HomeMy WebLinkAboutWQ0004216_Final Permit_19950615State of North Carolina
Department of Environment,
Health and Natural Resources
Division of Environmental Management
James B. Hunt, Jr., Governor
Jonathan B. Howes, Secretary
A. Preston Howard, Jr., P.E., Director
June 15, 1995
Mr. Richard Goodson, Owner
1404 Staley Boswell Road
Yanceyville, North Carolina 27379
Dear Mr. Goodson:
1 • •
r �T
E-= F1
Subject: Permit No. WQ0004216
Richard Goodson
Single Family Wastewater
Spray Irrigation Facility
Caswell County
In accordance with your application received March 6, 1995, we are forwarding herewith Permit
No. WQ0004216, dated June 15, 1995, to Mr. Richard Goodson for the continued operation of the
subject single family wastewater treatment and spray irrigation facilities.
This permit shall be effective from the date of issuance until May 31, 2000, shall void Permit No.
WQ0004216 issued December 6, 1990, and shall be subject to the conditions and limitations as specified
therein. Please pay particular attention to the monitoring requirements in this permit. Failure to establish
an adequate system for collecting and maintaining the required operational information will result in future
compliance problems.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of
this permit. This request must be in the form of a written petition, conforming to Chapter 150B of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings, P.O. Drawer
27447, Raleigh, NC 27611-7447. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this matter, please contact Ms. -Angela Y. Griffin at (919) 733-5083 ext 554.
Sincerely,
A. Prest Howard, Jr., P.E.
cc: Caswell County Health Department
Winston-Salem Regional Office, Water Quality Section
Training and Certification Unit
Facilities Assessment Unit
Alley, Williams, Carmen & King, Inc.
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-5083 FAX 919-733-9919
An Equal Opportunity Affirmative Action Employer 50% recycled/ 10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT, HEALTH AND NATURAL RESOURCES
RALEIGH
SINGLE FAMILY SPRAY IRRIGATION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Mr. Richard Goodson
Caswell County
1-taffW01
continued operation of a 360 GPD spray irrigation wastewater treatment and disposal system consisting of
a 1,500 gallon baffled septic tank, a 6 foot by 52.5 foot subsurface sand filter, a tablet chlorinator, a 2,000
gallon storage/pump tank, and a 12,868 ft2 spray irrigation area to serve the Goodson Residence, with no
discharge of wastes to the surface waters, pursuant to the application received March 6, 1995, and in
conformity with the project plan, specifications, and other supporting data subsequently filed and
approved by the Department of Environment, Health and Natural Resources and considered a part of this
permit.
This permit shall be effective from the date of issuance until May 31, 2000, shall void Permit No.
WQ0004216 issued December 6, 1990, and shall be subject to the following specified conditions and
limitations:
I. PERFORMANCE STANDARDS
1. The spray irrigation facilities shall be effectively maintained and operated at all times so that
there is no discharge to the surface waters, nor any contamination of ground waters which
will render them unsatisfactory for normal use. In the event that the facilities fail to
perform satisfactorily, including the creation of nuisance conditions or failure of the
irrigation area to adequately assimilate the wastewater, the Permittee shall take immediate
corrective actions including those actions that may be required by the Division of
Environmental Management, such as the construction of additional or replacement
wastewater treatment and disposal facilities. -
2. The issuance of this permit shall not relieve the Permittee of the responsibility for damages
to surface or groundwaters resulting from the operation of this facility.
3. The sand media of the subsurface sandfilter must comply with the Division's sand
specifications.
4. The residuals generated from these treatment facilities must be disposed in accordance with
General Statute 143-215.1 and in a manner approved by the North Carolina Division of
Environmental Management.
5. Diversion or bypassing of the untreated wastewater from the treatment facilities is
prohibited.
6. The following buffers shall be maintained:
a) 400 feet between wetted area and any residence or places of public assembly under
separate ownership,
b) 150 feet between wetted area and property lines,
c) 100 feet between wetted area and wells,
d) 100 feet between wetted area and drainageways or surface water bodies,
e) 50 feet between wetted area and public right of ways,
f) 100 feet between treatment/storage units and any wells, and
g) 50 feet between treatment units and property lines.
II. OPERATION AND MAINTENANCE REQUIREMENTS
I . The facilities shall be properly maintained and operated at all times.
2. Upon classification of the facility by the Certification Commission, the Permittee shall
employ a certified wastewater treatment plant operator to be in responsible charge (ORC) of
the wastewater treatment facilities. The operator must hold a certificate of the type and
grade at least equivalent to or greater than the classification assigned to the wastewater
treatment facilities by the Certification Commission. The Permittee must also employ a
certified back-up operator of the appropriate type and grade to comply with the conditions
of Title 15A, Chapter 8A, .0202. The ORC of the facility must visit each Class I facility at
least weekly and each Class II, III, and IV facility at least daily, excluding weekends and
holidays, and must properly manage and document daily operation and maintenance of the
facility and must comply with all other conditions of Title 15A, Chapter 8A, .0202.
3. A suitable vegetative cover of 100 lbs/acre of Tall Fescue and 50 lbs/acre of Rye Grain
shall be maintained during the months of January - July , November and December.
During the months of August, September, and October, 100 lbs/acre of Tall Fescue and 50
lbs/acre of Sorghum-Sundan Hybrids shall be maintained.
4. Irrigation shall not be performed during inclement weather or when the ground is in a
condition that will cause runoff.
5. Adequate measures shall be taken to prevent wastewater runoff from the spray field.
6. The application rate shall not exceed 20.5 inches per year.
7. The facilities shall be effectively maintained and operated as a non -discharge system to
prevent the discharge of any wastewater resulting from the operation of this facility.
8. No type of wastewater other than that from the Goodson Residence shall be sprayed onto
the irrigation area-
9.
rea.
9. In the event that the sprinkler heads fail to achieve the design diameter due to obstructions,
the obstructions shall be removed or the sprinkler heads shall be raised and supported to
such height that the design diameter is achieved.
10. No traffic or equipment shall be allowed on the disposal area except while installation
occurs or while normal maintenance is being performed.
11. The Permittee is responsible for the operation and maintenance of the entire treatment and
disposal system including, but not limited to, the following items:
a. The septic tank shall be checked annually and pumped out as needed.
2
b. The tablet chlorinator shall be checked every week. Tablets shall be added so as to
provide proper chlorination.'
c. The storage, pump, and alarm systems shall be inspected weekly. The scum layer shall
be removed at the same interval as the septic tank is cleaned out.
d. The spray system shall be inspected weekly to make certain of the sprayers proper
operation, that the vegetative growth allows a proper spray pattern, that the soil is
assimilating the disposed treated wastewater with no surface runoff, and that no
objectionable odors are being generated.
III. MONITORING AND REPORTING REQUIREMENTS
I . Any monitoring deemed necessary by the Division of Environmental Management to insure
surface and ground water protection will be established and an acceptable sampling
reporting schedule shall be followed.
2. The Permittee shall maintain records of all maintenance performed on the system and
irrigation area, as required in Condition II 11 for a minimum of five years. This
information shall be provided to the Division of Environmental Management upon request.
3. Noncompliance Notification:
The Permittee shall report by telephone to the Winston-Salem Regional Office, telephone
number (910) 771-4600, as soon as possible, but in no case more than 24 hours or on the
next working day following the occurrence or first knowledge of the occurrence of any of
the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility
incapable of adequate wastewater treatment, such as mechanical or electrical failures of
pumps, spray heads, etc.; or
b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to
receiving waters without treatment of all or any portion of the influent to such station or
facility.
Persons reporting such occurrences by telephone shall also file a written report in letter
form within 15 days following first knowledge of the occurrence. This report must outline
the actions taken or proposed to be taken to ensure that the problem does not recur.
IV. INSPECTIONS
1. Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to
insure proper operation of the subject facilities.
2. Any duly authorized officer, employee, or representative of the Division of Environmental
Management may, upon presentation of credentials, enter and inspect any property,
premises or place on or related to the disposal site or facility at any reasonable time for the
purpose of determining compliance with this permit, may inspect or copy any records that
must be maintained under the terms and conditions of this permit, and may obtain samples
of groundwater, surface water, or leachate.
V. GENERAL CONDITION
1. This permit shall become voidable unless the facilities are constructed in accordance with
the conditions of this permit, the approved plans and specifications, and other supporting
data.
3
2. This permit is effective only with respect to the nature and volume of wastes described in
the application and other supporting data.
3. This permit is not transferable. In the event there is a desire for the facilities to change
ownership, or there is a name change of the Permittee, a formal permit request must be
submitted to the Division of Environmental Management accompanied by an application
fee, documentation from the parties involved, and other supporting materials as may be
appropriate. The approval of this request will be considered on its merits and may or may
not be approved.
4. Upon the availability of a municipal or regional sewerage collection system, the subject
wastewater treatment facilities shall be abandoned and all wastewater discharged into the
municipal or regional sewerage system.
5. The spray irrigation field shall be fenced with at least a two strand wire fence.
6. Failure to abide by the conditions and limitations contained in this permit may subject the
Permittee to an enforcement action by the Division of Environmental Management in
accordance with North Carolina General Statute 143-215.6(a) to 143-215.6(c).
7. The issuance of this permit does not preclude the Permittee from complying with any and
all statutes, rules, regulations, or ordinances which may be imposed by other government
agencies (local, state, and federal) which have jurisdiction.
8. This permit may be revoked if the Permittee fails to abide by the conditions of the
"Operation and Maintenance Agreement" previously signed by the Permittee.
9. A set of approved plans and specifications for the subject project must be retained by the
Permittee for the life of the project.
10. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its
extension. Upon receipt of the request, the Commission will review the adequacy of the
facilities described therein, and if warranted, will extend the Permit for such period of time
and under such conditions and limitations as it may deem appropriate.
Permit issued this the 15th day of June, 1995
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
A. Preston Howard, Jr., .E., Director
Division 6f Environmental Management
By Authority of the Environmental Management Commission
Permit Number WQ0004216
4
RATING SCALE FOR CLASSIFICATION OF WATER POLLUTION CONTROL SYSTEMS
Name of Facility:
]wner or Contact Person:
Mailing Address: R c ,4,e a 2,9
County: Jut& i Telephone:12ra
Present Classification: New Faclllty Existing Facility_ Se
NPDES Per. NCoo Nondisc. Per. No.W �o Health Dept.Per No.
Rated by: Z - Telephone; (2/0-277/-�Ed� Date; 3-?L-i-5—
Reviewed b . Health Dept. Telephone:
Regional Office Telephone: 7-��Od
Central Office Telephone:
ORC: Gra Tele hone:
Check Classification (s): Slabsuriace pray irrigation Land Application
Wastewater Classification: (Circle One) 1 11 111 tv Total Points:
SUBSURFACE CLkSStFIC–ATM
(check all units that apply)
1. septic tanks
2. pump tanks
3. siphon or pun dosing systems
4. sand filters
Ste_ grease traprinterceptor
6 _oil/water separalors
7. gravhy subsurface treatment and disposal:
8. pressure subsurface treatment and disposal
SPRAY FdVGATI N CL SStF)C'ATION
(&*ck all units that apply)
1. preliminary treatment (definition no. 32 )
lagoons
3septic tanks
4 pump tanks
s—l�pumps
a sand fihers
7. grease trapAntereeptor
8. o➢/waler s,eparalors
o. � dtsinfection
1G. chemical addition for rt rWent/algae control
14. -spray irrigation of wastewater
In addition to the above classifications, pretreatment of wastewater In excess of these components •hall
be rated using the point rating system and will require an operator wlth an appropriate dual certification.
LAN6APPLICATIONIRESIDUALS CLASSIFICATION (Applies only to permit holder)
1. Land application of bksolids, residuals or carttarninated lolls on ■ designated site.
WASTENATER TREATMENT T FACUTY CLASSiFICATtON
The following systems she be assigned a Class I dasslfic"on, Lznle55 ft flow k of a significara quanllty or the technology Is unusually
complex, to require consideration by ttw Commission on a case -by- ase basis: (Check if Appropriate)
S.-_ CHVwater Separator Systems consisting only of physics! separation, pumps and disposal;
2. r ptic Tank/Sand Fitter !Systems consisting wily of seplic tanks, doeirp eppara:us, pumpr.,sartd rfters, disinfection
and direct discharge;
3.Lagoon Systems o"Isting only of prerliminary treatment, lagoon:, pumps, cWnledion, neoessary chemical treatment for
algae or nutrient control, and direct discharge;
4.-- C4owd-scop Rtecyde Systems:
S` Groundwater Remediation Systems oonsWing only of olYwater ssparalors, pumps, air -gripping, carbon adsorption, disinfection
and dispos ;l;
s- Aquacunure operatlons with dusdwge to surface waters;
7�Waler Plant sludge handling and back -mash water treatment;
Il, Seadood processing comisti of screening and disposal.
D.Single-family discharging systems, with the exception of Aerobic Treatment Units, will be classified K permitted after July 1,
I M or If upon Inspection by the DMision, k Is found that the system Is not being adequately operated or mak tamed. Such
systems will be ratified of the classification or reclauIfication by the Commission, in writing.