Loading...
HomeMy WebLinkAboutWQCS00225_Compliance Evaluation Inspection_20180827 f cps ROY COOPER s Goi-eruo MICHAEL S.REGAN Water Resources LINDA CULPEPPER Environmental Quality Intel mi Director August 27, 2018 RECEIVED/DENRIDWR Lorenzo Carmon, Town Administrator AUG 3 0, 2018 Town of Pinetops 101 East Hamlet Street Water Resources Pinetops, NC 27864 Permitting Section Subject: Compliance Evaluation Inspection Town of Pinetops Wastewater Collection System Permit Number WQCS00225 Edgecombe County Dear Mr. Carmon: Mitch Hayes of the Raleigh Regional Office conducted the subject inspection on August 20, 2018. The assistance of Phil Webb, Operator in Responsible Charge (ORC) with this inspection was greatly appreciated. Below is a list of findings developed from the inspection and review of the permit. 1. The subject collection system was reclassified from a CS-2 system to a CS-1 system effective March 01, 2018. The subject permit was reissued, became effective May 01, 2018 and will expire April 30, 2026. There were no significant changes made to the permit. 2. A map of the collection system is maintained; however, it does not include line size, flow direction, or type of pipe material. 3. Education materials on proper grease disposal are sent to customers twice a year. Information on proper grease disposal is also available on the web. Food establishments are inspected throughout the year. There have been no enforcements for'the past year. 4. The Capital Improvement Program was updated October 09, 2017 and includes projects for fiscal years 2016 through 2025. Known deficiencies have been identified and are prioritized by importance. Currently, the CIP does not list any projects for the collection system. 5. Work orders, complaints, repairs made to equipment, line cleaning, right of way maintenance, high priority line inspection, SSO's, pump station maintenance ,are maintained in separate log books. Log books are reviewed weekly. 6. According to the permit, the amount of gravity sewer in the collection system is 11.3 miles or 59,664 feet. A review of the records indicates that 10% of gravity line have been cleaned for the fiscal year July 2017 through July 2018. 7. There are two pump stations in the collection system. Both stations have restricted access, contact information signage, audible /visual alarms, SCADA, and on-site generators with manual start and transfer switches. Audible / visual alarms functioned at both pump -:::"--"Nothi!rg Compares-4-4-A., Division of Vv'atet Resources, Raleigh Regional Office, Water Quality Operations Section http://portal.ncdenr.otg/web/wd/aps 1628 Mail Service Center,Raleigh,NC 27699-1628 Phone.(919)791-4200 Location:3800 Barlett Drive,Raleigh,NC 27609 Fax (919)788-7159 stations when the high-water float was lifted SCADA reported a high wet well. Pumps at both pump stations activated when their respective floats were lifted. SCADA reported a high wet well. The generators started and operated under load when power was turned off to the pump station and the generators were manually started. SCADA reported a power outage. 8. Three aerial lines were inspected. Two lines cross a ditch and have no supports. There was no bank erosion. The third aerial line was approximately 100 feet long and had concrete piers along its length. All piers appeared leveled with no erosion around the base of the piers. �_y __ ______V _ 9. The West Wood right-of-way was inspected. Three manholes were inspected. All manholes were solid with no crumbling. Flow in all three manholes were unobstructed with no grease or debris. The right-of-way was well maintained with no sinkholes or depressions noted. I would like to thank Phil Webb for his time and assistance with this inspection. If you have any questions concerning the inspection or this letter please contact Mitch Hayes at 919.791.4261 or at mitch.hayes cr,ncdenr.gov ,------� Sincc . 0 a.,n'/-y1/4-- 77-7 Danny Smith, Regional Supervisor Water Quality Regional Operations Section Raleigh Regional Office Division of Water Resources, NC DEQ cc: Permit files, Central files PERCS Unit Compliance Inspection Report Permit. WQCS00225 Effective: 05/01/18 Expiration: 04/30/26 Owner: Town of Pinetops SOC: Effective: Expiration: Facility: Pinetops Collection System County: Edgecombe PO Drawer C Region: Raleigh Pinetops NC 27864 Contact Person: Phil 0 Webb Title. Utility Director Phone: 252-827-4435 Directions to Facility: System Classifications: CS1, Primary ORC: Phil 0 Webb Certification: 15352 Phone: 252-827-4435 Secondary ORC(s): On-Site Representative(s): 24 hour contact name Lorenzo Carmon 252-827-4435 On-site representative Phil 0 Webb 252-827-4435 Related Permits: NC0020435 Town of Pinetops-Pinetops WWTP Inspection Date: 08/20/2018 Entry Time: 10 30AM Exit Time: 12 30PM byPrimary Inspector: Mitchell S Hayes ��aa (,� , e./ £2 22_, zoi 0 Phone: 919-791-4200 Secondary Inspector(s): Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type• Collection system management and operation Facility Status: I Compliant El Not Compliant Question Areas: s Miscellaneous Questions NIPerformance Standards Atl Operation&Maint Reqmts ® Records g Monitoring&Rpting Reqmts [2 Inspections 1 Pump Station ET Manhole , Lines (See attachment summary) Page 1 Permit: WQCS00225 Owner-Facility.Town of Pinetops Inspection Date. 08/20/2018 Inspection Type:Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary The subject collection system was reclassified from a CS-2 system to a CS-1 system effective March 01, 2018 The subject _ _ permit was reissued, became effective May 01, 2018 and will expire April 30, 2026 There were no significant changes made to the permit A map of the collection system is maintained however it does not include line size, flow direction, or type of pipe material Education materials on proper grease disposal are sent to customers twice a year Information on proper grease disposal is also available on the web Food establishments are inspected throughout the year There have been no enforcements for the past year The Capital Improvement Program was updated October 09, 2017 and includes projects for fiscal years 2016 through 2025. Known deficiencies have been identified and are prioritized by importance. Currently, the CIP does not list any projects for the collection system Work orders, complaints, repairs made to equipment, line cleaning, right of way maintenance, high priority line inspection, SSO's, pump station maintenance are maintained in separate log books Log books are reviewed weekly According to the permit, the amount of gravity sewer in the collection system is 11 3 miles or 59,664 feet.A review of the records indicates that 10% of gravity line have been cleaned for the'fiscal year July 2017 through July 2018. There are two pump stations in the collection system Both stations have restricted access, contact information signage, audible/visual alarms, SCADA, and on-site generators with manual start and transfer switches Audible/visual alarms functioned at both pump stations when the high-water float was lifted SCADA reported a high wet well Pumps at both pump stations activated when their respective floats were lifted SCADA reported a high wet well.The generators started and operated under load when power was turned off to the pump station and the generators were manually started SCADA reported a power outage Three aerial lines were inspected Two lines crosses a ditch and have no supports.There was no bank erosion The third aerial line was approximately 100 feet long and had concrete piers along its length All piers appeared leveled with no erosion around the base of the piers. . - The West Wood right-of-way was inspected.Three manholes were inspected All manholes were solid with no crumbling Flow in all three manholes were unobstructed with no grease or debris The right-of-way was well maintained with no sinkholes or depressions noted Page. '2 • Permit: WQCS00225 Owner-Facility Town of Pinetops Inspection Date. 08/20/2018 Inspection Type:Collection System Inspect Non Sampling Reason for Visit: Routine Performance Standards Yes No NA NE Is Public Education Program for grease established and documented? El El El ❑ What educational tools are used'? Educational flyers on proper grease disposal Is Sewer Use Ordinance/Legal Authority available'? El El El Does it appear that the Sewer Use Ordinance is enforced'? El El ❑ Is Grease Trap Ordinance available'? tF, El El El Is Septic Tank Ordinance available(as applicable, i.e annexation) El El El List enforcement actions by permittee, if any, in the last 12 months None Has an acceptable Capital Improvement Plan(CIP)been implemented'? I El El El Does CIP address short term needs and long term\"master plan\"concepts'? gl El El El Does CIP cover three to five year period'? ❑ ❑ 0 Does CIP include Goal Statement'? ❑ ❑ El Does CIP include description of project area'? El El El Does CIP include description of existing facilities'? El ❑ ❑ Does CIP include known deficiencies'? in ❑ El El Does CIP include forecasted future needs'? " El El ❑ Is CIP designated only for wastewater collection and treatment? ❑ EZI ❑ El Approximate capital improvement budget for collection system'? Total annual revenue for wastewater collection and treatment'? CIP Comments Currently there are no monies allocated for the collection system. Is system free of known points of bypass'? PI 0 El El If no,describe type of bypass and location Is a 24-hour notification sign posted at ALL pump stations'? ❑ El El #Does the sign include' Instructions for notification'? E 0 ❑ El Pump station identifier'? Es 1,1, El ❑ ❑ 24-hour contact numbers 0 ❑ El If no,list deficient pump stations #Do ALL pump stations have an"auto polling"feature/SCADA? 1M El ❑ ❑ Number of pump stations 2 Number of pump stations that have SCADA 2 Number of pump stations that have simple telemetry 0 Number of pump stations that have only audible and visual alarms 0 Page. 3 Permit WQCS00225 Owner-Facility:Town of Pinetops Inspection Date• 08/20/2018 Inspection Type.Collection System Inspect Non Sampling Reason for Visit: Routine Number of pump stations that do not meet permit requirements 0 #Does the permittee have a root control program? ❑ El El #If yes,date implemented? Describe - - - - Roots are removed when lines are cleaned Comment Inspections Yes No NA NE Are maintenance records for sewer lines available'? ® El ❑ ❑ Are records available that document pump station inspections? ❑ ❑ ❑ Are SCADA or telemetry equipped pump stations inspected at least once a week'? ❑ ❑ ❑ Are non-SCADA/telemetry equipped pump stations inspected every day'? ❑ ❑ ❑ Are records available that document citizen complaints'? ❑ ❑ ❑ #Do you have a system to conduct an annual observation of entire system'? ❑ ❑ ❑ #Has there been an observation of remote areas in the last year'? ❑ ❑ ❑ Are records available that document inspections of high-priority lines'? ❑ ❑ ❑ Has there been visual inspections of high-priority lines in last six months'? ❑ ❑ ❑ Comment Operation &Maintenance Requirements • Yes No NA NE Are all log books available'? 4 ❑ ❑ ❑ Does supervisor review all log books on a regular basis'? ❑ ❑ ❑ Does the supervisor have plans to address documented short-term problem areas? El ❑ ❑ El What is the schedule for reviewing inspection, maintenance,&operations logs and problem areas'? weekly - Are maintenance records for equipment available'? ❑ ❑ ❑ Is a schedule maintained for testing emergency/standby equipment? 0 ❑ ❑ ❑ What is the schedule for testing emergency/standby equipment? weekly Do pump station logs include Inside and outside cleaning and debris removal'? El ❑ ❑ ❑ Inspecting and exercising all valves'? ❑ ❑ ❑ Inspecting and lubricating pumps and other equipment'? 0 ❑ ❑ ❑ Inspecting alarms,telemetry and auxiliary equipment'? EU ❑ El ❑ Is there at least one spare pump for each pump station w/o pump reliability'? 0 ❑ ❑ ❑ Are maintenance records for right-of-ways available'? 0 ❑ ❑ ❑ Are right-of-ways currently accessible in the event of an emergency'? E ❑ ❑ ❑ Are system cleaning records available'? LI ❑ ❑ ❑ Has at least 10%'of system been cleaned annually'? [1 ❑ ❑ ❑ Page 4 Permit: WQCS00225 Owner-Facility:Town of Pinetops Inspection Date• 08/20/2018 Inspection Type.Collection System Inspect Non Sampling Reason for Visit Routine What areas are scheduled for cleaning in the next 12 months'? Grease prone areas Is a Spill Response Action Plan available'? El El El Does the plan include 24-hour contact numbers El El 0 Response time El 0 El Equipment list and spare parts inventory k ; El El El Access to cleaning equipment El 0 0 Access to construction crews, contractors,and/or engineers Li 0 El Source of emergency funds - El 0 El Site sanitation and cleanup materials • 0 El El Post-overflow/spill assessment Ell El El El Is a Spill Response Action Plan available for all personnel? El 0 0 Is the spare parts inventory adequate'? fal El 0 El Comment Records Yes No NA NE Are adequate records of all SSOs,spills and complaints available'? El 0 Are records of SSOs that are under the reportable threshold available? 6 El El El Do spill records indicate repeated overflows(2 or more in 12 months)at same location? ® El El If yes,is there a corrective action plan? El El El Is a map of the system available'? El El El Does the map include Pipe sizes El El El Pipe materials El 0 El Pipe location El 0 El Flow direction E ❑ El Approximate pipe age ❑ El El Number of service taps Pump stations and capacity El El El 0 If no,what percent is complete'? 90 List any modifications and extensions that need to be added to the map See above #Does the permittee have a copy of their permit? El El 0 Comment Monitoring and Reporting Requirements Yes No NA NE Are copies of required press releases and distribution lists available'? F El ElEl Are public notices and proof of publication available'? El 0 0 El Page. 5 10001=10000000 Z Z ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ W ❑ ❑ ❑ ❑ 0 ❑ ❑ Z ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ z ❑ 00000000 � ❑ ❑ ❑ ❑ a) o ❑ ❑ Z ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ M . 00000000M . ❑ ❑ ❑ ❑ } 0 0 . (9 N 01 i C o. • 1 E i a) co o Z U a) Q_ N C V7 v E v u) Q 0 N l) I a) Q o_ r O r O -t-9.3 • @ r a) .6 o t _C a3 I- EO ui r1 03 E aTL a i N I a N o O E o Fo LL so_ c 0.o_ 2 0 a) u cn o_ O as (a c Y i 0Z w ; ..c - ' L t (Q — Cl) # 3 a) 0 O o c 0 Q r r O rO c 0 a) OaU co aO6 17, r O) - c 0) O 6 L a) a) N O a) 0N Op CD N N coo o N r (6 'O N C . T o a)0N O C ❑ Oa) Q 7 O O a (113C fl_ 16 O OE NN C a O E N vE cp o E o C r N 0 z2 c r • E o . a) ' EI oo (13 0 a) p 0 aN - T mE N E Cciu a c N E C a) _ O • NaN N -NC p Q - N a) -C ---- _O (3 ( 5 O 2 a) aa) '6 O j r TC O 'Oj NC (n2 .L p O > p o ` Q O O i _ . Oa) O_ aO co . ac C O) O ao � Lo o co O L Co m o FL Q C c o an 0 • QO _C w o NC E -OC • CQ o o o c � cE v O N C O fl. O N " C 73 E Q (n a) 0OOCaL VN V) N m Q (6 (n (0 O Cl) NOaN oN O C Na) C4- Uy OO O Eo oOr u U a) T O — a 55 C ❑ p O a) ,3-' N c C Q . E o 2as m -o S 4-�, o .= E ( a- as a a7 > ) (n 5 WOd C NO 9a) 4- a)a3 co a0a5 O_ T 2 T T 0 o � (1) ❑ OT o .� NaO Cl) 0 Cl) m c +, as as o @n � «- a+ 03 as o as a 3O 0 m vL axo am s maxi o4 m cm . uN Jo o pa a) N J _ o o o a 9 o (° c aQ t as a) N -1....r. i52 sc m > ,---c) Qaa0f a ) ) C a) n W c w E co 0) 0-) a) c < w N n = < T 0 W c o w w c O C N T n y n iii w (nn * * Q * n * — < J * * _ UQN n w < * J v, * F It D > > D m > > m v, cn Fri > > D > > r m > -0 -0 (!) n -* It 0 * D m w 3 3 3 m 3 3 0 CD - - 0 (D (D (D m w r.. m c = m o '< D — m 3 m r..) m m cn 0 m CD CrCT 0 m m 3 3 c a Cl- c m CD CO 0 -o - -C3 n m m CD * v 'A (D coCD y � R CD N C C T3 -O o -O 0 = — 0 0 - c0 -„ (D m m 7- coo _ o 5 7 0 0 -0 o. Q. O O v cn -O -O 7 C) 3 Cl) 2 N 3 '.< 7 O O CD n) 0 N -fin C p' p N a -o y g C C (D -� v .. (D (p (D N N o N CD c m -0 0 m m 0 0 .0 D) v co cu 9_ a_ 0 nn) a) 3 3 m m cn o �, D m `D — C) m a m a m 2 0 3 < < cn o. 0. (D (D 5 5 0 3 m m w 3 — d o CD m m 0 * 0 0 0 O -, 0 0 3 m w m m 0 ' S < 0 o `� `� 0 3 m o -o 0 m o —I < �<, N m v -* 5 CD 0 0 m CO m m < < 0 0 u m m v, m o m m m m �7 0 3 0 a ° Si m 0 0. m 0 0 m m c m v `Z °' m o m °' o m j 0 m m m 0 0 3 0 0 c 0 0 5 m (n g ,..s- c o 0 s 0 0 CO Ill o — 0. m a o m - 0 0 0 c II < o_ 0 g �, m m CD m m 0 x m J m m H m w o 0- 0 e _ CD C (n O J 05 3 O O Cl) (D o (D (D CO 0 N N N p (D N N (U (D (n Cl) .-�, 0 7 L)) < ( N _ 3 7 m F 0 m m c 0 0 3 3 0 co 3 CD O (o o N 0 (0 0 = J C (D N J 6 (7 CD Cl)( U) 9 J D D 'a (D U) n) 0 N -4 U) N '� (D 'O C O C7 -0 0 J -O N N J N (D 0- O 73 N 0 0 N 0 o O — O CI)— C O J C n o o 0 O cs (D v O J J 0 3 N J D D N -" - O 0 J 01 D Q (D = in 0 C Q O O W O- N 3 n N Q. n • 00 7 0 .0 (Q c n) .Q o O u) W _ OD C O (0 "3 ..O 7 v C• CJ J N ? CD '00 0 -0 (D N O O O C_ J J a1 N to- Q •( D co 00 o O O J O J N o. j 0 J N • O 0 Q 0 J J O C J 3 CD v iiT o 0) (D m 0 a < o 'o Cl CD Q- O ' 0 o m ° -i n J A a (D 3 i m `c o DI mo cn 3' m ( J ^ O O 7 • < (D N cD 0 7 a a z 0 7 CD as 3 a 5 an ID co m In0 O S O C tl! t w 'x SD I:10E10 `• 1=10100000000N1001:101:11:10001=1 0 .4, I: 0 121 El . CO z ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ z ❑ ❑ ❑ ❑ ❑ y ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ m ❑ ❑ ❑ ❑ ❑ ❑ Permit. WQCS00225 Owner-Facility•Town of Pinetops Inspection Date: 08/20/2018 Inspection Type•Collection System Inspect Non Sampling Reason for Visit: Routine Does it include Instructions for notification? n ❑ ❑ ❑ Pump station identifier? ❑ ❑ ❑ Emergency phone number ❑ ❑ ❑ Is public access limited? ❑ ❑ ❑ Is pump station free of overflow piping'? MEDD Is the pump station free of signs of overflow'? —❑ ❑ ❑ Are run times comparable for multiple pumps'? yes Comment. Generator is manual start with manual transfer switch. BURNETTE STREET - 704 Pump Station Yes No NA NE Pump station type Duplex Are pump station logs available'? ❑ ❑ ❑ Is it accessible in all weather conditions'? ❑ ❑ ❑ #Is general housekeeping acceptable? ® ❑ ❑ ❑ Are all pumps present'? ❑ ❑ ❑ Are all pumps operable'? ❑ CI ❑ Are wet wells free of excessive debris'? anou Are upstream manholes free of excessive debns/signs of overflow'? ❑ ❑ ❑ Are floats/controls for pumps/alarms operable? ❑ ❑ ❑ Is"auto polling"feature/SCADA present'? MOOD Is"auto polling"feature/SCADA operational'? 41 ❑ ❑ ❑ Is simple telemetry present? ❑ RI ❑ ❑ Is simple telemetry operational'? ❑ ❑ E ❑ Are audio and visual alarms present'? MOOD Are audio and visual alarms operable'? MEDD Is the Pump station inspected as required'? ® ❑ ❑ ❑ Are backflow devices in place'? 0 ❑ ❑ ❑ Are backflow devices operable'? IV ❑ ❑ ❑ Are air relief valves in place'? ❑ ❑ ❑ Are air relief valves operable' ® ❑ ❑ ❑ # Is an emergency generator available'? ffi ❑ ❑ ❑ Can the emergency generator run the pumps'? ` ❑ ❑ ❑ Is the pump station equipped for quick hook-up'? ❑ =`_ ❑ ❑ Is the generator operable'? ❑ ❑ ❑ #Is fuel in tank and sufficient? 12 ❑ ❑ ❑ Page 8 r Permit: WQCS00225 Owner-Facility:Town of Pinetops Inspection Date: 08/20/2018 Inspection Type:Collection System Inspect Non Sampling Reason for Visit Routine Is the generator inspected according to their schedule'? LI LI [I Is a 24-hour notification sign posted'? DEO Does it include Instructions for notification? tLI [] Pump station identifier'? O D D Emergency phone number ® DEO Is public access limited'? El El El Is pump station free of overflow piping'? I El E LI Is the pump station free of signs of overflow'? HEILID Are run times comparable for multiple pumps'? yes Comment Generator is manual start with manual transfer switch. • • Page. 9