Loading...
HomeMy WebLinkAboutWQ0011313_Inspection_20180815Compliance Inspection Report Permit: WQ0011313 Effective: 10/25/07 Expiration: 09/30/16 owner: Peppertree Atl Bch Owner's Assoc Inc SOC: Effective: Expiration: Facility: Peppertree Resort WWTF County: Carteret 715 W Fort Macon Rd Region: Wilmington Atlantic Beach NC 28512 Contact Person: Katherine Sanchez Title: Property Manager Phone: 252-247-5841 Directions to Facility: From Wilmington, follow US 17N to NC 24 E to US 70E. Turn right on Atlantic Beach Causeway, Turn right on NC 58W, facility is on the left. System Classifications: WW2, Primary ORC: Joseph A Lawrence Certification: 6418 Phone: 252-393-8720 Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 08/15/2018 Entry Time: 11:OOAM Primary Inspector: Brian S West Secondary Inspector(s): Helen I Perez Reason for Inspection: Routine Permit Inspection Type: High Rate Infiltration Facility Status: ❑ Compliant Not Compliant Question Areas: Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Treatment Flow Measurement -Water Treatment Use Records Treatment Filters Record Keeping Treatment Sludge Storage/Treatment End Use -Irrigation Treatment Disinfection Treatment Flow Measurement Standby Power Wells Exit Time: 12:30PM Phone: 910-796-7341 Inspection Type: Compliance Evaluation (See attachment summary) Miscellaneous Questions Treatment Barscreen Treatment Activated Sludge Treatment Clarifiers 0 Treatment Return pumps Page: 1 Permit: WQ0011313 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Date: 08/15/2018 Inspection Type : Compliance Evaluation Reason for Visit: Routine Inspection Summary: Inspection with Dan Fortin and staff. Permit expired 9/30/16. Permittee has submitted renewal application twice, but the app has been returned twice due to failure to provide required additional information, most recently 5/1/18. Current issues pending include primarily multiple ownership of site parcels and lack of recorded unrestricted access easements, lease agreements etc required by 02T.0704(f). The facilties remain in noncomliance for this issue. In addition, the following was noted: 1) The 'old' treatment trains 1 and 2 are currently used for emergency storage as indicated by the operators. Both tanks have visible significant corrosion, and it recommended that the tanks not be used until a structural engineer can inspect and make recommendations for usage. The end of tank 2 is buckled outward with several top tank welds broken loose. It is recommended this tank be pumped out and removed from service immediately; 2) The active trains are missing walkway gratings creating a safety hazard for operators. Gratings should be installed in these areas and corroded gratings in other locations replaced as determined to be needed by operators; 3) The primary flow equalization tank has excessive grease that needs to be pumped out. The grease can foul pump and alarm control floats and create excessive odors; 4) Drip irrigation field no. 2 is in need of grass cutting so that routine inspection of drip lines can be made; 5) Monitoring well data (GW -59 forms) have not been received for the following months: 6/16, 6/17, 10/17, 2/18. If theses analyses have been performed, please submit the data on the appropriate forms. Lack of submittal of this data is a monitoring violation in accordance with permit WQ0011313 and may result in further enforcement action Page: 2 Permit: WQ0011313 Inspection Date: 08/15/2018 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Type : Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Infiltration System ❑ Lagoon Spray, LR ❑ Single Family Spray, LR ❑ Activated Sludge Spray, LR ❑ Activated Sludge Spray, HR ❑ Reuse (Quality) ❑ Recycle/Reuse ❑ Single Family Drip ❑ Activated Sludge Drip, LR Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? ❑ 0 ❑ ❑ Do all treatment units appear to be operational? (if no, note below.) ❑ 0 ❑ ❑ Comment: Facilties were permitted for nutrient removal via an anoxic system; construction was started but not completed. Currently, the plant is being operated as extended aeration plant (2 trains in operation rated at 82,000 gpd). One anoxic basin was constructed and is being used for additional flow equalization. The original trains 1 and 2 are being used for'upset' storage and additional EQ during emergencies. The tanks are badly corroded and are recommended to be taken off-line unless an independent structural analysis is performed. The side wall at the end of tank no. 2 is buckled outward and this tank should be taken off-line immediately Treatment Flow Measurement -Influent Yes No NA NE Is flowmeter calibrated annually? ❑ 1:10 ❑ Is flowmeter operating properly? ❑ ❑ 0 ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? ❑ ❑ ❑ Comment: Treatment Flow Measurement -Water Use Records Yes No NA NE Is water use metered? ❑ 1:10 ❑ Are the daily average values properly calculated? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement -Effluent Yes No NA NE Is flowmeter calibrated annually? 0 ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ 0 Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Page: 3 Permit: WQ0011313 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Date: 08/15/2018 Inspection Type : Compliance Evaluation Reason for Visit: Routine Does flowmeter appear to monitor accurately? ❑ ❑ ❑ 0 Comment: Standby Power Yes No NA NE Is automatically activated standby power available? ❑ ❑ ❑ Is generator tested weekly by interrupting primary power source? ❑ ❑ ❑ Is generator operable? 0 ❑ ❑ ❑ Does generator have adequate fuel? ❑ ❑ ❑ 0 Comment: Treatment Barscreen Yes No NA NE Is it free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screenings in compliance? 0 ❑ ❑ ❑ Are the bars spaced properly? 0 ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: Screen was recently replaced Treatment Activated Sludge Yes No NA NE Is the aeration mechanism operable? 0 ❑ ❑ ❑ Is the aeration basin thoroughly mixed? 0 ❑ ❑ ❑ Is the aeration equipment easily accessed? 0 ❑ ❑ ❑ Is Dissolved Oxygen adequate? ❑ ❑ ❑ Are Settleometer results acceptable? ❑ ❑ ❑ Is activated sludge an acceptable color? ❑ ❑ ❑ Comment: Treatment Clarifiers Yes No NA NE Are the weirs level? 0 ❑ ❑ ❑ Are the weirs free of solids and algae? ❑ ❑ ❑ Is the scum removal system operational? ❑ ❑ ❑ Is the scum removal system accessible? ❑ ❑ ❑ Is the sludge blanket at an acceptable level? ❑ ❑ ❑ Is the effluent from the clarifier free of excessive solids? ❑ ❑ ❑ Comment: Treatment Return pumps Yes No NA NE Are they in place? 0 ❑ ❑ ❑ Are they operational? ❑ ❑ ❑ 0 Comment: Page: 4 Permit: WO0011313 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Date: 08/15/2018 Inspection Type : Compliance Evaluation Reason for Visit: Routine Treatment Filters Yes No NA NE Is the filter media present? ❑ ❑ ❑ Is the filter media the correct size and type? ❑ ❑ ❑ Is the air scour operational? 0 ❑ ❑ ❑ Is the scouring acceptable? 0 ❑ ❑ ❑ Is the clear well free of excessive solids? ❑ ❑ ❑ Is the mud well free of excessive solids and filter media? ❑ ❑ ❑ Does backwashing frequency appear adequate? 0 ❑ ❑ ❑ Comment: Treatment Sludge Storage/Treatment Yes No NA NE Is the aeration operational? ❑ ❑ ❑ Is the aeration pattern even? ❑ ❑ ❑ If required, are Sanitary "Ts" present in tankage? ❑ ❑ 0 ❑ Comment: Treatment Disinfection Yes No NA NE Is the system working? 0 ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time (-30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas, does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ Is the chlorinator accessible? 0 ❑ ❑ ❑ If tablets, are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑ If UV, are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ # Is it a dual feed system? ❑ ❑ 0 ❑ Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes, then what is the EPA twelve digit ID Number? (1000--) If yes, then when was the RMP last updated? Comment: UV unit on train 3 is inoperable, operators use chlorine tablets placed in clarifier troughs and the UV trough. Residual levels appear adequate and contact time was determined to be sufficient. Record Keeping Yes No NA NE Is a copy of current permit available? ❑ ❑ ❑ 0 Page: 5 Permit: WQ0011313 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Date: 08/15/2018 Inspection Type : Compliance Evaluation Reason for Visit: Routine Are monitoring reports present: NDMR? ❑ ❑ ❑ 0 NDAR? ❑ ❑ ❑ 0 Are flow rates less than of permitted flow? 0 ❑ ❑ ❑ Are flow rates less than of permitted flow? 0 ❑ ❑ ❑ Are application rates adhered to? 0 ❑ ❑ ❑ Is GW monitoring being conducted, if required (GW -59s submitted)? 0 ❑ ❑ ❑ Are all samples analyzed for all required parameters? 0 ❑ ❑ ❑ Are there any 2L GW quality violations? ❑ ❑ 0 ❑ Is GW -59A certification form completed for facility? 0 ❑ ❑ ❑ Is effluent sampled for same parameters as GW? 0 ❑ ❑ ❑ Do effluent concentrations exceed GW standards? 0 ❑ ❑ ❑ Are annual soil reports available? ❑ ❑ 0 ❑ # Are PAN records required? ❑ ❑ 0 ❑ # Did last soil report indicate a need for lime? ❑ ❑ 0 ❑ If so, has it been applied? ❑ ❑ 0 ❑ Are operational logs present? 0 ❑ ❑ ❑ Are lab sheets available for review? ❑ ❑ ❑ 0 Do lab sheets support data reported on NDMR? ❑ ❑ ❑ 0 Do lab sheets support data reported on GW -59s? ❑ ❑ ❑ 0 Are Operational and Maintenance records present? ❑ ❑ ❑ 0 Were Operational and Maintenance records complete? ❑ ❑ ❑ 0 Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑ 0 Is a copy of the SOC readily available? ❑ ❑ 0 ❑ No treatment units bypassed since last inspection? 0 ❑ ❑ ❑ Comment: End Use-Irriqation Yes No NA NE Are buffers adequate? ❑ 0 ❑ ❑ Is the cover crop type specified in permit? ❑ ❑ 0 ❑ Is the crop cover acceptable? ❑ ❑ 0 ❑ Is the site condition adequate? 0 ❑ ❑ ❑ Is the site free of runoff / ponding? ❑ ❑ ❑ Is the acreage specified in the permit being utilized? ❑ ❑ ❑ Is the application equipment present? ❑ ❑ ❑ Is the application equipment operational? ❑ ❑ ❑ Is the disposal field free of limiting slopes? ❑ ❑ ❑ Is access restricted and/or signs posted during active site use? ❑ ❑ ❑ Page: 6 Permit: WO0011313 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Date: 08/15/2018 Inspection Type : Compliance Evaluation Reason for Visit: Routine Are any supply wells within the CB? Are any supply wells within 250' of the CB? How close is the closest water supply well? Is municipal water available in the area? # Info only: Does the permit call for monitoring wells? Are GW monitoring wells located properly w/ respect to RB and CB? Are GW monitoring wells properly constructed, including screened interval? Are monitoring wells damaged? ❑❑■❑ ❑❑❑■ ❑❑❑■ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑❑❑■ ❑❑❑■ Page: 7 Permit: WQ0011313 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Date: 08/15/2018 Inspection Type : Compliance Evaluation Reason for Visit: Routine Comment: Property including drip zones is currently subdivided with 4 different owners. Prior to permit renewal (expired 9/30/16) , unrestricted permittee access easments will need to be approved and recorded. Permittee, Peppertree Owner's Association, is currently in bankruptcy precedings according to the site manager. Page: 8 Permit: WO0011313 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Date: 08/15/2018 Inspection Type : Compliance Evaluation Reason for Visit: Routine Page: 9 Permit: WO0011313 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Date: 08/15/2018 Inspection Type : Compliance Evaluation Reason for Visit: Routine Page: 10 Permit: WO0011313 Owner - Facility: Peppertree Atl Bch Owner's Assoc Inc Inspection Date: 08/15/2018 Inspection Type : Compliance Evaluation Reason for Visit: Routine Field no. 2 is in need of landscaping maintenance. The grass is high enough that visual inspection of the field is not possible. Page: 11