee. This Iog of inspections shall be maintained by the Permittee for a period
of three years from the date of the inspection and shall be made available upon request to
the Division of Environmental Management or other permitting authority.
4
3. Any duly authorized officer, employee, or representative of the Division of Environmental
Management may, upon presentation of credentials, enter and inspect any property,
premises or place on or related to the disposal site or facility at any reasonable time for the
purpose of determining compliance with this permit, may inspect or copy any records that
must be maintained under the terms and conditions of this permit, and may obtain samples
of groundwater, surface water, or leachate.
V I. GENERAL CONDITIONS
This permit shall become voidable unless the facilities are constructed in accordance with
the conditions of this permit, the approved plans and specifications, and other supporting
data.
2. This permit is effective only with respect to the nature and volume of wastes described in
the application and other supporting data.
3. This permit is not transferable. In the event there is a desire for the facilities to change
ownership, or there is a name change of the Permittee, a formal permit request must be
submitted to the Division of Environmental Management accompanied by an application
fee, documentation from the parties involved, and other supporting materials as may be
appropriate. The approval of this request will be considered on its merits and may or may
not be approved.
4. Failure to abide by the conditions and limitations contained in this permit may subject the
Permittee to an enforcement action by the Division of Environmental Management in
accordance with North Carolina General Statute 143-215.6(a) to 143-215.6(c).
5. The issuance of this permit does not preclude the Permittee from complying with any and
all statutes, rules, regulations, or ordinances which may be imposed by other government
agencies (local, state, and federal) which have jurisdiction.
6. A set of approved plans and specifications for the subject project must be retained by the
Permittee for the life of the project.
7. The annual administering and compliance fee must be paid by the Permittee within thirty
(30) days after being billed by the Division. Failure to pay the fee accordingly may cause
the Division to initiate action to revoke this permit as specified by 15A NCAC 2H .0205
(c)(4).
8. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its
extension. Upon receipt of the request, the Commission will review the adequacy of the
facilities described therein, and if warranted, will extend the permit for such period of time
and under such conditions and limitations as it may deem appropriate.
Permit issued this the thirty-first day of October, 1995
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
o C�CU� l.11.CYC�C I , L /& -
A. Presto oward, Jr., P.E., Director
Division &Environmental Management
By Authority of the Environmental Management Commission
Permit Number WQ0004367
5
•,� \ Cem C:hapcl �)i I s �/ 1
. \ 'Cem y,, ' } �'' e I
i .�12.5 ...�
•�77.5 f {`-' Sandpit 2
Robinson : •Is53 _
��� Cam
Newliope
PhoenixITO
G pit
'
L
Traik3r £z •�
Perk - 'o.--------- - —
�
]1 _ h ernx �� a
iBM
7.3 Oil
Trailer /• � �
Park s
_ a `Eastbrook
. // % � -_ �`\` ���—✓ Yam\ � - � ',�
Johns4 n -
.. Chapel
, er 1455
Williams 1 �' Park
/f Cam,- _
/
B�Trailer90
�j Park
BM
am .�
BM 20.2
�� f- �� V. •. " Leland
eliti •6M 7.6
'F
Ch
��`� ' •.� I �:� Ot _ _-�.-Se'thel..`-Subst f
\1 Py `� ■ o� ? Lea %P 1 E
�� A- .CgQpF ••I • •,`' SAS
168 6' — 169 '70 (Win+nrnaowl 171 f,fKMTOU.S. 772r30r,
1 nn 5352 it W WICMINUTOrV! 12
KM
LC--_LR7�lD ��tSll� LDRPr)Q�I-T1DI�CALE 1.24000
MN 1 .5 0 KILOWTERS 1 2
GN 1000 0 METERS 1000 2000
1 .5 0 1
5 h' MILES —
16 MILS 1139• 1000 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10 000
2s MILS - — FEET
e
t/
WP,tr4f FAKT,1- Midi,
PNO'Otsc WCncRI . �
9-7'0r ze
C," AluST
ruMr otJ
FU W O P P !�� A& f6
u'
7a N ' s
Leland Resin Corporation
Brunswick County
WQ0004367/GW95157
August, 1995
a�
,t
All &V
Ales = 2.co. I A44 v�5