HomeMy WebLinkAboutWQ0002161_Final Permit_19991103State of North Carolina
Department of Environment
and Natural Resources
Division of Water Quality
James B. Hunt, Jr., Governor
Bill Holman, Secretary
Kerr T. Stevens, Director
November 3, 1999
John McGovern, Assistant Principal
Carolina Friends School
4809 Friends School Road
Durham, N.C. 27705
Dear Mr. McGovern:
l � •
NCDENR
NORTH CAROLINA DEPARTMENT OF
ENVIRONMENT ANp NATURAL RESOURCES
Subject: Permit No. WQ0002161
Carolina Friends School
Wastewater Spray Irrigation
Orange County
In accordance with your application received April 8, 1999 we are forwarding herewith Permit No.
WQ0002161, dated November 3, 1999, to Carolina Friends School for the construction and operation of the
subject wastewater treatment and spray irrigation facilities.
This permit shall be effective from the date of issuance until January 31, 2002, shall void Permit No.
WQ0002161 issued February 13, 1997, and shall be subject to the conditions and limitations as specified
therein. Please pay particular attention to the monitoring requirements in this permit. Failure to establish an
adequate system for collecting and maintaining the required operational information will result in future
compliance problems. Please also note condition I.I. and condition 1.2, and condition 1.8 requiring
certification and notification of installation of the additional treatment units.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right
to request an adjudicatory hearing upon written request within thirty (30) days following receipt of this permit.
This request must be in the form of a written petition, conforming to Chapter 150B of the North Carolina
General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC
27699-6714. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this matter, please contact Sue Homewood at (91PV733-5083 extension 502.
l
rr T. Stevens
cc: Orange County Health Department
Civil Consultants Inc.
Raleigh Regional Office, Water Quality Section
Raleigh Regional Office, Groundwater Section
Groundwater Section, Central Office
Technical Assistance and Certification Unit
Non -Discharge Compliance/Enforcement Unit
1617 Mail Service Center, Raleigh, North Carolina 27699-1617 Telephone (919) 733-5083 Fax (919) 733-0719
An Equal Opportunity Affirmative Action Employer 50% recycled/10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
SPRAY IRRIGATION SYSTEM PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and
other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Carolina Friends School
Orange County
FOR THE
continued operation of a 4,000 GPD spray irrigation treatment and disposal facility consisting of a 1,000 gallon septic
tank, a 18 GPM pump station, 150 linear feet of 1.5 inch force main to collect wastewater from the shop, a 1,500
cr
gallon septic tank, a 22 GPM pump station with duplex pumps and 450 linear feet of 2 inch force main to collect
wastewater from the early school, teacher lounge, resource center, and library building, a 1,200 gallon septic tank.
1500 gallon storage tank (to be converted from an existing pump tank), and 500 linear feet of 2 inch force main
collect wastewater from the middle school, a 1000 gallon septic tank, a 18 GPM pump station and 100 linear feet of
1.5 inch force main to collect wastewater from the center building, a 55,903 gallon storage lagoon, a tablet chlorinator,
800 linear feet of 2.5 inch force main, a 66 GPM pump station with dual pumps and a 34,636 square feet irrigation
field, and
the construction and operation of a 2,000 gallon septic tank, a 23 GPM pump station with duplex pumps, and
approximately 20 linear feet of 2 inch force main to collect wastewater from a new multipurpose center, and all
associated valves piping, and appurtenances to serve the Carolina Friends School, with no discharge of wastes to the
surface waters, pursuant to the application received April 8, 1999 and in conformity with the project plan,
specifications, and other supporting data subsequently filed and approved by the Department of Environment and
Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until January 31, 2002, shall void Permit No.
WQ00021.61 issued February 13, 1997, and shall be subject to the following specified conditions and limitations:
I. PERFORMANCE STANDARDS
1. Upon completion of construction and prior to operation of the new facilities for the multipurpose center, a
certification must be received from a professional engineer certifying that the permitted units have been
installed in accordance with this permit, the approved plans and specifications, and other supporting
materials. Mail the Certification to the Non -Discharge Permitting Unit, Division of Water Quality, 1617
Mail Service Center, Raleigh, NC 27699-1617.
2. The Raleigh Regional Office, telephone number 919-571-4700 shall be notified at least forty-eight (48)
hours in advance of operation of the newly installed facilities so that an in -place inspection can be made.
Such notification to the regional supervisor shall be inade during the normal office hours from 8.00 a.m.
until 5:00 p.m. on Monday through Friday, excluding State Holidays.
3. The spray irrigation facilities shall be effectively maintained and operated at all times so that there is no
discharge to the surface waters, nor any contamination of ground waters which will render them
unsatisfactory for normal use. In the event that the facilities fail to perform satisfactorily, including the
creation of nuisance conditions or failure of the irrigation area to adequately assimilate the wastewater, the
Permittee shall take immediate corrective actions including those actions that may be required by the
Division of Water Quality (Division), such as the construction of additional or replacement wastewater
treatment and disposal facilities.
4. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to surface or
graundwaters resulting from the operation of this facility.
The residuals generated from these treatment facilities must be disposed in accordance with General
Statute 143-215.1 and in a manner approved by the Division.
Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited.
7. The following buffers shall be maintained:
a) 400 feet between wetted area and any residence or places of public assembly under separate
ownership,
b) 150 feet between wetted area and property lines,
c) 100 feet between wetted area and wells,
d) 100 feet between wetted area and drainageways or surface water bodies,
e) 50 feet between wetted area and public right of ways,
f) 100 feet between wastewater treatment units and wells, and
g) 50 feet between wastewater treatment units and property lines.
Some of the buffers specified above may not have been included in previous permits for this waste
treatment and disposal system. These buffers are not intended to prohibit or prevent modifications, which
are required by the Division, to improve performance of the existing treatment facility. These buffers do,
however, apply to modifications of the treatment and disposal facilities which are for the purpose of
increasing the flow that is tributary to the facility. These buffers do apply to any expansion or
modification of the spray irrigation areas and apply in instances in which the sale of property would cause
any of the buffers now complied with, for the treatment and, disposal facilities, to be violated. The
applicant is advised that any modifications to the existing facilities will require a permit modification.
8. A leakage test shall be performed on the new septic tank and new pump station to insure that any
exfiltration occurs at a rate which does not exceed twenty (20) gallons per twenty-four (24) hours per
1,000 gallons of tank capacity. The engineer's certification will serve as proof of compliance with this
condition.
H. OPERATION AND MAINTENANCE REQUIREMENTS
1. The facilities shall be properly maintained and operated at all times.
2. Upon classification of the facility by the Water Pollution Control System Operators Certification
Commission (WPCSOCC), the Permittee shall employ a certified wastewater treatment plant operator to
be in responsible charge (ORC) of the wastewater treatment facilities. The operator must hold a certifica
of the type and grade at least equivalent to or greater than the classification assigned to the wastewater
treatment facilities by the WPCSOCC. The Perrnittee must also employ a certified back-up operator of the
appropriate type and grade to comply with the conditions of 15A NCAC 80 .0202. The ORC of the
facility must visit each Class I facility at least weekly and each Class II, III, and IV facility at least daily,
excluding weekends and holidays, and must properly manage and document daily operation and
maintenance of the facility and must comply with all other conditions of 15A NCAC 8G .0202.
3. A suitable year round vegetative cover shall be maintained.
4. Irrigation shall not be performed during inclement weather or when the ground is in a condition that will
cause runoff.
5. Adequate measures shall be taken to prevent wastewater runoff from the spray field
6. The facilities shall be effectively maintained and operated as a non -discharge system to prevent the
discharge of any wastewater resulting from the operation of this facility_
7. The application rate shall not exceed a cumulative loading of 52 inches over any twelve (12) month period
at an instantaneous application rate not to exceed 0.25 'inches per hour.
8. No type of wastewater other than that from Carolina Friends School shall be sprayed onto the irrigation
area.
9. No traffic or equipment shall be allowed on the disposal area except while installation occurs or whi'
normal maintenance is being performed.
10. Public access to the land application sites shall be controlled during active site use. Such controls may
include the posting of signs showing the activities being conducted at each site.
III. MONITORING AND REPORTING RE UIREMENTS
Any monitoring (including groundwater, surface water, soil or plant tissue analyses) deemed necessary by
the Division to insure surface and ground water protection will be established and an acceptable sampling
reporting schedule shall be followed.
2. Adequate records shall be maintained by the Permittee tracking the amount of wastewater disposed. These
records shall include, but are not necessarily limited to, the following information.
a. date of irrigation,
b. volume of wastewater irrigated,
c. field irrigated,
d. length of time field is irrigated,
e. continuous weekly, monthly, and year-to-date hydraulic (inches/acre) loadings for each field,
f. weather conditions, and
g. maintenance of cover crops.
3. Three (3) copies of all operation and disposal records (as specified in condition 111 2) on Form NDAR-1
shall be submitted on or before the last day of the following month. All information shall be submitted to
the following address:
NC Division of Water Quality
Water Quality Section
Non -Discharge Compliance/Enforcement Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
4. Noncompliance Notification:
The Permittee shall report by telephone to the )4W Regional Office, telephone number Yyyy, as soon as
possible, but in no case more than 24 hours or on the next working day following the occurrence or first
knowledge of the occurrence of any of the following:
a. Any occurrence at the wastewater treatment facility which results in the treatment of significant
amounts of wastes which are abnormal in quantity or characteristic, such as the dumping of the
contents of a sludge digester; the known passage of a slug of hazardous substance through the facility;
or any other unusual circumstances.
b. Any process unit failure, due to known or unknown reasons, that render the facility incapable of
adequate wastewater treatment such as mechanical or electrical failures of pumps, aerators,
compressors, etc.
c. Any failure of a pumping station, sewer line, or treatment facility resulting in a by-pass directly to
receiving waters without treatment of all or any portion of the influent to such station or facility.
d. Any time that self -monitoring information indicates that the facility has gone out of compliance with
its permit limitations.
Persons reporting such occurrences by telephone shall also file a written report in letter form within five
(5) days following first knowledge of the occurrence. This report must outline the actions taken or
proposed to be taken to ensure that the problem does not recur.
IV. GROUNDWATER REQUIREMENTS
1. Any additional groundwater quality monitoring, as deemed necessary by the Division, shall be provided
2. The COMPLIANCE BOUNDARY for the disposal system is specified by regulations in 15A NCAC 2L,
Groundwater Classifications and Standards. The Compliance Boundary is for the disposal system
constructed after December 31, 1983 is established at either (1) 250 feet from the waste disposal area, or
(2) 50 feet within the property boundary, whichever is closest to the waste disposal area. An exceedance
of Groundwater Quality Standards at or beyond the Compliance Boundary is subject to immediate
remediation action in addition to the penalty provisions applicable under General Statute 143-
215.6A(a)(1).
In accordance with 15A NCAC 2L, a REVIEW BOUNDARY is established around the disposal systems
midway between the Compliance Boundary and the perimeter of the waste disposal area. Any exceedance
of standards at the Review Boundary shall require remediation action on the part of the permittee.
4
V. INSPECTIONS
Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to insure prop
operation of the subject facilities.
2. The Permittee or his designee shall inspect the wastewater treatment and disposal facilities to prevent
malfunctions and deterioration, operator errors and discharges which may cause or lead to the release of
wastes to the environment, a threat to human health, or a nuisance. The Permittee shall keep an inspection
log or summary including at least the date and time of inspection, observations made, and any
maintenance, repairs, or corrective actions taken by the Permittee. This log of inspections shall be
maintained by the Permittee for a period of three years from the date of the inspection and shall be made
available upon request to the Division or other permitting authority.
3. Any duly authorized officer, employee, or representative of the Division may, upon presentation of
credentials, enter and inspect any property, premises or place on or related to the disposal site or facility at
any reasonable time for the purpose of determining compliance with this permit; may inspect or copy any
records that must be maintained under the terms and conditions of this permit, and may obtain samples of
groundwater, surface water, or leachate.
VI. GENERAL CONDITIONS
This permit shall become voidable unless the facilities are constructed in accordance with the conditions of
this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the application
and other supporting data.
This permit is not transferable. In the event there is a desire for the facilities to change ownership, or there
is a name change of the Permittee, a formal permit request must be submitted to the Division accompanied
by an application fee, documentation from the parties involved, and other supporting materials as may be
appropriate. The approval of this request will be considered on its merits and may or may not be
approved.
4. Failure to abide by the conditions and limitations contained in this permit may subject the Permittee to an
enforcement action by the Division in accordance with North Carolina General Statute 143-215.6A to 143-
215.6C.
5. The issuance of this permit does not preclude the Permittee from complying with any and all statutes,
rules, regulations, or ordinances which may be imposed by other government agencies (local, state, and
federal) which have jurisdiction.
6. A set of approved plans and specifications for the subject project must be retained by the Permittee for the
life of the project.
7. The annual administering and compliance fee must be paid by the Permittee within thirty (30) days after
being billed by the Division. Failure to pay the fee accordingly may cause the Division to initiate action to
revoke this permit as specified by 15A NCAC 2H .0205 (c)(4).
W
The Permittee, at least six (6) months prior to the expiration of this permit, shall request its extension.
Upon receipt of the request, the Commission will review the adequacy of the facilities described therein,
and if warranted, will extend the permit for such period of time and under such conditions and limitations
as it may deem appropriate.
Permit issued this they, 3' day of November 1999
NORTH
AL MANAGEMENT COMMISSION
-%:�Xerr T. Stevens, Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0002161
Permit No. WQ0002161
November 3, 1999
Construction of wastewater collection system for new Multipurpose Center
ENGINEER'S CERTIFICATION
Partial Final
as a duly rein
gistered Professional Engineer in the State of North
Carolina, having been authorized to observe (periodically, weekly, full time) the construction of the project,
Project Name
Location and County
for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the
construction such that the construction was observed to be built within substantial compliance and intent of this permit,
the approved plans and specifications, and other supporting materials.
Signature
Date
Registration No.
WATER POLLUTION CONTROL SYSTEM OPERATORS
CERTIFICATION COMMISSION
CLASSIFICATION
RATING SHEET FOR WATER POLLUTION CONTROL SYSTEMS
FACILITY INFORMATION:
NAME OF FACILITY: Carolina Friends School
MAILING ADDRESS: 4809 Friends School Road, Durham, NC 27705
COUNTY: Orange
CONTACT PERSON: John McGovern TELEPHONE: 919/383-6602
PERMIT NO.: WQ0002161 Check One: NC WQ ✓ HEALTH DP
ORC: Richard Davis TELEPHONE:
RATING INFORMATION: (Before completing this section, please refer to pages 2-4)
PERMITTED FLOW: 0.004 MGD BNR? YES NO
CHECK CLASSIFICATION: WASTEWATER: 1 2 3 4
COLLECTION: 1 2 3 4
SPRAY IRRIGATION ✓ SUBSURFACE LAND APPLICATION
PHYSICAL/CHEMICAL GRADE I GRADER
RATED BY: Randv Jon REGION: RRO DATE: 7/2/99
REGIONAL OFFICE TELEPHONE NUMBER: 919/571-4700 EXT: 249
Permit No.: WQ0002161
Page 1
CIassification of Biological Water Pollution Control Treatment Systems:
Grade I Biological WPCS
- Septic tank/sand filter systems
-Biological lagoon systems
- Constructed wetlands and associated appurtenances
Grade II Biological WPCS
- Systems that utilize an activated sludge or fixed growth process with a permitted flow
less than or equal to 0.5 million gallons per day (mgd)
Grade III Biological WPCS
- Systems that utilize an activated sludge or fixed growth process with a permitted now
of greater than 0.5 through 2.5 million gallons per day (mgd)
- Grade II systems that are required to achieve biological nutrient reduction
Grade IV Biological WKS
- Systems that utilize an activated sludge or fixed growth process with a permitted flow
of greater then 2.5 million gallons per day (mgd)
- Grade III systems that are required to achieve biological nutrient reduction
Biological Nutrient Reduction -
ne reduction of total nitrogen or total phosphorus by an activated sludge or fixed growth
process as required by the facilities permit.
Classification of Collection Water Pollution Control Systems:
(whichever provides lowest grade)
Same grade as biological water pollution control system. Grade of system: flflflfl
Based on population served:
1,500 or Less = Grade I
1,501 to 15,000 = Grade II
15,001 to 50,000 = Grade III
50,001 or more = Grade IV
Permit No.: WQ0002161
Page 2
Classification of Spray Irrigation Water Pollution Control Systems:
✓ Systems which utilize spray irrigation for the reuse or disposal of wastewater.
These systems include: septic tanks, sand filter, oil/water separators, Iagoons,
storage basins, screening, sedimentation. Systems other than those listed above
shall be subject to additional classification.
Classification of Land Application of Residuals Systems:
Systems permitted and dedicated for the land application of residuals that are produced by
a water pollution control system or contaminated soils.
..............................................................................................................................................................
Classification of Physical/Chemical Water Pollution Control Treatment Systems:
Grade I Physical/Chemical: Any water pollution control system that utilizes a primarily
physical process to treat wastewater. This classification includes groundwater remediation
systems **
Grade H Physical/Chemical: Any water pollution control system that utilizes a primarily
chemical process to treat wastewater. This classification includes reverse osmosis,
electrodialysis, and ultrafiltration systems. **
* *Any water pollution control system that utilizes a physical/chemical process to enhance an
activated sludge or fixed growth process, shall not be subject to additional classification
Classification of Subsurface Water Pollution Control Systems:
Systems which utilize the soil for subsurface treatment and disposal of wastewater
And/or are required to have a certified operator under 15A NCAC I SA. 1961. ***
*** Any subsurface system that has as part of its treatment process a water pollution control
system that may be classified under Rules .0302 through .0307 of this section shall be
subject to additional classification.
Permit No.: WQ0002161
Page 3