HomeMy WebLinkAboutNCG510500_Compliance Evaluation Inspection_20180802ROY COOPER
covn"4w
MICHAEL S. BEGAN
Ser ---Y
LINDA CULPE<PPLP,
hrrerfrA &[rector
Mr. Frank Craven, President
General Store of Denver
6360 NC Hwy 150 East
Sherrills Ford, North Carolina 28673
Dear Mr. Craven:
NORTH CAROLINA
btlo ronmantaf QuaNty
August 2, 2018
Subject: Compliance Inspection
General Store of Denver
Permit #NCG510500
Groundwater Remediation
Denver, Catawba County
On July 31, 2018, staff of the Mooresville Regional Office (MRO) completed a Compliance
Evaluation Inspection of the remediation system at the subject site to determine compliance with
remediation activities as per permit NCG510500. The system is back online and performing at
levels consistent with the active permit for this facility. The MRO would like to thank Matt
Westendorf of Hart and Hickman for his time during the inspection.
The attached inspection report should be self-explanatory. Should you have questions with the
report or the findings listed herein, please contact Edward Watson by phone at (704) 235-2198
or email (edward.watson(a ncdenr.gov).
Sincerely,
DocuSigned by:
F161F669A2D84A3...
Andrew H. Pitner, P.G.
Assistant Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources
Attachment: NCG510500 Compliance Inspection Report 2018
CC: Steve Libby, Hart and Hickman (email)
DWR files (Laserfiche)
EQ>
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 I Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN I 2 15 I 3 I NCG510500 111 12 I 18/07/31 I17 18 I S J 19 LG] 201 I
211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 1 1 1 1 166
Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA ----------------------Reserved-------------------
67 1.0 70 71 tyI I 72 n u 73 �74 751
u I I I 1 1 1 I80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
09:30AM 18/07/31
16/10/17
General Store of Denver
6360 NC Hwy 150 E
Exit Time/Date
Permit Expiration Date
Sherrills Ford INC 28673
11:00AM 18/07/31
20/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Matt Westendorf//704-526-2049 /
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Frank Craven,6360 NC Hwy 150 E Sherrills Ford NC
28673/President/704-483-2686/7044835468 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Edward Watson MRO GW/// DocuSigned by:
// �n 8/2/2018
ECA4CEBF8F85F415...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax NumbersDocusigned by: Date
*-. w H P:zt t.
EAF161FB69A2D84A3
8/2/18
...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont.)
NCG510500 111 121 18/07/31 1 17 18 ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
During the site visit, it was discovered that the treatment system had been turned off by by directive of
the UST Trust Fund in August 2017 and re -started in March of 2018. No notification was provided to
MRO-DWR that the system was being taken out of service. Conditons for general permit Section E
Reporting Requirements states that the DWR- MRO is to be notified within 24 hours of system shut off
or failure. Failure to report similar incidence in the future may result in the issuance of a Notice of
Violation(NOV).
Other than the notification, the system was reviewed and found to be in compliance with the permit. A
new flow meter was installed on July 2, 2018. A copy of the receipt of purchase has been provided to
the MRO and will be used as proof of meter calibration.
Waste manifests for spent carbon was also recieved by the MRO.
The system is permitted to discharge up to 50,000 gallons per day(GPD)of treated effluent. However,
the average dailty output for this system is about 239 GPD.
Page#
Permit: NCG510500 Owner - Facility: General Store of Denver
Inspection Date: 07/31/2018 Inspection Type: Compliance Evaluation
has improved system
❑
❑
operations.
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
0
❑
application?
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑ ❑
❑
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The Dermit does not exDire until 9/30/2020. The Dermit renewal aDDlication should be
submitted 180 days prior to the expiration of the permit.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Operation and maintenance lops were reviewed during the site visit.
Durina the site visit. both recovery wells were reviewed. The reauested correction to lower
the riser pipem has been made to RW -5 to to prevent the top of the well from hitting the
gallery cover. Also, bolsters were placed around RW -5 to prevent additional damage from
occuring to the well gallery box. This seems to have help to protect the well as no additional
damage appeared to be present. However, it was suggested that high visibility paint be
applied to the bolsters to make the RW more visible.
The air stripper was serviced during system shut -down.
Surge tank floats were replaced this past June 2018. This change
has improved system
❑
❑
operations.
❑
❑
❑
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
0 ❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑ ❑
❑
0
If effluent (diffuser pipes are required) are they operating properly?
❑ ❑
0
❑
Comment: No flow was observed at the outfall.
The system outfall pipe has some vexation growing around the outfallpipe. The outfall is to
remain clear of debrids and obstructions.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Page#
3
Permit: NCG510500
Inspection Date: 07/31/2018
Flow Measurement - Effluent
Owner - Facility: General Store of Denver
Inspection Type: Compliance Evaluation
(If units are separated) Does the chart recorder match the flow meter?
Comment: A new flow meter has been installed. The MRO has received an email copy of the
purchase and will use this as evidence of calibration within the calender year.
Yes No NA NE
❑ ❑ ■ ❑