HomeMy WebLinkAboutWQ0002737_Final Permit_20061211December 11, 2006
MATTHEW CORREGAN
5107 QUAIL HOLLOW ROAD
SANFORD, NC 27332
Dear Mr. Corregan:
Michael F. Easley, Governor
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Alan W, Klimek, P.E. Director
Division of Water Quality
Subject: Permit No. WQ0002737
Matthew Corregan SFR
Surface Irrigation Facility
Lee County
In accordance with your permit renewal application received August 25, 2006, we are forwarding
herewith Permit No. WQ0002737 dated December 11, 2006, to Matthew Corregan for the continued
operation of the subject single family wastewater treatment and surface irrigation facilities at 413 Willow
Creek Road, Sanford, NC.
This permit shall be effective from the date of issuance until November 30, 2011, shall void
Permit No. WQ0002737 issued January 30, 2003, and shall be subject to the conditions and limitations as
specified therein. Please pay particular attention to the monitoring requirements in this permit. Failure to
establish an adequate system for collecting and maintaining the required operational information will
result in future compliance problems. Note: Upon sale of this property, another change of ownership
request shall be submitted in accordance with Conditions V(3).
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of
this permit. This request must be in the form of a written petition, conforming to Chapter 150B of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service
Center, Raleigh, NC 27699-6714. Unless such demands are made this permit shall be final and binding.
If you need additional information concerning this matter, please contact Michael Rogers at (919)
715-6166.
Sincerely,
it" Alan W. Klimek, P. E.
CC' Orange County Health Department
Raleigh Regional Office - Aquifer Protection Section
Technical Assistance and Certification Unit
APS Central Files (WQ0002737)
LAU Files
North Carolina
J1laturA!!�
Aquifer Protection Section 1636 Mail Service Center Raleigh, NC 27699-1636 Phone (919) 733-3221 Customer Service
Internet: http://h2o.enr.state.nc.us 2728 Capital Boulevard Raleigh, NC 27604 Fax (919) 715-0588 l-877-623-6748
Fax (919)715-6048
An Equal Opportunity/Affirmative Action Employer— 50% Recycledll D% Post Consumer Paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
SINGLE FAMILY RESIDENCE SURFACE IRRIGATION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended., and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Matthew Corregan
Lee County
FOR THE
continued operation of a 480 GPD spray irrigation wastewater treatment and disposal system consisting
of a 1,000 baffled septic tank, a 396 square foot subsurface sand filter, a tablet chlorinator, two (2) 1,200
gallon storage tanks, a 1,000 gallon pump tank with a simplex 23 GPM submersible pump and high water
alarms, and a 30,000 square foot spray irrigation area to serve the Corregan residence, and all associated
piping and appurtenances with no discharge of wastes to the surface waters, pursuant to the application
received August 25, 2006, and in conformity with the project plan, specifications, and other supporting
data subsequently filed and approved by the Department of Environment and Natural Resources and
considered a part of this permit. This permit shall be effective from the date of issuance until November
30, 2011, shall void Permit No. WQ0002737 issued January 30, 2003, and shall be subject to the
following specified conditions and limitations:
1. PERFORMANCE STANDARDS
The surface irrigation facilities shall be effectively maintained and operated at all times so that
there is no discharge to surface waters, nor any contamination of ground waters, which will
render them unsatisfactory for normal use. In the event that the facilities fail to perform
satisfactorily, including the creation of nuisance conditions or failure of the irrigation area to
adequately assimilate the wastewater, the Permittee shall take inunediate corrective actions
including those actions that may be required by the Division of Water Quality, such as the
construction of additional or replacement wastewater treatment and disposal facilities.
2. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to
surface or ground waters resulting from the operation of this facility.
3. The residuals generated from these treatment facilities must be disposed in accordance with
General Statute 143-215.1 and in a manner approved by the Division.
4. Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited.
5. The following buffers shall be maintained:
a. 400 feet between wetted area and any residence or places of public assembly under separate
ownership,
b. 150 feet between wetted area and property lines,
c. 100 feet between wetted area and wells,
d. 100 feet between wetted area and drainage ways or surface water bodies,
e. 50 feet between wetted area and public right of ways,
f. 100 feet between treatment/storage units and any wells, and
g. 50 feet between treatment units and property lines.
Some of the buffers specified above may not have been included in previous permits for this
waste treatment and disposal system. These buffers are not intended to prohibit or prevent
modifications, which are required by the Division, to improve performance of the existing
treatment facility. These buffers do, however, apply to modifications of the treatment and
disposal facilities that are for the purpose of increasing the flow that is tributary to the facility.
These buffers do apply to any expansion or modification of the surface irrigation areas and
apply in instances in which the sale of property would cause any of the buffers now complied
with, for the treatment and disposal facilities, to be violated. The applicant is advised that any
modifications to the existing facilities will require a permit modification.
6. The pump tank(s) shall have functional audible and visual high water alarms that are external to
any structure.
II. OPERATION AND MAINTENANCE REQUIREMENTS
1. The facilities shall be properly maintained and operated at all times.
2. Upon classification of the wastewater treatment and surface irrigation facilities by the Water
Pollution Control System Operators Certification Commission (WPCSOCC), the Permittee
shall designate and employ a certified operator to be in responsible charge (ORC) and one or
more certified operator(s) to be back-up ORC(s) of the facilities in accordance with 15A NCAC
8G .0201. The ORC shall visit the facilities in accordance with 15A NCAC 8G .0204 or as
specified in this permit and shall comply with all other conditions specified in these rules.
3. A suitable year round vegetative cover shall be maintained
4. Irrigation shall not be performed during inclement weather or when the ground is in a condition
that will cause runoff,
5. Adequate measures shall be taken to prevent wastewater runoff from the irrigation field.
6. The application rate shall not exceed a cumulative loading of 31.2 inches over any twelve (12)
month period at an instantaneous application rate not to exceed 0.25 inches per hour.
7. The facilities shall be effectively maintained and operated as a non -discharge system to prevent
the discharge of any wastewater resulting from the operation of this facility.
8. No type of wastewater other than that from the Corregan residence (413 Willow Creek Road)
shall be sprayed onto the irrigation area.
9. No traffic or equipment shall be allowed on the disposal area except while installation occurs or
while normal maintenance is being performed.
10. The irrigation field shall be fenced with at least a two -strand wire fence.
11. Wastewater treatment units open to the atmosphere shall have restricted access and pump
control panels shall be locked.
12. The Permittee is responsible for the operation and maintenance of the entire treatment and
disposal system including, but not limited to, the following items:
2
a. The septic tank shall be checked annually and pumped out as needed. The septic tank
effluent filter shall be checked and cleaned at the same frequency of the septic tank.
b. The tablet chlorinator shall be checked every week. Tablets shall be added to provide
proper chlorination.
c. The storage, pump, and alarm systems shall be inspected monthly. The scum layer shall be
removed at the same interval as the septic tank is cleaned out.
d. The system shall be inspected monthly to make certain of the proper operation of the spray
heads, that the vegetative growth allows a proper spray pattern, that the soil is assimilating
the disposed treated wastewater with no surface runoff, and that no objectionable odors are
being generated.
III. MONITORING AND REPORTING REQUIREMENTS
1. Any monitoring deemed necessary by the Division to insure surface and ground water
protection will be established and an acceptable sampling reporting schedule shall be followed.
2. The Permittee shall maintain records of all maintenance performed on the system and irrigation
area, as required in Condition H(12) for a minimum of five years. This information shall be
provided to the Division upon request.
3. Noncompliance Notification:
The Permittee shall report by telephone to the Raleigh Regional Office, telephone number
(919) 791-4200, as soon as possible, but in no case more than 24 hours or on the next working
day following the occurrence or first knowledge of the occurrence of any of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility
incapable of adequate wastewater treatment, such as mechanical or electrical failures of
pumps, spray heads, etc.; or
b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to
receiving waters without treatment of all or any portion of the influent to such station or
facility.
Occurrences outside normal business hours may also be reported to the Division's Emergency
Response personnel at telephone number (800) 858-0368 or (919) 733-3300. Persons reporting
such occurrences by telephone shall also file a written report in letterform within five (5) days
following first knowledge of the occurrence. This report must outline the actions taken or
proposed to be taken to ensure that the problem does not recur.
IV. INSPECTIONS
1. Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to insure
proper operation of the subject facilities.
2. Any duly authorized officer, employee, or representative of the Division may, upon
presentation of credentials, enter and inspect any property, premises or place on or related to
the disposal site or facility at any reasonable time for the purpose of determining compliance
with this permit, may inspect or copy any records that must be maintained under the terms and
conditions of this permit, and may obtain samples of groundwater, surface water, or leachate.
V. GENERAL CONDITIONS
This permit shall become void unless the facilities are constructed in accordance with the
conditions of this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
This permit is not transferable. In the event there is a desire for the facilities to change
ownership, or there is a name change of the Permittee, a formal permit request must be
submitted to the Division accompanied by documentation from the parties involved, and other
supporting materials as may be appropriate. The approval of this request will be considered on
its merits and may or may not be approved.
4. Upon the availability of a municipal or regional sewerage collection system, the subject
wastewater treatment facilities shall be abandoned and all wastewater discharged into the
municipal or regional sewerage system.
Failure to abide by the conditions and limitations contained in this permit may subject the
Permittee to an enforcement action by the Division in accordance with North Carolina General
Statute 143-215.6A to 143-215.6C.
6. The issuance of this permit does not preclude the Permittee from complying with any and all
statutes, rules, regulations, or ordinances, which may be imposed by other government agencies
(local, state, and federal), which have jurisdiction.
7. This permit may be revoked if the Permittee fails to abide by the conditions of the "Operation
and Maintenance Agreement" previously signed by the Permittee.
8. The Permittee shall retain a set of approved plans and specifications of the subject facility for
the life of the project.
9. The Permittee shall pay the annual administering and compliance fee within 30 days of being
billed by the Division. Failure to pay the fee accordingly may cause the Division to initiate
action to revoke this permit as specified by 15A NCAC 2T .0105(e)(2).
10. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its
extension. Upon receipt of the request, the Commission will review the adequacy of the
facilities described therein, and if warranted, will extend the Permit for such period of time and
under such conditions and limitations, as it may deem appropriate.
Permit issued this the 1It' day of December 2006
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
J&C-- J,
S�&
Alan W. Klimek, P.E., Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0002737
4