HomeMy WebLinkAboutWQ0004967_Inspection_20180815
North Carolina Department of Environmental Quality | Division of Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
August 15, 2018
Kristina Armbrust
Alljuice Realty LLC
2001 Butterfield Road – Suite 600
Downers Grove, IL 60515
SUBJECT: Compliance Inspection Report
Alljuice WWTF
Non-discharge Permit No. WQ0004967
Henderson County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Alljuice WWTF on
7/25/2018. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non-discharge Permit No. WQ0004967. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
Although most of the sprayfield has a good stand of grass, there are patches that contain more weeds than
grass. This was noted during the last two inspections. According to the ORC, the Henderson County
Cooperative Extension Service was contacted for recommendations for controlling weed growth. Those
areas of the sprayfield that contain an excessive amount of weeds should be addressed so that the entire
field can accept and assimilate wastewater. Reseeding, if needed, does not have to be completed all at
once to ensure that there is adequate acreage available for spray. The soils report that was conducted
9/27/17 did not provide any fertilizer recommendations. A diagnostic soils analysis would be a tool to
identify nutrient deficiencies or excesses that may prevent optimal plant health in the sprayfield (i.e. weed
growth).
DocuSign Envelope ID: 9669C43A-BCAA-460E-93CF-1454772A5AD1
North Carolina Department of Environmental Quality | Division of Water Resources
2090 U.S. 70 Highway, Swannanoa, NC 28778
828-296-4500
An Industrial Pump & Haul permit was requested in June 2018. That permit expired June 29, 2018 per
Metropolitan Sewerage District (MSD), the receiving facility. Any future Industrial Pump & Haul permits will
require a new receiving facility acceptance letter.
A groundwater investigation is ongoing to address 2L Groundwater Standard exceedances. Any 2L
violations and/or GW-59 reporting issues will be addressed separately from this inspection report.
If you should have any questions, please do not hesitate to contact me at 828-296-4500 or via email at
bev.price@ncdenr.gov.
Sincerely,
Beverly Price, Environmental Senior Specialist
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Juanita James
WQS ARO Server
LF
20180815_WQ0004967_CEI.rtf
DocuSign Envelope ID: 9669C43A-BCAA-460E-93CF-1454772A5AD1
Compliance Inspection Report
Permit:WQ0004967 Effective:04/27/17 Expiration:03/31/22 Owner :Alljuice Realty LLC
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Henderson
Asheville
Juanita Reed James
Effective:Expiration:Facility:Alljuice WWTF
352 Jet St
Hendersonville NC 28792
Title:Phone:828-697-0063ORC
I-26 East to Hwy. 64 East (toward Bat Cave). Turn right at the first stop light onto Sugarloaf Road. Follow signs to Alljuice. Facility
is located approximately 3 miles on the left.
Davis Allen James 1001739 828-697-0063
Secondary ORC(s):
828-697-0063Phone:25034Certification:Juanita Reed JamesPrimary ORC:
SI,System Classifications:
24 hour contact name Juanita R James 828-697-0063
24 hour contact name Barry Sester 828-685-8821
On-site representative Barry Sester 828-685-8821
On-site representative Juanita R James 828-697-0063
On-Site Representative(s):
Related Permits:
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
07/25/2018 09:30AM 02:18PM
Beverly Price 828-296-4500
Brett Laverty
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Wastewater Irrigation
Compliance Evaluation
Question Areas:
Miscellaneous Questions Treatment Record Keeping
Treatment Lagoons End Use-Irrigation
(See attachment summary)
Page:1
DocuSign Envelope ID: 9669C43A-BCAA-460E-93CF-1454772A5AD1
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004967
07/25/2018 Compliance Evaluation
Alljuice Realty LLC
Routine
Inspection Summary:
The inspection was conducted by Beverly Price of the Asheville Regional Office (ARO). Juanita James, Barry Sester and
Fred Budde were present and assisted with the inspection. Also on site were Brett Laverty of the ARO, Chris Gilbert and
Chuck Pippen with Anchor QEA. Mr. Laverty, Mr. Gilbert & Mr. Pippen are addressing ongoing groundwater violations
believed to be associated with the unlined lagoon. Groundwater and surface water monitoring will continue as part of the
groundwater investigation.
Lagoon aerators are set to alternate run times; however, all three sometimes run simultaneously. Caustic soda (liquid) is
added to the process wastewater for pH adjustment. This should be documented in the operations/maintenance log.
Caustic is added inside the building prior to discharge to the irrigation pond. In the past, soda ash was added directly to the
pond but this process was stopped in December 2017 in favor of adding liquid caustic.
The flow meter was calibrated by NIAGRA meters on 9/19/17.
The Operation & Maintenance Plan – Update to include the following:
1.Operational Functions – include daily/weekly tasks (i.e. recording pond freeboard, monitoring irrigation field for runoff)
2.Maintenance Schedules – include frequency of pump and blower maintenance
3.Spill Response Plan – include a list of materials available for cleanup
Mike’s Septic hauled wastewater during the spring/summer of 2018 because the irrigation pumps were down. A new
irrigation pump was installed June 21, 2018. The facility should purchase a second backup pump in the event the first one
goes down.
An Industrial Pump & Haul permit was requested in June 2018. That permit expired June 30, 2018 per Metropolitan
Sewerage District (MSD), the receiving facility. Any future Industrial Pump & Haul permits will require a new receiving facility
acceptance letter.
The receiving crop is fescue grass. Although most of the sprayfield has a good stand of grass, there are areas that contain
more weeds than grass. This was noted during the last two inspections. According to the ORC, the Henderson County
Cooperative Extension Service was contacted for recommendations for controlling weed growth. Those areas of the
sprayfield that contain an excessive amount of weeds should be addressed so that the entire field can accept and assimilate
wastewater. To ensure that the sprayfield contains needed acreage, reseeding does not have to be completed all at once.
The soils report was conducted 9/27/17. This soils report did not provide any fertilizer recommendations. The soils analysis
can be used as a diagnostic tool to identify nutrient deficiencies or excesses that may prevent optimal plant growth. It is
recommended that this analysis or additional samples be collected to help identify problems with the sprayfield (i.e. weed
growth).
Irrigation was occurring at the time of inspection.
The permittee is working with IMOCO, Inc. to design a system to prevent residual juice concentrate from leaking out onto
facility grounds from the disposal system.
The facility site map needs to be updated to reflect the addition of Monitoring Well (MW#1) as required by permit condition
Schedule I.2. The updated map should be submitted after completion of the groundwater investigation.
2L Groundwater Standard exceedances and GW-59 reporting issues will be addressed under separate cover from this
inspection report.
Page:2
DocuSign Envelope ID: 9669C43A-BCAA-460E-93CF-1454772A5AD1
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004967
07/25/2018 Compliance Evaluation
Alljuice Realty LLC
Routine
Type Yes No NA NE
Activated Sludge Spray, HR
Activated Sludge Drip, LR
Recycle/Reuse
Infiltration System
Single Family Drip
Reuse (Quality)
Single Family Spray, LR
Activated Sludge Spray, LR
Lagoon Spray, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
At the time of the inspection, one aerator was down and a second aerator stopped working. The
ORC notified the Asheville Regional Office (ARO) on August 2nd that both of those aerators
were repaired and operational.
Comment:
Record Keeping Yes No NA NE
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Page:3
DocuSign Envelope ID: 9669C43A-BCAA-460E-93CF-1454772A5AD1
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004967
07/25/2018 Compliance Evaluation
Alljuice Realty LLC
Routine
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
Effluent is also sampled for Ammonia, TDS, TSS, BOD, Chloride and TKN.
2L GW quality violations March 2018: MW#1 (Background) - Iron=11.2 mg/L; Manganese - 0.166
mg/L; pH=5.71 Std. Units; Fecal Coliform = <10 colonies/100 mls. MW#2 - Iron=6.84 mg/L;
Manganese=9.07 mg/L; Fecal Coliform= <10 colonies/100 mls; Ammonia Nitrogen=30.0 mg/L.
MW#3 - Iron=0.243 mg/L; pH=5.04 Std. Units; Fecal Coliform=<10 colonies/100 mls.
PAN records are not required.
GW-59 for March 2018: MW#2 - Ammonia Nitrogen showed 30 ug/l, lab sheet showed 30 mg/l;
Manganese showed 9.07 ug/l, lab sheet showed 9.07 mg/l
GW-59 for March 2018: MW#3 - Ammonia Nitrogen & Chloride were not included, Manganese
showed 0.46 ug/l, lab sheet showed 0.46 mg/l.
March 2018 NDMR was reviewed for accuracy.
Comment:
End Use-Irrigation Yes No NA NE
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# Info only: Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
The cover crop is not specified in the permit.
One sprayhead was not working at the time of operation.
Comment:
Page:4
DocuSign Envelope ID: 9669C43A-BCAA-460E-93CF-1454772A5AD1
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004967
07/25/2018 Compliance Evaluation
Alljuice Realty LLC
Routine
001 -
Treatment Lagoons Yes No NA NE
Lagoon Type Aerated
Primary/Secondary Primary
Influent structure
Banks/berms (seepage and erosion)
Vegetation (excessive vegetation on banks/berms)
Liner
Liner Type Unlined
Baffles/curtains
Freeboard Marker
Required freeboard 24
Inches
Actual freeboard 40
Inches
Are increments clearly marked on gauge at adequate intervals?
Has the water level gauge been surveyed w/ respect to lowest point on dike? wall?
No Evidence of overflow
Acceptable color
Floating mats
Excessive solids buildup
Aerators/mixers
Effluent structure
Lagoon cover
Page:5
DocuSign Envelope ID: 9669C43A-BCAA-460E-93CF-1454772A5AD1