Loading...
HomeMy WebLinkAboutNC0037371_Inspection_20180912United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 15 I 3 I NCO037371 111 12 I 18/08/31 I17 18 I S i 19 LG] i 201 I 211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166 Inspection Work Days Facility Self-Monitoring Evaluation Rating 131 QA ----------------------Reserved------------------- 67 2.0 70 71 I.. I 72 I �, I 73 �74 751 I I I 1 1 1 I80 u Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES oermit Number) 11:05AM 18/08/31 14/06/01 North Iredell High School 156 Raider Rd Exit Time/Date Permit Expiration Date Olin NC 28660 12:35PM 18/08/31 19/03/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Dennis W Murdock/ORC/828-238-4659/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Kenny Miller,350 Old Murdock Rd Troutman NC 281669699//704-873-3755/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date EDoby: 9/12/2018 Wes Bell �� 24& MRO WQ//704-663-1699 Ext.2192/ A:6)96D90CC343T Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. DocuSigned by: -- 9/12/2018 AtaccsatAi=vazs... Page# NPDES yr/mo/day Inspection Type NC0037371 111 121 18/08/31 1 17 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) On-site Representatives: The following personnel were in attendance during the inspection: Mr. Mathew Costner/lredell-Statesville Schools; Mr. Chris Bitterman/Envirolink; Mr. Chip White/Envirolink; and Mr. Dennis Murdock/Envirolink. Page# Permit: NCO037371 Owner - Facility: North Iredell High School Inspection Date: 08/31/2018 Inspection Type: Compliance Evaluation Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? ❑ ❑ ❑ 0 Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ 0 ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: The last compliance evaluation inspection was performed at the facility on 2/1/18 by DWR staff. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ❑ ❑ ❑ 0 Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift? Is the ORC visitation log available and current? ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑ Page# 3 Permit: NCO037371 Inspection Date: 08/31/2018 Record Keeping Owner - Facility: North Iredell High School Inspection Type: Compliance Evaluation Yes No NA NE Comment: The records reviewed durina the inspection were oraanized and well maintained. Discharae Monitoring Reports (eDMRs) were reviewed for the period November 2017 through June 2018. Daily maximum effluent fecal coliform and TSS violations were reported in March 2018 (fecal coliform) and April 2018 (TSS). The Division has separately addressed these limit violations through the issuances of Notice of Violations (NOVs). No effluent total nitrogen and total phosphorus sampling was performed during the first quarter of 2018. This inspection report will address these monitoring violations. No indication of the ORC and/or Backup ORC being onsite was reported on the May 2018 edmr for the week of 5/20/18 and 5/29/18 — 5/30/18. A revised May 2018 edmr should be resubmitted to include this information. Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? ❑ ❑ 0 ❑ Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: On-site field analvses (DH. total residual chlorine. temDerature) are beina Derformed under Envirolink's field laboratory certification #5212. Statesville Analytical, Inc. (all effluent parameters except field) has also been contracted to provide analytical support. The ORC was not performing post -analysis calibration checks on the pH and total residual chlorine meters following field analyses at multiple sites. Post -analysis calibration checks must be performed in accordance with the NC Wastewater/Groundwater laboratory certification approved procedures for the analyses of dissolved oxygen, PH, and total residual chlorine. Note: The technical guidance documents developed by the Division's Laboratory Certification Unit detailing these approved laboratory procedures have been emailed to Envirolink's Field SUDervisor. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: The subject permit requires effluent grab samples. Page# 4 Permit: NCO037371 Owner - Facility: North Iredell High School Inspection Date: 08/31/2018 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The wastewater treatment facility appeared to be properly operated and well maintained. Yes No NA NE Is the basin aerated? Process control measurements were being performed and documented. ❑ ❑ The facility is equipped with a telemetry type alarm system to notify staff of selected alarm ❑ ❑ conditions. Is the basin free of excessive grease? 0 ❑ Bar Screens Yes No NA NE Type of bar screen 0 ❑ ❑ a.Manual Are all pumps operable? 0 ❑ b.Mechanical ❑ Are float controls operable? 0 Are the bars adequately screening debris? 0 ❑ ❑ ❑ Is the screen free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screening in compliance? 0 ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: Screenings are disposed at the County Landfill by a contracted company (Benfield Sanitation Services). Equalization Basins Yes No NA NE Is the basin aerated? 0 ❑ ❑ ❑ Is the basin free of bypass lines or structures to the natural environment? 0 ❑ ❑ ❑ Is the basin free of excessive grease? 0 ❑ ❑ ❑ Are all pumps present? 0 ❑ ❑ ❑ Are all pumps operable? 0 ❑ ❑ ❑ Are float controls operable? 0 ❑ ❑ ❑ Are audible and visual alarms operable? 0 ❑ ❑ ❑ # Is basin size/volume adequate? 0 ❑ ❑ ❑ Comment: Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? 0 ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ 0 ❑ Page# 5 Permit: NCO037371 Inspection Date: 08/31/2018 Owner - Facility: North Iredell High School Inspection Type: Compliance Evaluation Is the clarifier free of black and odorous wastewater? 0 ❑ Aeration Basins Yes No NA NE Are the diffusers operational? 0 ❑ ❑ ❑ Is the foam the proper color for the treatment process? 0 ❑ ❑ ❑ Does the foam cover less than 25% of the basin's surface? 0 ❑ ❑ ❑ Is the DO level acceptable? 0 ❑ ❑ ❑ Is the DO level acceptable?(1.0 to 3.0 mg/1) ❑ ❑ 0 ❑ Comment: The 30 -minute settleabilitv test Derformed durina the inspection was aDDroximately 350 ml/L with a clear supernate. The aeration basin dissolved oxygen levels were low (<1.0 mg/L); however, the wastewater appeared to be adequately treated. The ORC must ensure adequate dissolved oxygen levels are maintained in the aeration basin at all times. The Soda ash is added on an as -needed basis to maintain appropriate alkalinity/PH levels. Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? 0 ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ 0 ❑ Are weirs level? 0 ❑ ❑ ❑ Is the site free of weir blockage? 0 ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? 0 ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? ❑ ❑ 0 ❑ Is the return rate acceptable (low turbulence)? 0 ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc? 0 ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/ of the sidewall depth) 0 ❑ ❑ ❑ Comment: Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? 0 ❑ ❑ ❑ Number of tubes in use? 4 Is the level of chlorine residual acceptable? 0 ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? 0 ❑ ❑ ❑ Comment: Page# 6 Permit: NC0037371 Owner - Facility: Inspection Date: 08/31/2018 Inspection Type: North Iredell High School Compliance Evaluation # Is flow meter used for reporting? 0 De -chlorination Yes No NA NE Type of system ? Tablet 0 ❑ Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑ ❑ Is storage appropriate for cylinders? ❑ ❑ 0 ❑ # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ 0 ❑ Comment: Are the tablets the proper size and type? 0 ❑ ❑ ❑ Are tablet de -chlorinators operational? 0 ❑ ❑ ❑ Number of tubes in use? 4 Comment: Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? 0 ❑ ❑ ❑ Is flow meter calibrated annually? 0 ❑ ❑ ❑ Is the flow meter operational? 0 ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: The flow meter is calibrated annually and was last calibrated on 11/16/17 by Delta Systems Environmental. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? 0 ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑ 0 If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: The effluent appeared slightly turbid with no floatable solids or foam. Aerobic Digester Yes No NA NE Is the capacity adequate? 0 ❑ ❑ ❑ Is the mixing adequate? 0 ❑ ❑ ❑ Is the site free of excessive foaming in the tank? 0 ❑ ❑ ❑ # Is the odor acceptable? 0 ❑ ❑ ❑ # Is tankage available for properly waste sludge? 0 ❑ ❑ ❑ Comment: The facility is equipped with an aerated sludge holding tank. Wastewater solids are removed and disposed on an as -needed basis by Lentz Septic Tank Service. Page# 7