HomeMy WebLinkAboutWQ0002125_Final Permit_20081206Q�0� W r�RQG Michael F. Easley, Governor
William G. Ross Jr,, Secretary
f' North Carolina Department of Environment and Natural Resources
C oleenDivision
H. Sullins, Director
Division of Water Quality
December 6, 2008
LOUIS AND ANDREA QUINN
8409 FARRINGTON MILL ROAD '
CHAPEL HILL, NC 27517
Subject: Permit No. WQ0002125
Louis and Andrea Quinn SFR
Surface Spray Irrigation Facility
Durham County
Dear Mr. and Mrs. Quinn:
In accordance with your application received October 2, 2008, we are forwarding herewith Permit
No. WQ0002125 dated December 6, 2008, to Louis and Andrea Quinn for the continued operation of the
subject single-family wastewater treatment and spray irrigation facilities.
This permit shall be effective from the date of issuance until November 30, 2013, shall void Permit
No. WQ0002125 issued April 29, 2004, and shall be subject to the conditions and limitations as specified
therein. Please pay particular attention to the monitoring requirements in this permit. Failure to establish an
adequate system for collecting and maintaining the required operational information will result in future
compliance problems. Note: Upon sale of this property, another change of ownership request shall be
submitted in accordance with Condition V, 3.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of this
permit. This request must be in the form of a written petition, conforming to Chapter 150B of the North
Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center,
Raleigh, NC 27699-6714. Unless such demands are made this permit shall be final and binding.
If you need additional information concerning this matter, please contact Michael Rogers at (919)
715-6166.
Sincerely,
4
Coleen H. Sullins, Director
cc: Durham County Environmental Health Department
Raleigh Regional Office, Aquifer Protection Section
Technical Assistance and Certification Unit
LAU Files
APS Central Files
o `
NhCarolina
Aquifer Protection Section 1636 Mail Service Center Raleigh, NC 27699-1636 Phone (919) 733-3221 Customer Service
Internet: http:1lh2o.enr.state.nc.us 2728 Capital Boulevard Raleigh, NC 27604 Fax (919) 715-0588 1-877-623-6748
Fax (919)715-6048
An Equal OpportunitylAffirma5ve Action Employer— 50% Recycled/10% Post Consumer Paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
IM41a01["on
SINGLE FAMILY SPRAY IRRIGATION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and
other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Louis and Andrea Quinn
Durham County
FOR THE
continued operation of a 450 gallon per day (GPD) spray irrigation wastewater treatment and disposal system
consisting of a 1,200 gallon baffled septic tank, a distribution box, a 150 f12 surface sand filter, a tablet chlorinator,
an irrigation pump station with a 23.5 GPM pump, multiple storage tanks with a 2,400 gallon capacity,
approximately 420 linear feet of 1.5-inch force main, approximately 15,000 f 2 of spray irrigation area, and all
associated valves, piping, sprinklers and appurtenances with no discharge of wastes to the surface waters to serve
the Louis and Andrea Quinn residence (8409 Farrington Mill Road), pursuant to the application received October 2,
2008, and in conformity with the project plan, specifications, and other supporting data subsequently filed and
approved by the Department of Environment and Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until November 30, 2013, shall void Permit No.
WQ0002125 issued April 29, 2004, and shall be subject to the following specified conditions and limitations:
1. PERFORMANCE STANDARDS
The surface irrigation facilities shall be effectively maintained and operated at all times so that there is
no discharge to the surface waters, nor any contamination of ground waters, which will render them
unsatisfactory for normal use. In the event that the facilities fail to perform satisfactorily, including the
creation of nuisance conditions or failure of the irrigation area to adequately assimilate the wastewater,
the Permittee shall take immediate corrective actions including those actions that may be required by
the Division of Water Quality (Division), such as the construction of additional or replacement
wastewater treatment and disposal facilities.
2. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to surface
or ground waters resulting from the operation of this facility.
3. The sand media of the subsurface sand filter must comply with the Division's sand specifications.
4. The residuals generated from these treatment facilities must be disposed in accordance with General
Statute 143-215.1 and in a manner approved by the Division.
Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited.
WQ0002125 Page 2
6. The following buffers shall be maintained;
a. 400 feet between wetted area and any residence or places of public assembly under separate
. ownership,
b. 150 feet between wetted area and property lines,
c. 100 feet between wetted area and wells,
d. 100 feet between wetted area and drainage ways or surface water bodies,
e. 100 feet between wetted area and any swimming pools,
f 50 feet between wetted area and public right of ways,
g. 100 feet between treatment/storage units and any wells, and
h. 50 feet between treatment units and property lthes.
Some of the buffers specified above may not have been included in previous permits for this waste
treatment and disposal system. These buffers are not intended to prohibit or prevent modifications,
which are required by the Division, to improve performance of the existing treatment facility. These
buffers do, however, apply to modifications of the treatment and disposal facilities that are for the
purpose of increasing the flow that is tributary to the facility. These buffers do apply to any expansion
or modification of the surface irrigation areas and apply in instances in which the sale of property
would cause any of the buffers now complied with, for the treatment and disposal facilities, to be
violated. The applicant is advised that any modifications to the existing facilities will require a permit
modification.
7. The pump tank(s) shall have functional audible and visual high water alarms that are external to any
structure.
H. OPERATION AND MAINTENANCE RE UMEMENTS
1. The facilities shall be properly maintained and operated at all times
2. Upon classification of the wastewater treatment and spray irrigation facilities by the Water Pollution
Control System Operators Certification Commission (WPCSOCC), the Permittee shall designate and
employ a certified operator to be in responsible charge (ORC) and one or more certified operator(s) to
be back-up ORC(s) of the facilities in accordance with 15A NCAC 8G .0201. The ORC shall visit the
facilities in accordance with 15A NCAC 8G .0204 or as specified in this permit and shall comply with
all other conditions specified in these rules.
A suitable year round vegetative cover shall be maintained (or leaf litter in wooded areas).
4. Irrigation shall not be performed during inclement weather or when the ground is in a condition that
will cause runoff.
Adequate measures shall be taken to prevent wastewater runoff from the spray field.
6. The application rate shall not exceed a cumulative loading of 17.57 inches over any twelve (12) month
period at an instantaneous application rate so as not to cause ponding or runoff,
The facilities shall be effectively maintained and operated as a non -discharge system to prevent the
discharge of any wastewater resulting from the operation of this facility.
No type of wastewater other than that from the Quinn Residence (8409 Farrington Mill Road) shall be
sprayed onto the irrigation area.
9. No traffic or equipment shall be allowed on the disposal area except while installation occurs or while
normal maintenance is being performed.
10. The spray irrigation field shall be fenced with at least a two -strand wire fence.
WQ0002125 Page 3
11. Wastewater treatment units open to the atmosphere shall have restricted access and pump control
panels shall be locked.
12. The Permittee is responsible for the operation and maintenance of the entire treatment and disposal
system including, but not limited to, the following items:
a. The septic tank shall be checked annually and pumped out as needed.
b. The tablet chlorinator shall be checked every week. Tablets shall be added to provide proper
chlorination.
c. The stotage, pump, and alarm systems shall be inspected monthly. The scum layer shall be
removed at the same interval as the septic tank is cleaned out.
d. The system shall be inspected monthly to make certain of the proper operation of the spray head,
that the vegetative growth allows a proper spray pattern, that the soil is assimilating the disposed
treated wastewater with no surface runoff, and that no objectionable odors are being generated.
III. MONITORING AND REPORTING RE UUREMENTS
Any monitoring deemed necessary by the Division to insure surface and ground water protection will
be established and an acceptable sampling reporting schedule shall be followed.
2. The Permittee shall maintain records of all maintenance performed on the system and irrigation area, as
required in Condition U, 11 for a minimum of five years. This information shall be provided to the
Division upon request.
Noncompliance Notification:
The Permittee shall report by telephone to the Raleigh Regional Office, telephone number (919) 571-
4700, as soon as possible, but in no case more than 24 hours or on the next working day following the
occurrence or first knowledge of the occurrence of any of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of
adequate wastewater treatment, such as mechanical or electrical failures of pumps, spray heads,
etc.; or
b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to receiving
waters without treatment of all or any portion of the influent to such station or facility.
Persons reporting such occurrences by telephone shall also file a written report in letter form within
five (5) days following first knowledge of the occurrence. This report must outline the actions taken or
proposed to be taken to ensure that the problem does not recur.
IV. INSPECTIONS
Adequate inspection, maintenance, and cleaning shall be provided by the Permittec to insure proper
operation of the subject facilities.
Any duly authorized officer, employee, or representative of the Division may, upon presentation of
credentials, enter and inspect any property, premises or place on or related to the disposal site or
facility at any reasonable time for the purpose of determining compliance with this permit, may inspect
or copy any records that must be maintained under the terms and conditions of this permit, and may
obtain samples of groundwater, surface water, or leachate.
WQ0002125 Page 4
V. GENERAL CONDITIONS
This permit shall become void unless the facilities are constructed in accordance with the conditions of
this permit, the approved plans and specifications, and other supporting data.
2.. This permit is effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
3. This permit is not transferable. In the event there is a desire for the facilities to change ownership, or
there is a name change of the Permittee, a formal permit request must be submitted to the Division
accompanied by documentation from the parties involved, and other supporting materials as may be
appropriate. The approval of this request will be considered on its merits and may or may not be `
approved.
4. Upon the availability of a municipal or regional sewerage collection system, the subject wastewater
treatment facilities shall be abandoned and all wastewater discharged into the municipal or regional
sewerage system.
5. Failure to abide by the conditions and limitations contained in this permit may subject the Permittee to
an enforcement action by the Division in accordance with North Carolina General Statute 143-215.6A
to 143-215.6C.
6. The issuance of this permit does not preclude the Permittee from complying with any and all statutes,
rules, regulations, or ordinances, which may be imposed by other government agencies (local, state,
and federal), which have jurisdiction.
7. This permit may be revoked if the Permittee fails to abide by the conditions of the "Operation and
Maintenance Agreement" previously signed by the Permittee.
8. A set of approved plans and specifications for the subject project must be retained by the Permittee for
the life of the project.
9. The annual administering and compliance fee must be paid by the Permittee within 30 days after being
billed by the Division. Failure to pay the fee accordingly may cause the Division to initiate action to
revoke this permit as specified by 15A NCAC 2T .0105(e)(2).
10. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its extension.
Upon receipt of the request, the Commission will review the adequacy of the facilities described
therein, and if warranted, will extend the Permit for such period of time and under such conditions and
limitations as it may deem. appropriate.
Permit issued this the 6'1' day of December 2008
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
lI',
�&A � 4i
-
oleen H. Sullins, Director
Division of Water Quality
13y Authority of the Environmental Management Commission
Permit Number WQ0002125
WQ0002125 Page 5
OPERATION AND MAINTENANCE AGREEMENT
SINGLE FAMILY RESIDENCE SURFACE IRRIGATION SYSTEM
DIVISION OF WATER QUALITY
o
Property Owner(s) (as appearing on the property deed):
Mailing Address: �"rrr d otl6ii122
Facility Address (if different :,a'
oveDisposal Method; c )°BT IRRIGATION o DRIP IRRIGATION (Check One)
County: rCJ 4 Permit No.
I/We agree to operate and maintain the wastewater treatment system as follows:
1. The Permittee is responsible for the operation and maintenance of the entire treatment and disposal
system including, but not limited to, the following items:
a, The septic tank shall be checked annually and pumped out as needed. The effluent filter shall be
checked and cleaned at the same frequency of the septic tank,
b. The sand filter surface shall be raked and leveled every six (b ) months and any vegetative growth
shall be removed by hand [accessible sand filters only}.
-a c. Check one:
J
o The tablet chlorinator shall be checked every week. Tablets shall be added so as to provide
proper chlorination.
o The ultraviolet disinfection unit shall be checked every week. The lamp shall be cleaned
=` C\J and/or replaced to ensure proper disinfection.
The storage, pump, and alarm systems shall be inspected monthly. The scum layer shall be
aD removed at the same time interval as the septic tank is pumped out.
e. The irrigation system shall be inspected monthly to make certain of proper operation, that
vegetative growth does not interfere with the system inspection or operation, that the soil is
assimilating the disposed treated wastewater with no surface runoff, and that no objectionable
odors are being generated.
2. Failure of the Permittee to properly operate this system is subject to a penalty up to S25,000 per day,
3. Failure to meet the permit conditions or violation of the State's surface or groundwater regulations
will require evacuating the dwelling and may void the permit.
NOTE: All persons (owners) appearing on the legally registered property deed must sign this O&M
Agreement
IIWe understand the abov��ir .ements and agre�.,to these terms as part of the issued permit.
, ep,
Owner(s) Signatizre(s). f"- Date:
() gn () Date: �Zt,2 _,Z
Owners Si ature s
SFR O&M (version 07107 )