HomeMy WebLinkAboutNC0087602_Compliance Evaluation Inspection_20180824
North Carolina Department of Environmental Quality | Division of Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
August 24, 2018
Dan Harbaugh, Executive Director
Tuckaseigee Water & Sewer Authority
1246 W Main St
Sylva, NC 28779
SUBJECT: Compliance Inspection Report
Whittier WWTP
NPDES WW Permit No. NC0087602
Jackson County
Dear Mr. Harbaugh:
The North Carolina Division of Water Resources conducted an inspection of the Whittier WWTP on
8/20/2018. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0087602. Based on the on-site visit, the
facility was determined to be in compliance.
The following item was noted during the inspection:
Maintenance: Inadequate water pressure at facility to wash down treatment components (specifically
clarifier weir plates). Recommend installing or having onsite a means to adequately clean treatment
components that are not easily accessible.
Additional findings and comments are provided in the enclosed inspection report under Section D,
“Summary of Findings/Comments”. If you should have any questions, please do not hesitate to contact me at
828-296-4500 or via email at mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
DocuSign Envelope ID: 694548EE-730B-44F4-B451-4CACC059A392
North Carolina Department of Environmental Quality | Division of Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
ATTACHMENTS: Compliance Inspection Report
EC: WQS-ARO Server
LF
Stan Bryson-Wastewater Operations Superintendent
20180824_NC0087602_CEI
DocuSign Envelope ID: 694548EE-730B-44F4-B451-4CACC059A392
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0087602 18/08/20 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Whittier WWTP
Jackson County Industrial Park
Whittier NC 28789
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
10:00AM 18/08/20 17/11/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
George Harvey Bingham/ORC/828-586-9318/
Other Facility Data
11:00AM 18/08/20 22/08/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Dan Harbaugh,1246 W Main St Sylva NC 28779/Executive
Director/828-586-5189/8286319089
Contacted
Yes
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Mikal Willmer Division of Water Quality//828-296-4686/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: 694548EE-730B-44F4-B451-4CACC059A392
8/24/2018
8/24/2018
NPDES yr/mo/day
18/08/20
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Inspector Mikal Willmer, with the Asheville Regional Office, conducted a compliance evaluation
inspection of the Whittier WWTP. This inspection was conducted to determine whether the facility is
being operated and maintained in compliance with NPDES Permit No. NC0087602. ORC, Harvey
Bingham was present and assisted in the inspection.
Overall the plant is being well operated and maintained. Facility receives little flow which makes
maintaining healthy biota within the facility difficult. The plant was designed for 0.100 MGD and the
ORC reports they average about 8000 to 9000 GPD. Since flow is not consistent, the operator batches
treatment. All flow is directed into the EQ Basin/Surge tank before entering the AB.
Additional item noted during the inspection:
Algae is building up on the clarifier weir plates. This has the potential to cause weir blockage and
uneven distribution of flow across the weirs. Currently there is inadequate water pressure at the facility
to wash down the clarifier. Recommend installing or having onsite a means to adequately clean
treatment components that are not easily accessible.
NC0087602 17 (Cont.)
Page#2
DocuSign Envelope ID: 694548EE-730B-44F4-B451-4CACC059A392
Permit:NC0087602
Inspection Date:08/20/2018
Owner - Facility:
Inspection Type:
Whittier WWTP
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
DO, pH and Temp.Comment:
Flow Measurement - Influent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
A totalizer is used to record daily incoming flows.Comment:
Influent Sampling Yes No NA NE
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is sampling performed according to the permit?
Influent sampling is time composite.Comment:
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
ORC tests influent pump station floats and alarms once a week. Telemetry on pump station
will notify on-call staff if alarms go off.
Comment:
Permit Yes No NA NE
Page#3
DocuSign Envelope ID: 694548EE-730B-44F4-B451-4CACC059A392
Permit:NC0087602
Inspection Date:08/20/2018
Owner - Facility:
Inspection Type:
Whittier WWTP
Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Section A.(2) Permit Reopener Provisions. Package plant design and treatment
components should be clarified during the next permit renewal. Schematic shows two ABs
and one surge tank; however, ORC indicated he was utilizing two EQ basins and one AB.
Facility is using an effluent ultrasonic flow meter and Parshall flume.
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Maintains process control and effluent data on-site. Laboratory bench sheets are maintained
at TWSA #1.
Comment:
Page#4
DocuSign Envelope ID: 694548EE-730B-44F4-B451-4CACC059A392
Permit:NC0087602
Inspection Date:08/20/2018
Owner - Facility:
Inspection Type:
Whittier WWTP
Compliance Evaluation
Equalization Basins Yes No NA NE
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/l)
Blowers run for 1.5 hours and rest for two. ORC reports he tries to maintain a DO of 4 mg/L
in the basin.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Page#5
DocuSign Envelope ID: 694548EE-730B-44F4-B451-4CACC059A392
Permit:NC0087602
Inspection Date:08/20/2018
Owner - Facility:
Inspection Type:
Whittier WWTP
Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
Scum cup is broken on one of the two clarifiers limiting scum removal capabilities. Does not
appear to be exiting the clarifier. Algae is beginning to grow on weirs plates in both clarifiers.
This has not caused weir blockage, but has the potential to restrict even distribution of flow.
ORC reports he has no means of cleaning off the weir plates. Current water supply spigot is
below the plant. Water pressure is too low to remove growth and the plates are not easily
accessible for manually cleaning. Recommend supplying a means to wash down the weir
plates to prevent further build up.
Comment:
Pumps-RAS-WAS Yes No NA NE
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
ORC reports he has only had to waste once this year due to low flow conditions. Only two
loads were hauled to TWSA #1 last year.
Comment:
Filtration (High Rate Tertiary)Yes No NA NE
Type of operation:Cross flow
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
System backwashes filters at set intervals. Only one set of disc filters is used at a time.
Change over every six months and clean filters that are not in use.
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
ORC exercises the generator once a month.Comment:
Page#6
DocuSign Envelope ID: 694548EE-730B-44F4-B451-4CACC059A392
Permit:NC0087602
Inspection Date:08/20/2018
Owner - Facility:
Inspection Type:
Whittier WWTP
Compliance Evaluation
Standby Power Yes No NA NE
Disinfection - UV Yes No NA NE
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
ORC cleans UV bulbs every 2-3 weeks.Comment:
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Calibrated by ISI annually. Total flow is recorded daily to calculate daily flow. Chart recorder
is present, but is not being used for reporting purposes.
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
TWSA is in the process of setting sampling to flow proportional. DO and Temperature are
not required effluent parameters, but are monitored by the permittee. The DO of the effluent
has been around 2.5 mg/L and temperature has been approximately 35 degrees this month.
Comment:
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and
sampling location)?
Facility is only required to sample for ammonia.Comment:
Page#7
DocuSign Envelope ID: 694548EE-730B-44F4-B451-4CACC059A392