Loading...
HomeMy WebLinkAbout20180455 Ver 1_More Info Received_20180808C. MICHAEL ALBERTO, III, P. E., PLLC LICENSE NO. P-1753 58020TH AVENUE COURT NW HICKORY N C 28601 CIVIL ENGINEERING STRUCTURAL ENGINEERING SITE PLANNING CONSTRUCTION CONSULTANT Rodgers Mechanical, Inc. Mechanical Office PO Box 2403 Boone, NC 28607 RE: Rogers Mechanical Storage Buildings at 176 IJ Bingham Place Boone, NC 28607 Mr. Rogers, Mr. Seldomridge, et all, PHONE 919-621-7667 FAX 828-327-3188 cmichael.alberto@gmail.com 7-23-2018 Below find the requisite project calculations requested and associated attachments. PROJECT CALCULATIONS Method: Rational Method Site Information: 1. Site Location: Watauga County 2. Hydroligic Soil Group Gravelly Sandy Loam: B 3. Site paved with lined and vegetated swales 4. Average Site Slope: 1 1/2% (Use 3% for calculations, conservative) 5. 3.476 acres in site 6. 24%, 0.834 acres contributing runoff a. This estimate is conservative since much of the existing development does not drain through proposed swale. 7. Off-site runoff into project area, i.e. runoff from woods into swale at south end of site. a. Existing topography has a slope break at the road to the south of the site. Drainage to the south of the road ends up in the existing seasonal stream by way of existing DOT installed culvert. b. For analysis of swale erosion potential assume that the remainder of the area between the site and the road drains into the swale. Most of the drainage path between the road and the swale is on the order of 5% slope with steeper slopes (20%+/-) near the road over approximately 10 to 20 feet horizontal to the north of the road. Assume 10% average slope, conservative. c. Offsite drainage area is 1.55 acres between site swale and road to south of the site. (see attached sketch). Off Site Contributing Runoff to Swale at Node B - Average Velocity = 0.85 ft/sec (See attached sheet 1) Distance to Node B via Path 4 = 525 feet (See attached sheet 3) Time of Concentration = 10.29 minutes 10 year Rain Intensity (i) = 6.00 inches/hr (See attached sheet 2) - Runoff Coefficient ( C ) = 0.2 (for forested land) - Tributary Acres (A) = 1.55 acres (See attached sheet 3) Flow from Path 4 to Node B = CiA = 1.86 CFS On Site Contributing Runoff to Swale at Node A - Average Velocity = 3.75 ft/sec (See attached sheet 1, Slope Conservative) - Distance to Node A via Path 1 = 375 feet (See attached sheet 3, Path 1 Conservative) - Time of Concentration = 1.67 minutes - 10 year Rain Intensity (i) = 7.50 inches/hr (See attached sheet 2) - Runoff Coefficient ( C ) = 0.9 (for Asphalt Pavement) - Tributary Acres (A) = 0.834 acres (See attached sheet 3) Flow from Path 1 to Node A = CiA = 5.63 CFS Swale Runoff to Node B - Swale width = 20' - Swale Length (Path 3) = 375' - Average Velocity = 2.8 ft/sec (See attached sheet 1, Slope Conservative) - Distance to Node B via Path 3 = 375 feet (See attached sheet 3, Path 1 Conservative) - Time of Concentration = 2.23 minutes - 10 year Rain Intensity (i) = 7.50 inches/hr (See attached sheet 2) - Runoff Coefficient ( C ) = 0.25 (for Grass Swale) - Tributary Acres (A) = 0.172 acres (See attached sheet 3) Flow from Path 3 to Node B = CiA = 0.323 CFS Max CFS at Node A = 5.63 CFS Max CFS at Node B = 7.813 CFS Channel Flow Capacity and Bed Shear - At Node A Swale Section is 2'-0" bottom 1'-0" deep with 3:1 side slopes. Channel Bed Slope Assumed is 3%, Conservative. Manning n value = 0.025 Resulting Flow = 5.656 cfs Velocity = 4.415 ft/sec - At Node B Swale Section is 2'-0" bottom 3'-0" deep with 3:1 side slopes. Channel Bed Slope Assumed is 3%, Conservative. Manning n value = 0.025 Resulting Flow = 7.808 cfs Velocity = 4.872 ft/sec Flow Area = 1.603 ft/12 Wetted Perimeter = 4.924 ft Hydraulic Radius = 0.326 ft Tractive Force, tau = 0.933 psf (double check with alternate calculation below) - At Node B Swale Section is 2'-0" bottom 3'-0" deep with 3:1 side slopes. Channel Bed Slope Actual 0.5%. Manning n value = 0.025 Resulting Flow = 8.034 cfs Velocity = 2.6356 ft/sec Area Flow = 3.0483 ft/12 Wetted Perimeter = 6.1382 Hydraulic Radius = 0.496 ft Use conservative results at 3% slope at Node B above for calculation of bed shear capacity required for Swale liner. CLIENT: Rogers Mech JOB NO.: Jul - PROJECT: Storage Building Site DESIGNER: CMA DATE: 18 Jul - SUBJECT: Bed Shear Calculation for Liners CHECKER: CMA DATE: 18 Use worst case at 4.872 ft/sec at node B and 3% slope, Bed Shear Calculation Conservative UNITS Feet, sec, radians, and lbs 4.872 ft/s Velocity KEY Input Output Channel Slopes Channel Bed Slope Comments and Definitions So 0.030000 ft/ft Riverbed Slope, Direction of Flow Sf 0.030000 ft/ft Energy Grade Line Bank Slope H V 3 1 feet Design Shear Stress, (See Drawings for details) Channel Geometry Comments and Definitions b 2.00 feet Width of Channel Base, See attached Channel Yo 0.5 feet Depth of flow 2 0.333 ratio Side slope ratio Flow A 1.60 ft^2 Area P 4.92 feet Wetted Perimeter R 0.326 feet Hydraulic Radius Gamma 62.4 ft^3 Weight of water Bed Shear Ides 0.609 psf Design Bed Shear TC 2.00 psf Critical Bed Shear (Per Liner Brochure for SC150) 3.28 OK Factor of Safety Max FS 2.14 OK Factor of Safety Min Conclusion: 3% slopes are well in excess of those that will be provided in channels at the Storage building site. Actual slopes will tend toward 0.5% in swale and 1.5% max on pavement. Therefore, time of concentration utilized for calcs is conservative. Therefore, required flow capacity is conservative. Therefore, velocity is conservative. Even with conservative formulation, bed shear capacity of SC150 liner is more than adequate. No erosion should be expected in the swale, or at the swale transition to the seasonal stream with use of SC150 liner. Arrangements shall be made to minimize erosion at swale to stream intersection with the same liner wrapped around corner of intersection. After pipe removal to 49 feet remaining, seasonal stream shall also be outfitted with SC150 liner to prevent erosion of stream banks until vegetation takes root. Once vegetated, bed shear capacity can be expected to exceed 10 psf. Attachments: 1. Velocity 2. Rain Intensity Boone, NC 3. Drainage Area and Flow Paths for Time of Concentration 4. Vmx SC150 brochure with Bed Shear Capacity IF YOU SHOULD HAVE ANY QUESTIONS PLEASE GIVE ME A CALL. THANK YOU, C. MICHAEL ALBERTO, PE Hydrology _P A 7 O Fe 7-F-7 c•t.- IA t ■■■■■■■■�■■■►�t�■■t■�■■ice■■FAS INA no m IS ■■�tt�■m��■ ■■■■■■■■IIINII111111 ■I■■/■■/■11111► Imo■ ' ■■■■O�I�Ilillllll �■/I■!/��%IIII,1� /■ ■■■■1111111111, , I■%1111111 ,iiia■ - - �■■1111��lI .,�I -, �I►1111' I��IIII�1 + ��i•___■if_ Ola J•�I__is i__a�_ 01100 so .iiii • �__� __iiiiiii_� _.[. I___ lit._./..01 OWES �I_ loan ■■■■■ ,��1 A _ .; I_ ,/��■11111111■■ ' ■■■■ ,/� ail •� - /I/��������II�■■ ' ■■■ ,11 ',i • ' . /11111111111111■ ■■ ..1 ',1 I IN IN no WA a 00 W 0 MOM mom MEN IWO Wj IIIIIIII�■ ill /�I. SII► �Iliilllllllllllll�l TFFT 3 .3 .2 2 X4 .1 1 .1 .2 .3 .5 1 2 3 5 10 20 V � veLocrnr, v (Ft. sec.) J t Al A S . Figure 1 Shallow Concentrated Flow Velocities Hydraulics Manual we's Table 8.03c,- Intensity Duration fMggency ARI* 5 min. 10 min. For use with Rational Metnocr' 30 min. 60 min. 120 min. 3 hr. Urg Y RlQ h Carolina 35.0261N,84.0239W (years) ARI* 6 min. 10 min. 15 min, 30 min. 60 min. 120 min. 3 hr. 6 hr. 12 hr. 24 hr. (years) 2.41 0 1.51 0.89 M3 0.38 0.24 0.14 10 2 4.93 3.94 3.30 2.28 1.43 0.89 0.62 0.38 0.24 0.15 10 6.78 5.42 4.57 3.31 2.16 1.29 0.92 0.55 0.34 0.21 25 7.90 6.29 5.31 3.94 2.62 1.57 1.13 0.68 0.41 0.25 100 9.62 7.64 6.44 4.93 3.40 2.06 1.50 0.90 0.53 033 ARI* 5 min. 10 min. 15 min. 30 min. 60 min. 120 min. 3 hr. 6 hr. 12 hr. 24 hr. (years) 2 5.21 4.16 3.46 2.41 0 1.51 0.89 M3 0.38 0.24 0.14 10 7.06 5.65 4.76 3.45 2.25 1.30 0.91 0.55 0.34 0.20 25 8,09 6.44 5.45 4.03 2.69 1.56 1.10 0.66 0.40 0.24 100 9.68 7.69 6.48 4.96 3.42 2.00 1.43 0.86 0-50 0.30 ARI* 5 min. 10 min. 15 min. 30 min. 60 min. 120 min. 3 hr. 6 hr. 12 hr. 24 hr. (years) 2 5.71 4,57 3.83 164 1.66 1.00 0.72 0.48 0.31 0.18 10 7.50 6.00 5.06 3.67 2.39 1.46 1.06 0.69 0.44 0.28 25 8.59 6.85 5.78 4.28 2.85 1.77 1.29 0.83 0.52 0.34 100 10.38 8.25 6.95 5.32 3.67 2.35 1.72 1.08 0.65 0.44 ARI* 5 min. 10 min. 15 snip. 30 min. 60 min. 120 min. 3 hr. 6 hr. 12 hr. 24 hr. (years) 2 5.68 4.54 3.80 2.63 1.65 0.96 0.68 1 0.41 0.24 0.14 10 7.26 5.80 4.89 3.55 2.31 1.36 0.98 0.59 0.35 0.20 25 8.02 6.38 5.40 4.00 2.66 1.59 1.15 0.70 0.42 0.24 100 9.00 7.15 6.03 4.62 3.18 1.93 1.43 0.87 0.53 0.30 ARI* 5 min. 10 min. 15 min. 30 min. 60 min. 120 min. 3 hr. 6 hr. 12 hr. 24 hr. i (years) 2 5.46 4.36 3.66 2.52 1.58 0.93 0.66 0.40 0.23 0.14 10 6.85 5.48 4.62 3.35 2.18 1.30 0.92 0.56 0.33 0.20 25 7.39 5.89 4.98 3.69 2.46 1.49 1.06 0.65 0.39 0.23 100 7.93 6.30 5.31 4.07 2.80 1.75 1.24 0.78 0.48 0.29 ARI is the Average Return Interval. ** Intensity Duration Frequency table is measured in inches per hour, 8.03.8 Rev. 6106 A 11 E; I H vF f II r I � r m z a_ 0 N DO a .y / � 0 n �0 '01 °4� 'g4:6- '1 o � s t71 H vF H t � a_ 0 N DO a .y / � a S II°u -m m o3 v ftl COVER M1]5" MIN m a 6° WAX a 0 n �0 '01 °4� 'g4:6- '1 o � s t71 61mimammwmovA �:moi► 0 H vF H t i3 a_ 0 y .y / � a o3 a i 0 � a z a H 0 Z ? W m cn 2 h d 0 ,I c *i m —1 t 61mimammwmovA �:moi► 0 ee; / H H H t i3 y .y / � a a i 0 � a z a H 0 Z ee; / H H / � a i 0 a c §E MICHAEL ALBERTO, PE PLLC ���Jf�,A �p � � NpEw/'�sTOpR�ncc oui�oiwqq �� //��Fp rz: �g y�v CIVIL ENGINEERING V ROGERS MECHY1N�liA� '� E gE p� ! ILSE No P ':.5 STRUCTURAL ENGINEERING �� m Z P U 20th AVENUI COURT NVV tP6 I.J. BINCHAM PL BOONE, NO 26607 Mq� HICKORY, NC 28601 SITE PLANNING PHONE: 919-621-7667 i( -,I berto®gmiI com CONSTRUCTION CONSULTANT I„ 0 c m cn 2 0 c m §E MICHAEL ALBERTO, PE PLLC ���Jf�,A �p � � NpEw/'�sTOpR�ncc oui�oiwqq �� //��Fp rz: �g y�v CIVIL ENGINEERING V ROGERS MECHY1N�liA� '� E gE p� ! ILSE No P ':.5 STRUCTURAL ENGINEERING �� m Z P U 20th AVENUI COURT NVV tP6 I.J. BINCHAM PL BOONE, NO 26607 Mq� HICKORY, NC 28601 SITE PLANNING PHONE: 919-621-7667 i( -,I berto®gmiI com CONSTRUCTION CONSULTANT *0�11, ROLLMA?CTM V� ROLLED EROSION CONTROL ROLLED EROSION CONTROL SYSTEMS BROCHURE EroNet" SC1501 Extended -Term Photodegradable Double -Net Straw/Coconut Blanket With a layer of 70% straw and 30% coconut fiber stitched between a heavyweight UV -stabilized polypropylene top net and a lightweight photodegradable polypropylene bottom net, the SC150® ECB has increased durability, erosion control capabilities and longevity. It is suitable for steeper slopes, medium -flow channels and other areas where it may take vegetation up to 24 months to grow in. EroNet'" S1501 Short -Term Photodegradable Double -Net Straw Blanket The 5150 ECB is made with a 100% straw fiber matrix stitched between lightweight photodegradable polypropylene top and bottom nets. The S750 ECB's double -net construction has greater structural integrity than single net blankets for use on steeper slopes and in channels with moderate water flow. It provides erosion protection and mulching for up to 12 months. Every site has its own unique characteristics and challenges. EroNet Erosion Control Blankets are available in varying longevides to suit a variety of scenarios and conditions. EroNet"' DS150- Ultra Short -Term Photodegradable Double -Net Straw Blanket The DS150" ECB is suitable for high maintenance areas where close mowing will occur soon after installation. Special additives in the thread and top and bottom net ensure it degrades in adequate sunlight within 60 days. EroNet" S750 Short -Term Photodegradable Single -Net Straw Blanket The S75® ECB protects and mulches moderate slopes and low -flow channels in low maintenance areas for up to 12 months. It is constructed of 100% straw fiber stitched with degradable thread to a lightweight photodegradable polypropylene top net. EroNet'" DS75'" Ultra Short -Term Photodegradable Single -Net Straw Blanket Designed for high maintenance areas where close mowing will occur soon after installation, the DS75'" ECB degrades within 45 days because of special additives in the thread and top net that facilitate rapid breakdown in adequate sunlight. With our Erosion Control Materials Design Software (ECMDS), you can select either short-term, extended -term or long-term EroNet blankets based on your specific design needs. 7 1.6 v 0 0 r� 0 F71 D cn O C /) C C7 r� D D z r� FT -1 FT -1 0CTD D C/) C /) O z o c7 0 o CD N C D Q �\ cN0 0 C,71 6' O O J 277 CJS � TI N p N o n C C O cD 290,E DO O rT1ZE CD 9 F eJ m � C0 CD � = � C-) ` U' OCL N�7 O Q O V W CD 0 0 C� z- o (-D �c� c o • \ 606,, � cr co O O X 0 � � n CD O� O N 77 C 9 I s/%F y m � / 1/0 00 G-) CCD \ Tl z FT -1 / FM D o / z FT c� z ti o = � / � � cn � y Z G7 � F7-1 z O FT i / � � � D c� ➢ / m / cn 77 m o cm-) \ . \ s 29°17' FT -1 c�' / 2900CD / vC / zQ Q sC z W F N No o� / � m o� Q FF]�� , cf) Oo 0 II � F� C/') 60 �� FFF o z / 0' // \ 71 / \ c/) � / Cl) � / o / z X r o C / / I N 07°210099 / o00 / o /0� o, 71_84' F7-10 0 / D \ D C C J F7l \ F / Q0 Q = r CD iv � ---]00 s -91 '10 Sg00 , m r- � �Q Q \ o J � 0 c� S 05°49'00 W C \ 68.85' / �, o ➢C) � Fri O o CD 96,_8„ o O O D m O G7 y y � m � z cn CTI) � y m C FT -1 O rTrn 0 = o Q x � X F l 0 � �. O zz m�z n -0— o G7 n o Q 0 � � v) FTl Z F— G7 v7 O N Qo m Z COQ 0 Z C 0 N0 00 C CD CID 70 FT -1 o � � � � O -T3 cf) Cb c� � Q O N Q OOQ � CD ,. J o � C� D O O � CD F o O J CD Ln c�Fr-1 00Frl 77 �d n Frl rTi (D 0 N X W cli V) m m m� MICHAEL ALBERT PE,PLLCCIVIL ENGINEERING VO z _� mm NAcn ,� v' N -� Q o r� NEW STORAGE BUILDINGS FOR: 0 W m�DmO �mn �-o crIn �-o o) CD = C) C D Flt _ ���o� �ocZi� � o oy� coo � s s �' 'S z ROGERS MFICHANCALW��� "" ' � �� �o LICENSE No. P 1 753 STRUCTURAL ENGINEERING e�� (:) = r z 0 0 � F-- ozoo= o�zN o �.� 580 20th AVENUE COURT NW N m rT, ,�z� �m� Q �� SITE PLANNING Frl m� n 176 I.J. BINGHAV PL BOONE, NC 28607 ��� r- q= rno HICKORY, NC 28601 �= �mm o PHONE: 91 9-621 —667 � rTi r, i O – CD Z) c � co o�„ o � �K��0 z„� Q zm� �� o cmichcel.clberto@gmclI.com CONSTRUCTION CONSULTANT I I j I I � I I -Tl N C7 C� � fTl � x C3� Q � O I -Tl Z I -Tl � � � c.� ITl ITl � (/') D Z77 CO �7 O �J C O �fTl � I��Tl F-- D CD D � � z TI TI Tl 0 I I z z z D Cp ITl ITl ITl � FT -1 rTl � Co Co � � m z C II c � � II II II � � co co ITl = n = D Csl O O �"� � D r� z O z C x r� C 0 0 FT -1 � 0 o z O II � � � II � II � o � � II II II o c� o r � � � c� 0 0 0 `o IT1 z z � rn � � O z C � C D z 0 Lfl G� c� O o cfl cfl r� � Z II � rT� z � N O � O7 N \I D c9 D � II v 0 0 r� 0 F71 D cn O C /) C C7 r� D D z r� FT -1 FT -1 0CTD D C/) C /) O z o c7 0 o CD N C D Q �\ cN0 0 C,71 6' O O J 277 CJS � TI N p N o n C C O cD 290,E DO O rT1ZE CD 9 F eJ m � C0 CD � = � C-) ` U' OCL N�7 O Q O V W CD 0 0 C� z- o (-D �c� c o • \ 606,, � cr co O O X 0 � � n CD O� O N 77 C 9 I s/%F y m � / 1/0 00 G-) CCD \ Tl z FT -1 / FM D o / z FT c� z ti o = � / � � cn � y Z G7 � F7-1 z O FT i / � � � D c� ➢ / m / cn 77 m o cm-) \ . \ s 29°17' FT -1 c�' / 2900CD / vC / zQ Q sC z W F N No o� / � m o� Q FF]�� , cf) Oo 0 II � F� C/') 60 �� FFF o z / 0' // \ 71 / \ c/) � / Cl) � / o / z X r o C / / I N 07°210099 / o00 / o /0� o, 71_84' F7-10 0 / D \ D C C J F7l \ F / Q0 Q = r CD iv � ---]00 s -91 '10 Sg00 , m r- � �Q Q \ o J � 0 c� S 05°49'00 W C \ 68.85' / �, o ➢C) � Fri O o CD 96,_8„ o O O D m O G7 y y � m � z cn CTI) � y m C FT -1 O rTrn 0 = o Q x � X F l 0 � �. O zz m�z n -0— o G7 n o Q 0 � � v) FTl Z F— G7 v7 O N Qo m Z COQ 0 Z C 0 N0 00 C CD CID 70 FT -1 o � � � � O -T3 cf) Cb c� � Q O N Q OOQ � CD ,. J o � C� D O O � CD F o O J CD Ln c�Fr-1 00Frl 77 �d n Frl rTi (D 0 N X W cli V) m m m� MICHAEL ALBERT PE,PLLCCIVIL ENGINEERING VO z _� mm NAcn ,� v' N -� Q o r� NEW STORAGE BUILDINGS FOR: 0 W m�DmO �mn �-o crIn �-o o) CD = C) C D Flt _ ���o� �ocZi� � o oy� coo � s s �' 'S z ROGERS MFICHANCALW��� "" ' � �� �o LICENSE No. P 1 753 STRUCTURAL ENGINEERING e�� (:) = r z 0 0 � F-- ozoo= o�zN o �.� 580 20th AVENUE COURT NW N m rT, ,�z� �m� Q �� SITE PLANNING Frl m� n 176 I.J. BINGHAV PL BOONE, NC 28607 ��� r- q= rno HICKORY, NC 28601 �= �mm o PHONE: 91 9-621 —667 � rTi r, i O – CD Z) c � co o�„ o � �K��0 z„� Q zm� �� o cmichcel.clberto@gmclI.com CONSTRUCTION CONSULTANT I I j I I � I I -Tl N C7 C� � fTl � x C3� Q � O I -Tl Z I -Tl � � � c.� ITl ITl � (/') D Z77 CO �7 O �J C O �fTl � I��Tl F-- D CD D � � z TI TI Tl 0 I I z z z D Cp ITl ITl ITl � FT -1 rTl � Co Co � � m z C II c � � II II II � � co co ITl = n = D Csl O O �"� � D r� z O z C x r� C 0 0 FT -1 � 0 o z O II � � � II � II � o � � II II II o c� o r � � � c� 0 0 0 `o IT1 z z CD � N D Lfl G� c� o cfl cfl r� � Z II o N O O7 N \I D c9 II mz I I L� D CD x � � o n � O z � Cp � D D � D C z G7 c � z � = n = D D O � z C � D � z O z II II II O O o � 0 0 0 D G� c� o 0 0 Z D O7 N \I D V mz I I � x � D_ Cp D C z G7 c � O � C z G� c� o 0 0 0 O7 N \I D V D C c/) F -- C) m I .. o � 9" MIN �, � D z � z O DU N C CDJ O F7 F -- Fm o m aF7-1 D m 7-1 F7 z C/-) c7 m m m z 0 z m C./) O F-- --u O m _ I m 0 0 _ o � cn 00 N IV o� O O 0 --0 O O T-1 -r-1 � C7 D C C DC7 FT -1 m z = rC O c/) C c/) c--, OC o z FT -1 D rT-1 C7 C C1) F— Co D rzC7 I'I a C D FT-1FF] F— D c� F-- � � cr I /lJ II � o IIv I 0 0 71 oCD I� O O FF] z D z o � I� z o � m FT -1 z m m = CD z z � o � CD z m � CD m m m z cn n n �U m c" o O C z � o z m Iv O VARIES Ir 6" MIN. ZE D C/� m C7 C./) Cs C7 O Cn O F -- CD --o z z a m z 70 F7 - J IV c/) 77 D 0 z � D SCJ C/� m � 3'-0" m D m D cn n m O N x LIA Cli 2 m r-1 m� _ MICHAEL ALBERTO,PE.,PLLCC)m� C -)M m �`N o �� ��� " CIVIL ENGINEERING o z NEW STORAGE BUILDINGS �ORe D��- "' o � ��-0:;0 maw o O c� �_ co 0 0 Fl -1 < z ROGERS VECHANCALW��z " �� CD LICENSE No. P— 1 753 STRUCTURAL ENGINEERING cn G7 ° = c7 G� � n = m 0 z oz o o ozoocn �oZ Q= o �.= 580 20th AVENUE COURT NW F S S I�� z D CD W cin 12 �' a coo W� 176 I.J. BINGHAM PL BOONE, NC 28607 mgr m HICKORY NC 28601 SITE PLANNING CD m D °�C) o�z W PHONE: 91 9-621 —7667 CONSTRUCTION CONSULTANT ON C� r���o z„� Q r mm� moo o � z �� o cmichael.alberto@gmail.com Strickland, Bev From: Sean Martin <sean@cws-inc.net> Sent: Wednesday, August 08, 2018 1:34 PM To: Homewood, Sue; Fuemmeler, Amanda J CIV (US) Cc: Justin Rogers; John Seldomridge; Charles Alberto Subject: Re: [External] Fwd: Update on 404/401 re -submittal Attachments: Rogers Mech Storage Building Permit Drawings Rl_7-27-2018.pdf; Roger Mechanical Calculations 7-27-2018.pdf Report Spam. Please find attached the revised plans for the Roger's Mechanical project in Watauga County, which have reduced the proposed permanent stream impacts. Also attached are the supporting calculations for the vegetated swale. If the permittee has reduced the permanent stream impacts and the associated trout buffer clearing to approximately 50 If for the entrance drive, and the permittee intends to replant any previously cleared trout buffer areas, is a trout buffer variance still required for the project? Thank you, On Tue, Jul 10, 2018 at 9:49 AM, Homewood, Sue <sue.homewood@ncdenr.gov> wrote: Sean, I can issue a 401 once all my questions/concerns have been addressed and the applicant has submitted their application for the trout buffer variance. Let me know if you habe any other questions Sent from my Verizon, Samsung Galaxy smartphone Original message From: Sean Martin <sean@cws-inc.net> Date: 7/9/18 8:19 AM (GMT -05:00) To: "Homewood, Sue" <sue.homewood@ncdenr.gov> Subject: [External] Fwd: Update on 404/401 re -submittal ---------- Forwarded message ---------- From: Fuemmeler, Amanda J CIV (US) <Amanda.Jones@usace.army.mil> Date: Fri, Jul 6, 2018 at 10:22 AM Subject: Update on 404/401 re -submittal To: Justin Church <iustin@brec.biz> Cc: Sean Martin <sean@cws-inc.net> Justin, I'm just following back up since our last meeting back in May. I have not received any updated plans or revised permit application per our discussions. Please let me know where you are with this. I'll have to send out another notice of violation letter unless you plan on sending that information soon. Amanda Jones Regulatory Specialist U.S. Army Corps of Engineers Asheville Regulatory Field Office 151 Patton Avenue, Room 208 Asheville, NC 28801-5006 828-271-7980 ext. 4225 Sean Martin Sr. Scientist Carolina Wetland Services, Inc. 550 E. Westinghouse Boulevard Charlotte, NC 28273 Phone: 704-527-1177 Cell: 828-719-1320 Fax: 704-527-1133 i www.cws-inc.net Sean Martin Sr. Scientist Carolina Wetland Services, Inc. ....1'Ga�wZaB iwaocvt� �'ioo.o-H.fXar,ly 550 E. Westinghouse Boulevard Charlotte, NC 28273 Phone: 704-527-1177 Cell: 828-719-1320 Fax: 704-527-1133 www ewc-ine net