Loading...
HomeMy WebLinkAboutNC0035149_Compliance Evaluation Inspection_20180807 STATF q /0.'",.., ,rye .4 40"ti ROY COOPER NORTH CAROLINA Governor Environmental Quality MICHAEL S.REGAN Secretary LINDA CULPEPPER Interim Director August 7, 2018 Mr. Mark Harrill Seven Devils Resort 151 Mr. Bish Blvd Boone, NC 28607 RECE9VED/DENWOW R SUBJECT: Compliance Evaluation Inspection AUG 14 2018 Seven Devils Resort WWTP Water Resources NPDES Permit No. NC0035149 permitting Section Watauga County Dear Mr. Harrill, On August 2, 2018, Kelli Park and Gary Hudson, of this office, met with Josh Cagle to perform a Compliance Evaluation Inspection on the Seven Devils Resort wastewater treatment system. Mr. Cagle was filling in for the operator in responsible charge (ORC); Steve Taylor. This type of inspection consists of two basic parts: an in-office file review and an on-site inspection of the treatment facility. The attached EPA inspection form notes the areas that were evaluated for this inspection. The findings and observations are outlined below: I I. Permit The NPDES permit became effective October 1, 2017, and expires September 30, 2022. The facility had a copy of the permit available during the inspection. II. Self-Monitoring Program A review of the monthly discharge monitoring reports (DMR) for the period January 2017 through August 2018 showed that the facility was not in compliance with all permit limits. While they were previously addressed before this letter, they are also listed in the table below. '1.1TiE ) NORTH CAROJNA DARItrunt W FmGamnmtal 0.v11� North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office 1450 Hanes Mill Road,Suite 300 I Winston-Salem,North Carolina 27103 336.776.9800 . Seven Devils Resort WWTP,August 2,2018 c. Parameter Violation Date Violation Type Fecal Coliform 11/21/2017 Daily Max. Exceeded Fecal Coliform 9/13/2017 Daily Max. Exceeded Fecal Coliform 8/22/2017 Daily Max. Exceeded Grab samples are taken by the ORC at the effluent outfall. These samples are put on ice and analyzed by Water Quality Labs in Banner Elk. III. Records/Reports The permit and visitation log are located on site and show visitation times and plant conditions. Chain of custody forms are in good order. All required monitoring was performed per the frequencies specified in the NPDES permit. Miss Park noted no data transcription discrepancies from bench sheets to DMRs in her documentation review. Water Quality Labs maintains the documentation. ' IV. Flow Measurement The flow is measured continuously by a v-notch weir with an ultrasonic sensor. The device was calibrated in July 2018. V. Operations and Maintenance The wastewater treatment plant appeared to be well maintained and operated. The ORC and backup ORC are sufficiently qualified to be running the plant. Mr. Cagle mentioned that the diffusers in the plant were recently cleaned to improve the dissolved oxygen levels in the aeration basin. VI. Facility Site Review All components of the 0.020 million gallons per day facility appeared to be functioning properly. The aeration basin had a light brown color and a good earthy odor. All blowers were functioning properly and there were no dead spots. The secondary clarifier looked clean, however it was discharging effluent with traces of pin floc. Effluent is disinfected with chlorine tablets and de-chlorinator tablets before leaving the plant. Mr. Cagle believes the pin floc to be an inflow and infiltration issue from the heavy rains over the two weeks prior to the inspection. He reported that the plant will normally fluctuate around 6,000-11,000 gallons of wastewater a day, but due to the rain the plant was reading 16,000 gallons of wastewater the day of the inspection and 27,000 gallons the next day (August 3rd). When Miss Park spoke with him on August 6th Mr. Cagle reported that there was no pin floc in the effluent, and that it was clear. 2 • Seven Devils Resort WWTP,August 2,2018 The blower house structure is weak and missing large sections of wall around the blowers. It is recommended that this is repaired or a new structure is built to protect the blowers and be safer for the operators. A few areas in the metal walkway over the plant were weak. It is recommended that those sections be replaced with new metal panels for safety purposes. VII. Effluent/Receiving Waters The effluent from the facility was clear, but had pin floc in it the day of the inspection. Effluent is discharged into an unnamed tributary to the Watauga River, class C; trout waters in the Watauga river basin. There was no odor associated with the effluent. VIII. Sludge Maintenance and Handling Sludge was reported to be pumped about once a year due to low flow in the plant. Triple T Plumbing pumps the sludge and the time, date, and how much was pumped is recorded into the operator log on site. It is also documented at Water Quality Labs. IX. Conclusions The compliance evaluation inspection is satisfactory. Mr. Cagle maintains and operates the facility in a good manner. His efforts to comply with the permit are appreciated. If you have any questions regarding the inspection or this report, please contact Kelli Park or me at (336) 776-9800. Sincerely, Sherri V. Knight, P.E. Regional Supervisor Water Quality Regional Operations Division of Water Resources Attachments: BIMS EPA Water Compliance Inspection Report cc: Central Files WSRO C......._____--NPDES Unit 3 L. United States Environmental Protection Agency Form Approved EPA Washington,D C 20460 OMB No 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A National Data System Coding(i e,PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 �,,, L 2 [ I 3 I NC0035149 111 12 1 18/08/02 117 18 I,.I 19 1 S I 201 I 21111111 111 111 111 11 1 11 1111 `1 1 11 111 j 111111 11 I 1166 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved — 67I I 70I I 71 I 1 72 1 N I 731 1 174 751 1 1 1 1 1 1 180 Section B Facility Data Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 11 30AM 18/08/02 17/10/01 Seven Devils Resort 216 Hardin St Box F-1 Exit Time/Date Permit Expiration Date Blowing Rock NC 28605 12 00PM 18/08/02 22/09/30 Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data /// Joshua Kenneth Cagle/ORC/826-898-6277/ Name,Address of Responsible Official/Title/Phone and Fax Number Contacted Randy Carter,151 Mr Bish Blvd Boone NC 28607//828-963-7600/ No Section C Areas Evaluated During Inspection(Check only those areas evaluated) ▪ Permit • Flow Measurement • Operations&Maintenance • Records/Reports ▪ Self-Monitoring Program • Facility Site Review • Effluent/Receiving Waters Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date Gary Hudson Division of Water Quality//336-776-9694, Kelli A Park ' Q /pe WSRO WQ//336-776-9689/ vex_ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date EPA Form 3560-3(Rev 9-94)Previous editions are obsolete Page# 1 NPDES yr/mo/day ' Inspection Type 1 31 NC0035149 111 121 18/08/02 117 18 I—I C I Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) it Page# 2 lis- Permit: NC0035149 Owner-Facility: Seven Devils Resort Inspection Date 08/02/2018 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping'? • ❑ 0 0 Does the facility analyze process control parameters,for ex MLSS, MCRT, Settleable • 0 ❑ 0 Solids, pH, DO, Sludge Judge, and other that are applicable'? Comment The blower building needs upgraded as it is falling aparet and is missing large sections of siding Weak spots in the metal walkways over the plant Permit Yes No NA NE (If the present permit expires in 6 months or less) Has the permittee submitted a new ❑ ❑ • ❑ application'? Is the facility as described in the permit'? • 0 ❑ ❑ #Are there any special conditions for the permit'? 0 MI 0 ❑ Is access to the plant site restricted to the general public'? U ❑ ❑ ❑ Is the inspector granted access to all areas for inspection'? • ❑ 0 0 • Comment Record Keeping Yes No NA NE Are records kept and maintained as required by the permit'? • 0 ❑ ❑ Is all required information readily available, complete and current'? • ❑ 0 ❑ Are all records maintained for 3 years(lab reg required 5 years)' I ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑ Is the chain-of-custody complete'? • 0 ❑ ❑ Dates, times and location of sampling • Name of individual performing the sampling IN Results of analysis and calibration • Dates of analysis II Name of person performing analyses MI Transported COCs MI Are DMRs complete do they include all permit parameters'? • ❑ ❑ 0 Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ■ ❑ (If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ • 0 on each shit? Is the ORC visitation log available and current'? M ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification'? • ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification'? • ❑ ❑ ❑ Is a copy of the current NPDES permit available on site'? • ❑ 0 ❑ Page# 3 m Permit. NC0035149 Owner-Facility. Seven Devils Resort Inspection Date: 08/02/2018 Inspection Type Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? ❑ ❑ • ❑ Comment. _ Bar Screens Yes No NA NE Type of bar screen a Manual • b.Mechanical 0 Are the bars adequately screening debris? • ❑ 0 0 Is the screen free of excessive debris'? • 0 0 ❑ Is disposal of screening in compliance? • ❑ 0 ❑ Is the unit in good condition'? • ❑ ❑ 0 Comment. _ Aeration Basins Yes No NA NE Mode of operation Ext Air Type of aeration system Diffused Is the basin free of dead spots'? • ❑ ❑ ❑ Are surface aerators and mixers operational'? • ❑ 0 0 Are the diffusers operational'? • ❑ ❑ ❑ Is the foam the proper color for the treatment process'? • ❑ ❑ ❑ Does the foam cover less than 25%of the basin's surface'? • 0 0 0 Is the DO level acceptable'? • ❑ 0 0 Is the DO level acceptable?(1 0 to 3 0 mg/I) • ❑ 0 ❑ Comment _ Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater'? • ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier'? • Cl ❑ ❑ Are weirs level'? • ❑ 0 ❑ Is the site free of weir blockage'? • ❑ ❑ ❑ Is the site free of evidence of short-circuiting'? • ❑ ❑ ❑ Is scum removal adequate'? • ❑ ❑ ❑ Is the site free of excessive floating sludge'? • ❑ ❑ ❑ Page# 4 Permit. NC0035149 Owner-Facility Seven Devils Resort Inspection Date: 08/02/2018 Inspection Type: Compliance Evaluation Secondary Clarifier Yes No NA NE Is the drive unit operational? • 0 0 0 Is the return rate acceptable(low turbulence)' • 0 ❑ ❑ Is the overflow clear of excessive solids/pin floc'? 0 • ❑ ❑ Is the sludge blanket level acceptable'? (Approximately%4 of the sidewall depth) • ❑ 0 0 Comment Pin Floc being discharged day of inspection Disinfection-Tablet Yes No NA NE Are tablet chlorinators operational'? • ❑ 0 ❑ Are the tablets the proper size and type'? • ❑ ❑ ❑ Number of tubes in use'? 2 Is the level of chlorine residual acceptable'? • ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup'? • ❑ ❑ ❑ Is there chlorine residual prior to de-chlorination? ❑ ❑ ❑ • Comment. De-chlorination Yes No NA NE Type of system'? Tablet Is the feed ratio proportional to chlorine amount(1 to 1)7 U ❑ ❑ El Is storage appropriate for cylinders'? 0 ❑ U ❑ #Is de-chlorination substance stored away from chlorine containers'? ❑ ❑ MI ❑ Comment. _ Are the tablets the proper size and type? • ❑ 0 ❑ Are tablet de-chlorinators operational'? • El El El Number of tubes in use'? 1 Comment also throws in loose de chlorination tabs Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained'? • ❑ 0 ❑ Are the receiving water free of foam other than trace amounts and other debris'? • ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly'? U ❑ ❑ ❑ Comment effluent had some pin floc in it Page# 5