September 7, 2018
Ms. Tara Hamlin
Pavillon International
P.O. Box 189
Mill Springs, NC 28756-0189
Subject: Minor modification of NPDES Permit NC0085294
Britten Creek WWTP
Polk County
Grade II Biological WPCS
Dear Ms. Hamlin:
The Division has received and reviewed your request to modify the subject permit. The
Division does not object to your request. This modification is issued pursuant to the requirements of
North Carolina General Statute 143-215.1 and the Memorandum of Agreement between North
Carolina and the U.S. Environmental Protection Agency dated October 15, 2007 (or as subsequently
amended). Insert the attached pages into your permit and discard the old pages.
This modified permit includes the following changes from your current permit:
> The facility component list has been updated.
> Monitoring frequencies have been updated in Section A. (1.) for all parameters except
Ammonia Nitrogen, due to the current facility classification per 15A NCAC 02B .0508.
If any parts, measurement frequencies or sampling requirements contained in this
modification are unacceptable to you, you have the right to an adjudicatory hearing upon written
request within thirty (30) days following receipt of this letter. This request must be in the form of a
written petition, conforming to Chapter 150B of the North Carolina General Statutes, and filed with
the Office of Administrative Hearings (6714 Mail Service Center, Raleigh, North Carolina 27699-6714).
Unless such demand is made, this decision shall be final and binding.
This permit is not transferable except after notice to the Division. The Division may require
modification or revocation and reissuance of the permit. This permit does not affect the legal
requirements to obtain other permits which may be required by any other Federal, State, or Local
- governmental regulation. If you have any questions concerning this matter, please contact Emily
Phillips at (919) 707-3621 or via e-mail [emily.phillips@ncdenr.gov].
erely,
iftziflirt ,
F
Linda Culpepper
Interim Director, Division of Water Resources
cc: Central Files
NPDES Unit
State of North Carolina I Environmental Quality I Water Resources
1617 Mail Service Center I Raleigh,NC 27699-1617
919 807 6300 919-807-6389 FAX
haps://deq.nc.gov/about/divisions/water-resources/water-resources-permits/wastewater-branch/npdes-wastewater-permits
Permit NC0085294
Grade II Biological Water Pollution Control System [15A NCAAC 08G .0302]
Part I.
A. (1.) EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
[15A NCAC 02B .0400 et seq., 02B .0500 et seq.]
During the period beginning on the effective date of this permit and lasting until
expiration, the Permittee is authorized to discharge from outfall 001. Such discharges shall
be limited and monitored2 by the Permittee as specified below:
EFFLUENT CHARACTERISTICS
LIMITS MONITORING REQUIREMENTS -
- s ' - Monthly Daily , Measurement Sample Sample
Parameter Code - . . Average- Maximum Frequency Type Location
Flow 0.00586 MGD Weekly Instantaneous Influent or Effluent
50050
BOD, 5-day(20°C) 30.0 mg/L 45.0 mg/L Weekly Grab Effluent
C0310
Total Suspended Solids 30.0 mg/L 45.0 mg/L Weekly Grab Effluent
C0530 ,
NH3 as N Monthly Grab ' Effluent
C0
C0610
Fecal Coliform(geometric mean) 200/100 ml 400/100 ml Weekly Grab Effluent
31616
Total Residual Chlorine(TRC) 28 pg/L Weekly Grab Effluent
50060
Temperature(°C)
00010 Weekly Grab Effluent
pH Not<6.O nor>9.0
00400 Standard Units Weekly Grab Effluent
Footnote:
1. The Division shall consider all effluent TRC values reported below 50 µg/L to be in compliance with
the permit. However, the Permittee shall continue to record and submit all values reported by a
North Carolina certified laboratory (including field certified), even if these values fall below 50 µg/L.
2. The Permittee shall submit discharge monitoring reports electronically using the Division's eDMR
system [see A. (3.)].
THERE SHALL BE NO DISCHARGE OF FLOATING SOLIDS OR VISIBLE FOAM IN OTHER THAN
TRACE AMOUNTS.
Page 3 of 6